York BP 036 warranty FIELD-INSTALLED Accessories

Page 6

day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventila- tion. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Com- fort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algo- rithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLI- Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.

Simplicity® INTELLI-Comfort™ with ModLINC CON- TROL - The York® Simplicity® INTELLI-Comfort™ with ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi- tional control to translate communications from MOD- BUS to the BACnet MSTP protocol.

Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system control- ler is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto- mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

Factory installed Smoke Detectors in the Return Air, may be subjected to freezing temperatures during "off" times due to Out Side Air infiltration. These Smoke Detectors have an operational limit of 32°F to 131°F. Smoke Detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.

255027-YTG-B-0507

STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.

BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connec- tions for applications in cold environments to reduce freezing drain lines.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped inside the unit to prevent ship- ping damage. These must be field installed for toolless operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in /plug-in damper assembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in /plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

ELECTRIC HEATERS wired for single point power sup- ply. These nickel chromium heater elements are pro- vided with limit and automatic reset capability to prevent operation at excessive temperatures.

ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.

6

Unitary Products Group

Image 6
Contents Single Package Heat Pump Units DescriptionHigh Efficiency Table of Contents Product Nomenclature 048 C00 a 2 a AA 1 0 1 2 4 aFeatures FACTORY-INSTALLED Options Unit CutawayFIELD-INSTALLED Accessories Sound Power RATING1 Capacity RatingBP036 Cooling Capacities 3 TON 75F 85FBP048 Cooling Capacities 4 TON 115F 125FCapacity Input Return Dry Bulb F BP060 Cooling Capacities 5 TON BP072 Cooling Capacities 6 TON Capacity1 Input Return Dry Bulb F BP036-072 Heating Capacities DB FAvailable External Static Pressure IWG1 AIR Flow CFM RPM AIR Available External Static Pressure IWG1 Flow 1000 789 527 831 567 874 602 1000 833 564 879 605 1200 961 696 1003 716 1045 725 1086 723 1000 862 453 901 498 1500 935 658 967 721 1001 1221 1088 1262 1119 1314 1150 1372 1183 1435 1217 1500 2300 MED Belt Drive Blower Motor and Drive Data Static ResistancesElectric Heater CFM Limitations Amps Ampacity Size Each FLA 111.6 YTG-B-0507 YTG-B-0507 YTG-B-0507 YTG-B-0507 036 YTG-B-0507 Physical Data Electric Heat Correction FactorsVoltage LIMITATIONS1 Typical Power Wiring Typical Control WiringUnit Dimensions Front View Unit with Fixed Outdoor AIR/MOTORIZED Damper Rainhood DISCONNECT/BLOWER Access Location Utilities Entry Minimum ClearancesTypical Applications Operating Weights LBS Four and SIX Point LoadingGuide Specifications GeneralDescription Indoor Evaporator FAN Assembly Manual Outdoor AIR Damper YTG-B-0507 YTG-B-0507