Premier user manual Fire Alarm Control Panel Safety Issues, Purpose of a Fire Alarm System

Page 3

PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

1. FIRE ALARM CONTROL PANEL SAFETY ISSUES

There is no need to open this fire alarm during normal operation. Any work carried out on this system must be performed by a competent person who is familiar with this type of system.

This equipment will operate safely provided it has been installed correctly in compliance with the Installation Manual.

It is recommended that the system is serviced frequently. It is customary to arrange a regular maintenance contract with a competent organisation. (Ask the installation company for recommendations). The system needs a thorough maintenance check annually at the very minimum.

If any part of this Fire Alarm Control Panel becomes damaged, contact the company responsible for system maintenance to arrange repair / replacement.

C E European Union Directives Conformance Statement

This product has been manufactured in conformance with the requirements of all applicable EU Council Directives. The Declaration of Conformance for this product is located at the following Address: GLT Exports Ltd, 72-78 Morfa Road, Hafod, Swansea, SA1 2EN, United Kingdom

2. THE PURPOSE OF A FIRE ALARM SYSTEM

A Fire Alarm System is used to provide an early warning of a fire, so that the property can be evacuated and the fire extinguished if it can be safely tackled, or the local fire brigade called, according to the company evacuation procedure.

Alarms can come from Smoke or Heat Detectors, or manually be a person operating a Manual Call Point.

Split the system into Zones, each covering a different area of a building. This will indicate which area of the system is giving the alarm (or fault).

During an alarm, the panel will start its sounders, and indicate which zone has the fire. It will also activate its auxiliary relay.

Fault Monitoring

All circuits must be checked for line integrity. If a part of the system has a problem which may affect its operation, a fault warning must be given by the fire alarm panel (LED & buzzer indication). The fault relay will also activate.

Disablements

An engineer may be required to work on part of a system, while the system is still active (eg extending a detection zone). During such circumstances, it would be advisable to disable that zone, so that it will not give false alarms. Similarly you may wish to disable a zone that has a fault that has not been fixed, or a zone covering an area with a temporary unusual environment, such as an area which is dusty because of construction work etc.

Delays

In public places, it may be desirable to delay the activation of an alarm until the responsible person has verified the cause of the alarm. (This would avoid a panic evacuation caused by a smoky room, or a maliciously activated call point.) On verification of the alarm, the sounders can be started by pressing the override button, or the panel can be reset in the case of a false alarm. If a delay has been set, it must be recorded on the system configuration chart at the back of this manual.

Power Supply Equipment- General Description.

The NPSX FACP has an integral linear power supply capable of supplying 1.2 amps in total. It contains a current limited output for charging sealed lead acid batteries (7 Ah maximum). The PSE is monitored for main supply failure, the battery not taking a charge and low battery voltage. If the battery voltage drops below approximately 20VDC (a fault condition), the battery charging current will be turned off , thus stopping charging. This PSE is only capable of supplying power to the CIE, and is not designed for any other use.

Approved Document No: GLT.MAN-102

PAGE 3

Issue: 1.3 Authorised: GH

Date: 9/6/2004

 

Image 3
Contents Page Purpose of a Fire Alarm SYSTEM……………………………………………… Purpose of a Fire Alarm System Fire Alarm Control Panel Safety IssuesDaily Inspection Responsible person mustAccessed Control Available to Authorised Users only Panel Indications & ControlsGeneral Controls LED Condition Panel Status HOW the Premier SX Indicates AN Alarm Fire / Zones Building evacuation procedure should now be followedFire Condition Different Types of Fault Fault ConditionSounder Fault Earth FaultTo Enable a Zone AND/OR External Sounders DisablementsReasons for Disabling Certain Parts of a Fire Alarm System To Disable a Zone AND/OR External SoundersWhat is a Sounder Delay Using Sounder DelaysFire Zone Information Fire Alarm System SummaryFire Alarm LOG Book Maintenance Work False Alarms ALL Events Other than Maintenance Work or False Alarms Commissioning the SYSTEM, Including P.S.E DESIGN, Installation & Commissioning CertificatesName in block letters Installation & Commissioning Recommendations Address Address Address