Johnson Controls BQ 060, BQ 036, BQ 048 Safety Controls, Compressor Protection, Flash Codes, Reset

Page 33

364985-XIM-B-0508

ing is still present at the conclusion of the ASCD, the UCB will re-energize the compressor.

Should a freezestat open three times within two hours of operation, the UCB will lock-out the compressor and flash a code (see Table 32).

LOW AMBIENT COOLING

To determine when to operate in low ambient mode, the UCB has a pair of terminals connected to a temper- ature-activated switch set at 45ºF. When the low ambi- ent switch is closed and the thermostat is calling for cooling, the UCB will operate in the low ambient mode.

Low ambient mode operates the compressors in this manner: 10 minutes on, 5 minutes off. The indoor blower is operated throughout the cycle. The 5-minute off period is necessary to defrost the indoor coil.

Low ambient mode always begins with compressor operation. Compressor minimum run time may extend the minutes of compressor operation. The defrost cycle will begin immediately following the elapse of the mini- mum run time.

When operating in low ambient mode, the UCB will not lockout the compressor due to a freezestat trip. How- ever, a freezestat trip will de-energize the compressor. If the call for cooling is still present at the end of the ASCD and the freezestat has closed, the unit will resume operation.

SAFETY CONTROLS

The unit control board monitors the following inputs for the cooling system:

1.A suction line freezestat to protect against low evaporator temperatures due to a low airflow or a low return air temperature, (opens at 26 ± 5 °F and resets at 38 ± 5°F).

2.A high-pressure switch to protect against exces- sive discharge pressures due to a blocked con- denser coil or a condenser motor failure, (opens at 380 ± 10 psig and resets at 300 ± 10 psig).

3.A low-pressure switch to protect against loss of refrigerant charge, (opens at 7 ± 3 psig and resets at 22 ± 5 psig).

The above pressure switches are hard-soldered to the unit. The refrigeration system is monitored and con-

trolled. On any fault, the system will be affected by any safety/preventive action.

The unit control board monitors the temperature limit switch of the electric heat.

COMPRESSOR PROTECTION

The compressor also has inherent (internal) protection. If there is an abnormal temperature rise in a compres- sor, the protector will open to shut down the compres- sor. The UCB incorporates features to minimize compressor wear and damage. An anti-short cycle delay (ASCD) is utilized to prevent operation of a com- pressor too soon after its previous run. Additionally, a minimum run time is imposed any time a compressor is energized.

The ASCD is initiated on unit start-up and on any com- pressor reset or lock-out.

FLASH CODES

The UCB will initiate a flash code associated with errors within the system. Refer to UNIT CONTROL BOARD FLASH CODES Table 32.

RESET

Remove the call for cooling, by raising thermostat set- ting higher than the conditioned space temperature. This resets any pressure or freezestat flash codes.

HEATING SEQUENCE OF OPERATIONS

WITH OR WITHOUT ELECTRIC HEAT

When the thermostat calls for the first stage of heating, the low voltage control circuit is completed between “R” and “W1”. The 24vac signal is passed through the UCB to the “Y” contact on the Defrost Control (DC) assuring the reversing valve cannot be energized, except during defrost. If the ASCD timer is satisfied the UCB will energize compressor contactor M1.

If the compressor alone cannot satisfy the heating requirements, a second stage call from the thermostat completes the circuit between “R” and “W2”. This 24vac signal is passed through the UCB to the electric heat section (if available). The total available kW of electric heat will be energized on a call for “W2”.

Johnson Controls Unitary Products

33

Image 33
Contents Installation Table of Contents List of Tables List of FiguresGeneral Safety ConsiderationsInspection ReferenceTon Sunline Simplicity Model Number Nomenclature Product NomenclatureInstallation Safety Information InstallationLimitations Unit Application Data BQClearances Rigging and HandlingDuctwork Condensate DrainService Access CompressorsFilters Typical Power Wiring Control Wire Sizes Power and Control WiringOPTIONS/ACCESSORIES ThermostatElectric Heater CFM Limitations Minimum Position Adjustment Enthalpy Setpoint Adjustment BQ 6 Point Loads Weight Distribution BQ 4 Point Loads Weight DistributionPhysical Data Operating Weights LBSMCA Pwr Max Size Motors Fuse XIM-B-0508 Pwr Max MCA1 Voltage LIMITATIONS1 Electric Heat Correction FactorsUnit with Economizer Rainhood Minimum Clearances Unit Dimensions Rear ViewRPM BHP BHP RPM BHP Belt Drive RPM Selection Belt Drive Blower Motor and Drive DataStatic Resistances Drive Selection Factor Phasing Supply AIR BlowersChecking Supply AIR CFM Operation Sequence of Operations OverviewCooling Sequence of Operation Cooling Operation Errors Reset Safety ControlsCompressor Protection Flash CodesHeat Anticipator Setpoints Electric Heat Limit Control SettingSTART-UP Cooling TroubleshootingXIM-B-0508 Unit Control Board Flash Codes Unit Flash CodesNormal Maintenance MaintenanceMotors Outdoor CoilXIM-B-0508 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK

BQ 048, BQ 036, BQ 060 specifications

Johnson Controls has established itself as a leading player in the HVAC and building management industries, and its BQ series of chillers - including the BQ 060, BQ 036, and BQ 048 - reflects this commitment to innovation and efficiency. These models are designed to provide advanced cooling solutions suitable for a variety of commercial applications.

The BQ 060 is particularly notable for its high-performance capabilities. With a cooling capacity of 60 tons, it utilizes variable-speed compressors, allowing it to adjust its performance based on the cooling demand. This flexibility not only enhances energy efficiency but also reduces operational costs. The unit incorporates advanced microprocessor controls that facilitate seamless integration with building management systems, enabling real-time monitoring and adjustments.

Moving on to the BQ 036, this model is engineered for facilities that require a smaller footprint but still demand reliability and efficiency. With a cooling capacity of 36 tons, it features a compact design without compromising on performance. The BQ 036 also employs environmentally friendly refrigerants, aligning with Johnson Controls' commitment to sustainability. Enhanced insulation and sound-dampening technologies make it an ideal choice for noise-sensitive environments, ensuring comfort without sacrificing efficiency.

The BQ 048 lies in between the two, with a capacity of 48 tons, making it versatile for medium-sized commercial buildings. Its design incorporates a modular approach, allowing for easy scalability in future expansions. This model also features energy recovery options that can utilize excess heat to improve overall efficiency, further solidifying its role in sustainable building practices. Its user-friendly interface enhances operability, simplifying management for building operators.

All three models of the BQ series share key characteristics, such as robust construction to withstand diverse environmental conditions, and low maintenance requirements thanks to their durable components. They utilize advanced technologies for temperature control and energy efficiency, including an intelligent controller that automates more routine tasks. Together, the BQ 060, BQ 036, and BQ 048 offer comprehensive solutions that cater to the growing demands of energy efficiency, sustainability, and reliability in modern building operations. With these chillers, Johnson Controls continues to lead the way in shaping the future of HVAC solutions.