Nordyne M1B, M1G, M1S, M1M owner manual Troubleshooting Direct Ignition Furnaces Including GAS GUN

Page 29

humidity requires higher temperatures for the same level of comfort. Check for proper humidity level in the home.

TROUBLESHOOTING -

DIRECT IGNITION FURNACES INCLUDING GAS GUN

Burner Motor Does Not Run—

Thermostat Calls For Heat

a. Check the electrical supply to the furnace. b. Be sure the furnace On-Off switch is in the

“ON” position.

c. Defective thermostat circuit - white and red thermostat low voltage leads (M1M*, M1B* models). If the burner motor or combustion fan runs, check:

Thermostat connections

Thermostat

d.No voltage to control module - determine if 24 volts (or 120 volts) is available to the control module. If voltage is not available check for:

Blown fuse, defective transformer, circuit breaker, no electrical supply.

Limit switch open.

Loose connections.

Combustion Blower Does Run - No Flame a. Defective centrifugal switch (M1B* Model).

Check the operation of centrifugal switch by removing end bell of the burner motor.

Clean contacts of motor.

If the contacts are closed, replace the motor.

b.Defective pressure switch (M1M* and M1G* 077, 090 Models) - check air tube and elec- trical connections.

c.Burner in purge mode - allow 75 seconds for flame establishing period.

d.Check for proper electrical connections at purge timer, control box, or gas valve.

e.Check for gas supply - gas line valve on, control lever on.

Control Module Is Powered—

Ignitor Does Not Heat Up

a. Disconnect ignitor leads at AMP receptacle and check for 120 volts at the plug during ignition sequence.

b. Replace ignition control if 120 volts is not available at AMP plug during ignition se- quence.

120 Volts Is Available At AMP Plug— Ignitor Does Not Heat Up

a. Disconnect power to the furnace.

b. Disconnect AMP plug to the ignitor, and check ignitor resistance with an ohm meter.

Set on RX1 scale.

Normal reading should be 40 - 75 ohms.

If above or below this rating at room tem- perature change ignitor.

c.Check for continuity from ignitor receptacle to burner.

Main Flame Ignites—

Burner Locks Out

a. Ignition control is not properly grounded. b. Defective ignition control.

c. Improper polarity of 120 volt power supply. d. Ignitor has hairline crack.

e. Improper gas pressure or burner air adjust- ment is not allowing flame to contact ignitor tip for flame rectification.

f. Misaligned ignitor does not allow flame to contact ignitor tip for flame rectification.

Burner Short Cycling —-

Thermostat Calls for Heat, Limit Switches Closed

a. Check for polarity. b. Check ground. c. Check flue.

d. Check combustion air. e. Check gas pressure. f. Check orifice.

g. Check the position of ignitor, a normal read- ing should be 40-75 ohms.

24 Volts Supplied To Gas Valve During

Ignition —

No Main Gas Flow

a. Gas valve may be defective. Replace if necessary.

b. Gas piping may be plugged. Check for adequate gas supply to gas valve at union.

Burner Operates—

Insufficient Heat

a. Check thermostat for proper setting and location. Thermostat should not be located where it will be affected by another heat source.

b. Check for clean filter and proper air flow. c. Check burner for proper gas firing rate. d. Be sure unit is not undersized for its thermal

load.

e. Check thermostat anticipator. The nominal anticipator setting is 0.4.

Burner Flame Without Motor Running

a. Gas valve stuck open, check gas valve for proper operation (replace if necessary) and inspect heat exchanger.

b.Check for 115 volts to the combustion blower motor; replace if necessary.

