Installation

CLEARANCES

Your Forester stove has been tested and listed for installation in residential, mobile home, and alcove applications in accordance with the clearances given in FIGURES 3-4 and TABLE 1.

NOTE: Distance “D” on the left-hand side of your Forester stove may need to be greater than the minimum required clearance for suitable access to the control panel.

FIGURE 3

SIDEWALL / CORNER

MINIMUM CLEARANCES

PARALLEL

A - Backwall to heater

8.00” / 203mm

 

B - Backwall to flue

1.00” / 25mm

 

C - Sidewall to flue

7.50” / 191mm

CORNER

D - Sidewall to edge of unit

4.00” / 100mm

E - Adjacent wall to unit

2.00” / 50mm

ALCOVE

F - Alcove depth

25.00” / 635mm

 

G - Alcove Hieght

47.00”/ 1194mm

 

Alcove Width

26.50” / 673mm

TABLE 1

MINIMUM CLEARANCES

(inches/mm)

FIGURE 4

MINIMUM ALCOVE CLEARANCES

6

USSC

Image 6
Contents Ussc Table of Contents Safety Precautions Specifications Safety and EPA ComplianceFuel Considerations Installation Installation OptionsFloor Protection Clearances AlcoveMaximum Venting Distance Pellet Vent InstallationVenting Requirements Pellet Vent TypeVent Termination Clearances Through the Wall Installation Recommended Installation Through the ROOF/CEILING InstallationSpecial Mobile Home Requirements Understanding your stove How your stove worksSTART-UP Procedure Shut Down ProcedureOperation Daily Operation MaintenanceSafety and Convenience Features Exhaust SystemASH Disposal Check and Clean the HopperInterior Chambers Door and Glass GasketsTrouble Shooting ProblemParts Diagram Parts List Wiring Diagram Ussc Ussc