United States Stove 3500PB, 3700PB owner manual Combustible Wall Chimney Connector Pass-Throughs

Page 11

Combustible Wall Chimney Connector Pass-Throughs

NOTES:

Method A. 12” (304.8 mm) Clearance to Combustible Wall Member: Using a minimum thickness 3.5” (89 mm) brick and a 5/8” (15.9 mm) minimum wall thickness clay liner, construct a wall pass-through. The clay liner must conform to ASTM C315 (Standard Specifica- tion for Clay Fire Linings) or its equivalent. Keep a minimum of 12” (304.8 mm) of brick masonry between the clay liner and wall combustibles. The clay liner shall run from the brick masonry outer surface to the inner surface of the chimney flue liner but not past the inner surface. Firmly grout or cement the clay liner in place to the chimney flue liner.

Method B. 9” (228.6 mm) Clearance to Combustible Wall Member: Using a 6” (152.4 mm) inside diameter, listed, factory-built Solid- Pak chimney section with insulation of 1” (25.4 mm) or more, build a wall pass-through with a minimum 9” (228.6 mm) air space be- tween the outer wall of the chimney length and wall combustibles. Use sheet metal supports fastened securely to wall surfaces on all sides, to maintain the 9” (228.6 mm) air space. When fastening supports to chimney length, do not penetrate the chimney liner (the inside wall of the Solid-Pak chimney). The inner end of the Solid- Pak chimney section shall be flush with the inside of the masonry chimney flue, and sealed with a non-water soluble refractory ce- ment. Use this cement to also seal to the brick masonry penetra- tion.

Method C. 6” (152.4 mm) Clearance to Combustible Wall Member: Starting with a minimum 24 gage (.024” [.61 mm]) 6” (152.4 mm) metal chimney connector, and a minimum 24 gage ventilated wall thimble which has two air channels of 1” (25.4 mm) each, construct a wall pass-through. There shall be a minimum 6” (152.4) mm sep- aration area containing fiberglass insulation, from the outer surface of the wall thimble to wall combustibles. Support the wall thimble, and cover its opening with a 24-gage minimum sheet metal sup- port. Maintain the 6” (152.4 mm) space. There should also be a support sized to fit and hold the metal chimney connector. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner.

Method D. 2” (50.8 mm) Clearance to Combustible Wall Mem- ber: Start with a solid-pak listed factory built chimney section at least 12” (304 mm) long, with insulation of 1” (25.4 mm) or more, and an inside diameter of 8” (2 inches [51 mm] larger than the 6” [152.4 mm] chimney connector). Use this as a pass-through for a minimum 24-gauge single wall steel chimney connector. Keep solid-pak section concentric with and spaced 1” (25.4 mm) off the chimney connector by way of sheet metal support plates at both ends of chimney section. Cover opening with and support chimney section on both sides with 24 gage minimum sheet metal supports. See that the supports are fastened securely to wall surfaces on all

sides. Make sure fasteners used to secure chimney flue line.

1.Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through system and the chimney wall, to but not past the inner flue liner face.

2.A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.

11

Image 11
Contents Cast Iron Room Heater Table of Contents Stove Safety Adequate Provision of Air Before installing your stoveSpecifications Floor Protection Installation3500, 3500PB 3700, 3700PB Installation ClearancesChimney Connection Do not use the connector pipe as a chimneyChimney Height ChimneyFactory Built Chimney Masonry Chimney Combustible Wall Chimney Connector Pass-Throughs Air controls Operating Your StoveFuel First operation of stoveOvernight Burning RefuelingAsh Removal Care of Glass Stove MaintenanceTrouble Shooting Fire Burns too Quickly Smoke in RoomStove Limited Warranty Warranty Policy & Procedures12 13 14 3500, 3500PB Parts Diagram & List410 3700, 3700PB Parts Diagram & ListUssc