York B1CH180 Heat Anticipator Setpoints, Heat Anticipator Setting, Checking Supply AIR CFM

Page 16

511.06-N3Y

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct. Too high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint will give shorter “ON” cycles and may result in the lowering of the temperture within the conditioned space. Refer to the Heat Anticipator Setting Table for the required heat anticipator setting.

TABLE 13 - HEAT ANTICIPATOR SETTING

HEATER

VOLTAGE

 

SETTING, AMPS

 

KW

 

TH1

TH2

 

 

18

 

 

0.29

-

 

36

208/230-3-60

 

0.29

0.29

 

54

 

0.29

0.58

 

 

 

 

72

 

 

0.58

0.58

 

18

 

 

0.29

-

 

36

460-3-60

 

0.29

0.29

 

54

 

0.29

0.29

 

 

 

 

72

 

 

0.29

0.29

 

18

 

 

0.29

-

 

36

575-3-60

 

0.29

0.29

 

54

 

0.29

0.29

 

 

 

 

72

 

 

0.29

0.29

 

CHECKING SUPPLY AIR CFM

 

 

FIG.9 - BELT ADJUSTMENT

The RPM of the supply air blower will depend on the required CFM, the unit options/accessories and the static resistances of both the supply and the return air duct systems. With this information, the RPM for the supply air blower and the motor pulley adjustment (turns open) can be determined from the Blower Performance Data Tables.

High speed drive accessories (containing a smaller blower pulley and a shorter belt) are available for applications requiring the supply air blower to produce higher CFM’s and/or higher static pressures. Use Model 1LD0416 for 15 ton units and Model 1LD0417 for 20 ton units. Refer to the Blower Motor and Drive Data table.

Note the following:

1.The supply air CFM must be within the limitations shown in Unit Application Data table.

2.Pulleys can be adjusted in half turn increments.

3.The tension on the belt should be adjusted as shown in the Belt Adjustment Figure.

Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer.

To check the supply air CFM after the initial balancing has been completed:

1.Remove the two 5/16" dot plugs from the blower motor and the filter access panels shown in the Dimensions and Clearances Figure.

2.Insert at least 8" of 1/4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil.

NOTE: The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pres- sure will not affect the static pressure readings.

3.Using an inclined manometer, determine the pressure drop across a dry indoor coil. Since the moisture on an indoor coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To assure a dry coil, the compressors whould be de-activated while the test is being run.

4.Knowing the pressure drop across a dry coil, the actual CFM through the unit and clean 2" filters, can be determined from the curve in the figure below.

WARNING: Failure to properly adjust the total system air quantity can result in extensive blower damage.

After readings have been obtained, remove the tubes and reinstall the two 5/16" dot plugs that were removed in Step 1.

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST MEASUREMENTS TO ASSURE A DRY INDOOR COIL.

BELT DRIVE BLOWER

All units have belt drive single-speed blower motors. The variable pitch pulley on the blower motor can be adjusted to obtain the desired supply air CFM.

FIG. 10 - PRESSURE DROP ACROSS A DRY INDOOR COIL VS SUPPLY AIR CFM

16

Unitary Products Group

Image 16
Contents Sunline 2000 Single Package Heat Pumps Table of Contents Installation Service Access Power and Control WiringFixed Outdoor AIR Intake Damper Condensate DrainTypical Field Wiring Control Wire SizesPower EXHAUST/BAROMETRIC Relief Damper and Rain Hood Option Enthalpy SET Point AdjustmentOptional Electric Heaters Electric Heat Application DataEnthalpy Setpoint Adjustment Physical Data Return AIR Supply AIR Outdoor AIR Utilities Entry DataOpening Hole Size Used for Point Loads Unit Point Loads LBSBlower Motor CFM Pulley Speed Turns RPM ESP BHP OpenSpeed RPM Turns ESP BHP Open Static Resistances Power Exhaust PerformanceBlower Motor and Drive Data Electrical Data Basic Units Motor SupplyFuse Size FLA RLA LRA Amps Each Fuse SizeOperation Cooling SystemPreliminary Operation Cooling Cooling Sequence of OperationHeat Anticipator Setting Heater Voltage SETTING, Amps TH1 TH2Heat Anticipator Setpoints Checking Supply AIR CFMDefrost Sequence of Operation Lockout ControlMaintenance Normal MaintenanceT2 80 Minute Setting T3 110 Minute Setting Motors511.06-N3Y Unitary Products Group

B1CH240, B1CH180 specifications

The York B1CH240 and B1CH180 are two prominent models in the commercial HVAC (Heating, Ventilation, and Air Conditioning) sector, known for their efficiency and reliability in demanding environments. Both units are designed with the latest technologies to provide optimal climate control, making them suitable for a variety of applications including offices, retail spaces, and industrial environments.

One of the main features of the York B1CH series is its high energy efficiency. These models are equipped with advanced inverter technology, allowing them to adjust their cooling and heating output based on the current demand. This not only minimizes energy consumption but also reduces operating costs, making them an environmentally friendly choice. The units also meet or exceed industry standards for energy efficiency, complying with stringent regulations set forth by organizations such as ASHRAE and ENERGY STAR.

Another key characteristic of the B1CH240 and B1CH180 is their adaptability. These units come with customizable settings and programmable controls, enabling users to optimize performance based on specific needs. Whether it is cooling an entire building or maintaining comfortable temperatures in different zones, the B1CH series can be tailored to fit the unique demands of any space.

In terms of technology, York has integrated advanced refrigerant management into the B1CH series. The units utilize R-410A refrigerant, which not only enhances cooling efficiency but also minimizes environmental impact. This refrigerant is known for its higher performance and lower toxicity compared to traditional options, aligning with global efforts to reduce ozone depletion.

Durability is another hallmark of the York B1CH240 and B1CH180 models. Constructed from high-quality materials, these units are designed to withstand the rigors of everyday use while maintaining peak performance. The units are also equipped with comprehensive diagnostic and monitoring systems that alert users to any potential issues before they escalate, ensuring uninterrupted operation and reducing maintenance downtime.

Moreover, the B1CH series features a quiet operation mode, making them ideal for noise-sensitive environments. The design incorporates sound-dampening materials and efficient airflow dynamics to ensure that the units operate at a low noise level while providing powerful heating and cooling.

In summary, the York B1CH240 and B1CH180 models stand out in the HVAC market for their energy efficiency, adaptability, advanced refrigerant management, durability, and quiet operation. Together, these features make them an excellent choice for businesses seeking reliable and cost-effective climate control solutions. Whether for new construction or retrofitting existing spaces, these units are poised to meet the diverse needs of commercial and industrial applications.