DEFROST SEQUENCE OF OPERATION

These heat pumps have a unique “ambient modified” time-temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control will shorten the defrost initiation time periods above 35° F and will extend the defrost initiation time periods below 35° F. The control is factory set to defrost at 110 minutes (T3), but it can be field adjusted to defrost at 80 minutes (T2) or 50 minutes (T1) in areas with high humidity.

The curve in the Deforst Initation Times Figure shows how defrost initiation times are automatically compensated for changes in outdoor temperature.

EXAMPLE: If the timer is factory set on pin T-3 (110 minutes at 35° F outdoor) and the outdoor temperature climbs to 45° , the time initiation cycle will decrease to every 100 minutes.

If the outdoor temperature drops to 10° F where ice is less likely to form, the 110 minute interval will extend to every 150 minutes.

Two requirements must be met before a defrost cycle can be initiated.

1.The defrost time cycle must be complete.

2.The liquid line temperature must be less than 28° F.

Defrost will terminate when the liquid line sensor reaches 55° F or after 10 minutes. If both or just one circuit defrosts, electric heat is energized.

The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes.

During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 1/2" long, 3/16" apart and are mounted on a white base.

511.06-N3Y

LOCKOUT CONTROL

Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode:

1.The discharge line temperature reaches 255° F (215° F reset) or,

2.The discharge pressure reaches 398 PSIG (310 PSIG reset) or,

3.The suction line freezestat equals 26° F (38° F reset) or,

4.The low-pressure cut-out equals 7 PSIG (22 PSIG reset).

Alock-out will energize the emergency heat light on the thermostat and the red LED light on the unit relay board.Turning the thermostat switch to “Off” then back to “On”, will reset the system.

NOTICE TO OWNER:

If a lockout occurs, check for the following problems before calling a serviceman:

1.Dirty filters.

2.Snow accumulation.

3.Leaf or debris blockage.

After eliminating the problem, attempt to restart the system as follows:

turn the system switch on the thermostat to its “OFF” position for 10 seconds.

turn it back to its original position.

If the unit doesn’t start, call a serviceman.

NOTE: Models with an anti-recycle accessory will have a 5-minute delay before starting.

FIG. 11 - DEFROST INITIATION TIMES

Unitary Products Group

17

Image 17
Contents Sunline 2000 Single Package Heat Pumps Table of Contents Installation Power and Control Wiring Service AccessFixed Outdoor AIR Intake Damper Condensate DrainControl Wire Sizes Typical Field WiringEnthalpy SET Point Adjustment Power EXHAUST/BAROMETRIC Relief Damper and Rain Hood OptionOptional Electric Heaters Electric Heat Application DataEnthalpy Setpoint Adjustment Physical Data Opening Hole Size Used for Utilities Entry DataReturn AIR Supply AIR Outdoor AIR Unit Point Loads LBS Point LoadsSpeed Turns RPM ESP BHP Open Blower Motor CFM PulleySpeed RPM Turns ESP BHP Open Blower Motor and Drive Data Power Exhaust PerformanceStatic Resistances Motor Supply Electrical Data Basic UnitsFuse Size FLA RLA LRA Amps Each Fuse SizeCooling System OperationPreliminary Operation Cooling Cooling Sequence of OperationHeater Voltage SETTING, Amps TH1 TH2 Heat Anticipator SettingHeat Anticipator Setpoints Checking Supply AIR CFMLockout Control Defrost Sequence of OperationNormal Maintenance MaintenanceT2 80 Minute Setting T3 110 Minute Setting Motors511.06-N3Y Unitary Products Group

B1CH240, B1CH180 specifications

The York B1CH240 and B1CH180 are two prominent models in the commercial HVAC (Heating, Ventilation, and Air Conditioning) sector, known for their efficiency and reliability in demanding environments. Both units are designed with the latest technologies to provide optimal climate control, making them suitable for a variety of applications including offices, retail spaces, and industrial environments.

One of the main features of the York B1CH series is its high energy efficiency. These models are equipped with advanced inverter technology, allowing them to adjust their cooling and heating output based on the current demand. This not only minimizes energy consumption but also reduces operating costs, making them an environmentally friendly choice. The units also meet or exceed industry standards for energy efficiency, complying with stringent regulations set forth by organizations such as ASHRAE and ENERGY STAR.

Another key characteristic of the B1CH240 and B1CH180 is their adaptability. These units come with customizable settings and programmable controls, enabling users to optimize performance based on specific needs. Whether it is cooling an entire building or maintaining comfortable temperatures in different zones, the B1CH series can be tailored to fit the unique demands of any space.

In terms of technology, York has integrated advanced refrigerant management into the B1CH series. The units utilize R-410A refrigerant, which not only enhances cooling efficiency but also minimizes environmental impact. This refrigerant is known for its higher performance and lower toxicity compared to traditional options, aligning with global efforts to reduce ozone depletion.

Durability is another hallmark of the York B1CH240 and B1CH180 models. Constructed from high-quality materials, these units are designed to withstand the rigors of everyday use while maintaining peak performance. The units are also equipped with comprehensive diagnostic and monitoring systems that alert users to any potential issues before they escalate, ensuring uninterrupted operation and reducing maintenance downtime.

Moreover, the B1CH series features a quiet operation mode, making them ideal for noise-sensitive environments. The design incorporates sound-dampening materials and efficient airflow dynamics to ensure that the units operate at a low noise level while providing powerful heating and cooling.

In summary, the York B1CH240 and B1CH180 models stand out in the HVAC market for their energy efficiency, adaptability, advanced refrigerant management, durability, and quiet operation. Together, these features make them an excellent choice for businesses seeking reliable and cost-effective climate control solutions. Whether for new construction or retrofitting existing spaces, these units are poised to meet the diverse needs of commercial and industrial applications.