29

Image 29
Contents Leave These Instructions with the Homeowner B 056 a B W Table of ContentsMANUFACTURERWARRANTY, OWNER’S Responsibilities SpecificationsOwner Information about Your Central Furnace System General DescriptionNat M1 Furnace SpecificationsField Installation Blower Assemblies Installation StandardsCould cause unsafe operation, explo You feel that the furnace is not operMinimum Clearances Unit LocationReturn AIR Provisions Minimum Clearances27 45 All Weather Roof Jack AssembliesRoof Jack Selection AIR Distribution SystemsApplication Notes Slant Deck FlashingsNON-PLATINUM Series Duct Connector Selection Platinum SeriesCloset or Alcove Non-Platinum Series InstallationCUT OUT Floor Opening & Fuel Line Hole Alternate Attachment Methods Install Roof Jack Install FurnaceManufactured Home Site Installation of TRANSIT- Mode Venting SystemManufactured Home Factory Connect Thermostat Wires Electrical WiringConnect Power Supply Wires Control Panel All Models Fuel PipingTypical Gas Piping Thermostat Wire GaugeTypical Oil Piping for Above Ground Single-Line Supply Fuel Oil Type Hook-Up Procedure See FigureHow to Eliminate Air Leaks Lighting and Shutdown Flue GAS SamplingGENERAL-ALL Models Lighting Instructions for STAND- ING Pilot ModelsStanding Pilot Valve Sequence of Operation for STAND- ING PilotFurnace if YOU Smell GAS GENERAL-DIRECT Ignition ModelsOperating instructions for M1M Models with Direct IgnitionOil Gun Model Operating Instructions for OIL and GAS GUN FurnaceSequence of Operation for OIL GUN Models Oil Furnace Honeywell R7184 ControlFurnace Controls and FUNC- Tions Sequence of Operation for GAS GUN ModelsBurner Adjustments Service GuideCombustion AIR Gas GunOil Gun Only Electrode Setting Oil Gun OnlyGAS Conversion Atmospheric and Direct Ignition FurnacesBurner Adjustments Troubleshooting Standing Pilot ModelsControl Module Status Indicators M1M Series Control Module Is Powered Ignitor Does Not Heat Up Troubleshooting Direct Ignition Furnaces Including GAS GUNCad Cell Resistance when Sensing flame Troubleshooting OIL GUNOptional Accessories MaintenanceBy Serviceman Additional OIL Furnace MaintenanceDamper without Coil Cavity Non-Platinum Series Only Coil Cavity Damper Non-Platinum Series OnlyCooling Speed/ Evap Coil Wiring Diagrams M1GH 077, 090 Models 710150 08/00 710151 08/00 Blower WireTable Gas and Oil Furnaces, A/C Ready M1 B, S 066, 086 Models High Altitude Equivalent Orifice Sizes AT High Altitudes
Related manuals
Manual 40 pages 53.35 Kb

M1M, M1S, M1B, M1G specifications

Nordyne, a renowned player in the HVAC industry, has introduced a range of high-efficiency gas furnaces, including the M1S, M1G, M1B, and M1M models. Each of these furnaces is designed to provide efficient heating solutions tailored to the needs of homeowners.

The M1S series is well-known for its reliability and performance. It features a single-stage heating process that delivers consistent warmth to any space. With its multi-speed blower, the M1S ensures quiet and comfortable airflow, adapting seamlessly to varying temperature demands. Its robust construction coupled with an energy-efficient design makes it an ideal choice for those looking for dependable heating without sky-high utility bills.

The M1G model steps it up with a two-stage heating system that offers enhanced comfort and efficiency. By operating at a lower speed during milder conditions, the M1G can effectively reduce energy consumption while still maintaining a cozy environment. It is equipped with a variable-speed blower that not only enhances efficiency but also minimizes noise, making it perfect for residential areas. The M1G is designed with advanced safety features, including an integrated control board that monitors furnace functions to ensure optimal performance.

For those seeking a budget-friendly option without compromising on quality, the M1B model provides a solid performance with its straightforward, reliable single-stage heating. While it may lack some of the advanced features found in higher-end models, the M1B is built for ease of use with straightforward controls and maintenance, making it a great option for families.

The M1M model integrates cutting-edge technology with a focus on maximum efficiency. Featuring a modulating gas valve, this model can adjust its output based on real-time heating requirements. This adaptability ensures that the furnace operates at peak efficiency, significantly lowering energy bills and improving overall comfort. The M1M also boasts advanced diagnostic capabilities that allow for easy troubleshooting, thus reducing maintenance time and costs.

In summary, Nordyne's M1 series furnaces—M1S, M1G, M1B, and M1M—offer a range of options to meet diverse heating needs. With technologies designed for efficiency, reliability, and comfort, Nordyne continues to solidify its reputation as a leader in the HVAC market, providing homeowners with effective heating solutions tailored to their lifestyles and budgets.