Instructions for Installation (cont’d)

Temperature-Pressure Relief Valve

WARNING

At the time of manufacture this water heater was provided with a combination temperature-pressures relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, and the current edition of ANSI Z21.22 • CSA 4.4 and the code requirements of ASME. If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4 by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials.

The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 lbs./sq. in.) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3412 equal BTU/Hr. rate.)

Your local jurisdictional authority, while mandating the use of a temperature-pressure relief valve complying with ANSI Z21.22 • CSA 4.4 and ASME, may require a valve model different from the one furnished with the water heater.

Compliance with such local requirements must be satisfied by the installer or end user of the water heater with a locally prescribed temperature-pressure relief valve installed in the designated opening in the water heater in place of the factory furnished valve.

For safe operation of the water heater, the relief valve must not be removed from it’s designated opening or plugged.

The temperature-pressure relief valve must be installed directly into the fitting of the water heater designated for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet, or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6” air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

The Discharge Pipe:

Must not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Must not be plugged or blocked.

Must be of material listed for hot water distribution.

Must be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Must terminate at an adequate drain.

Must not have any valve between the relief valve and tank.

WARNING

The temperature-pressure relief valve must be manually operated at least once a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.

HOTCOLD

HOT COLD

CONDUIT

TEMPERATURE-

PRESSURE RELIEF VALVE

DISCHARGE PIPE (Do not cap or plug)

6” AIR GAP

FLOOR DRAIN

12

Image 12
Contents Series Six Safety Instructions Safety Instructions cont’d Table of Contents Product Specifications Customer In formationHR630SJRT HR630DJRT HR630SJLS HR630DJLS HR640SJRT HR640DJRT HR640SJRS HR640DJRS HR640SJLS HR640DJLS HR652SJRT HR652DJRT HR650SJRS HR650DJRS HR650SJLSHR650DJLS HR666SJRT HR666DJRT HR682SJRT HR682DJRT Product Specifications HR6120SJRT HR6120DJRTAccessories and Tools Needed AccessoriesAdditional Tools Needed When Sweat Soldering ToolsInstallation Instructions Removing the Old Water HeaterInstructions for Installation cont’d Typical InstallationLocating The New Water Heater Water Piping Valve and Pipe InsulationTemperature-Pressure Relief Valve Wiring Diagrams Standard Wiring for Single Element 240 VoltFilling the Water Heater Wiring Installation Checklist Model Rating PlateService and Maintenance Temperature RegulationTemperature Settings ThermostatsService and Maintenance cont’d Thermostat AdjustmentsTemperature-Pressure Relief Valve Operation Anode Rod InspectionThermostat Removal/Replacement DrainingElement Cleaning Replacement Thermostat Removal cont’dLower Thermostat Element Cleaning Replacement cont’d Drain Valve Washer ReplacementService Troubleshooting Start Up ConditionsOperational Conditions Troubleshooting cont’d Not Enough or no HOT WaterLeakage Checkpoints Page Repair Parts List Repair Parts List cont’d This is a Repair Parts LIST, not a Packing ListSee Repair Parts List cont’d See Note on Repair Parts List cont’d Model Number Serial Number Part Description Repair Parts List cont’d Repair Parts List cont’d Maytag State Page Warranty Full ONE Year WarrantyLimited Parts Warranty Limited Tank Warranty Against Leaks