FEATURES

All models are available with a wide variety of factory- mounted options such as electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guards to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over- head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizon- tal duct, remove the supply and return air panels on the rear of the unit.

All models are available with these “factory mounted” outdoor air damper options:

Single enthalpy economizer

Motorized outdoor air damper

Supply air blowers are equipped with either direct drive or belt drive that can be adjusted to meet the exact require- ments of the job.

All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo- nents.

Simplicity® Controls - Simplicity® control boards have standardized a number of features previously available only as options or by utilizing additional controls.

Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis- tance. Optionally, the control board can be pro- grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

255027-YTG-B-0507

Fan Delays - Fan on and fan off delays are fully pro- grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA listed.

Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty

Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni- form distribution of air across the heating elements. Every element is fully protected against excessive tem- perature by thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.

BAS Controls - York’s Sunline™ series units offer fac- tory mounted BAS controls such as Simplicity® INTELLI- Comfort™, Novar, Honeywell, Johnson, and CPC.

4

Unitary Products Group

Image 4
Contents Description Single Package Heat Pump UnitsHigh Efficiency Table of Contents Product Nomenclature 048 C00 a 2 a AA 1 0 1 2 4 aFeatures FACTORY-INSTALLED Options Unit CutawayFIELD-INSTALLED Accessories Sound Power RATING1 Capacity RatingBP036 Cooling Capacities 3 TON 75F 85FBP048 Cooling Capacities 4 TON 115F 125FCapacity Input Return Dry Bulb F BP060 Cooling Capacities 5 TON BP072 Cooling Capacities 6 TON Capacity1 Input Return Dry Bulb F BP036-072 Heating Capacities DB FAvailable External Static Pressure IWG1 AIR Flow CFM RPM AIR Available External Static Pressure IWG1 Flow 1000 789 527 831 567 874 602 1000 833 564 879 605 1200 961 696 1003 716 1045 725 1086 723 1000 862 453 901 498 1500 935 658 967 721 1001 1221 1088 1262 1119 1314 1150 1372 1183 1435 1217 1500 2300 MED Static Resistances Belt Drive Blower Motor and Drive DataElectric Heater CFM Limitations Amps Ampacity Size Each FLA 111.6 YTG-B-0507 YTG-B-0507 YTG-B-0507 YTG-B-0507 036 YTG-B-0507 Electric Heat Correction Factors Physical DataVoltage LIMITATIONS1 Typical Power Wiring Typical Control WiringUnit Dimensions Front View Unit with Fixed Outdoor AIR/MOTORIZED Damper Rainhood DISCONNECT/BLOWER Access Location Utilities Entry Minimum ClearancesTypical Applications Operating Weights LBS Four and SIX Point LoadingGeneral Guide SpecificationsDescription Indoor Evaporator FAN Assembly Manual Outdoor AIR Damper YTG-B-0507 YTG-B-0507