Trane UD1D120A9H51B Integrated Furnace Control Error Flash Codes, What to do if YOU Smell GAS

Page 24

Installer’s Guide

2.LOSS OF FLAME OR GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle (when flame is not present at the sensor), the control mod- ule will retry the ignition sequence up to two times after the sensor cools. If ignition is not achieved, it will lockout the furnace.

3.POWER FAILURE

If there is a power failure during a heating cycle, the system will restart the ignition sequence auto- matically when power is restored, if the thermostat still calls for heat.

4.INDUCED DRAFT BLOWER FAILURE

If pressure is not sensed by the pressure switch, it will not allow the gas valve to open, therefore the unit will not start. If failure occurs during a running cycle, the pressure switch will cause the gas valve

to close and shut the unit down.

Carbon monoxide, fire or smoke can cause serious bodily injury, death, and/ or property damage.

A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commis- sion recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufacturers installation in- structions to help alert dwelling occupants of the pres- ence of fire, smoke or unsafe levels of carbon monoxide.

These devises should be listed by Underwriters Labora- tories, Inc. Standards for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA Interna- tional Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19.

NOTE:

The manufacturer of your furnace does not test any de- tectors and makes no representations regarding any brand or type of detector.

! WARNING

Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch;

do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by

a qualified installer, service agency or the gas supplier.

INTEGRATED FURNACE CONTROL ERROR FLASH CODES

Flashing Slow ---

Normal - No call for Heat

 

Flashing Fast ---

Normal - Call for Heat

 

Continuous ON ---

Replace IFC

 

Continuous OFF ---

Check Power

 

2 Flashes ---

System Lockout (Retries or Recycles exceeded)

 

Draft Pressure Error - Possible problems:

3 Flashes ---

a) Venting problem

 

b) Pressure switch problem

 

 

c) Inducer problem

 

4 Flashes ---

Open Temperature Limit Circuit

5 Flashes ---

Flame sensed when no flame should be present

6 Flashes ---

115 volt AC power reversed, poor grounding or system voltage too low

7 Flashes ---

Gas valve circuit error

 

8 Flashes ---

Low flame sense signal

 

9 Flashes ---

Check Ignitor Circuit and Line "N" to 24VAC "Common" voltage (2 volts)

[possible grounding problem]

 

Trane

 

 

 

 

 

 

6200 Troup Highway

 

File Number

18-CD21D1-5

Tyler, TX 75707

 

 

Supersedes

18-CD21D1-4

 

 

 

 

Date

05/08

For more information contact

 

 

your local dealer (distributor)

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right

 

24

to change design and specifications without notice.

18-CD21D1-5

Image 24
Contents Canada USA/CANADA AlternateSafety Section Carbon Monoxide Poisoning HazardInstaller’s Guide Contents General Installation Instructions Location and ClearancesDrawing DD1-HF Outline Drawing Downflow Installation Upflow InstallationHorizontal Installation Required Floor Opening DownflowInput ALL EQUIP- Ment Installed Input ALL Equip Ment InstalledAIR for Combustion and Ventilation Less than 50 CU. FTMinimum Free Area in Square Inches Each Opening Furnace only Duct Connections Return AIR Duct ConnectionTypical Upflow Return AIR Filter Installations Bottom Filter Rack InstallationReturn AIR Filters FilterOptional Filter Rack Installation for Bottom Return Airf lowTypical Downflow Furnace Return AIR Filter Installations Filter Rack Retaining Screw/Pin Filter Bottom PanelGeneral Venting Instructions Cabinet Filter Filter Bracket Width Size LocationVent Piping Venting Into a Masonry ChimneyInternal Masonry Chimneys Carbon Monoxide Poisoning HazardElectrical Connections GAS Vent TerminationFurnace See Twinning Stage Heating only ThermostatGAS Piping Sequence of Operation Thermostat Call for HeatSTART-UP and Adjustment Preliminary InspectionsCombustion and Input Check Part Numbers for Replacement Orifices Orifice SizesHigh Altitude Derate Lighting Instructions To Shut OFFGAS Flow in Cubic Feet PER Hour Cubic Foot Dial Control and Safety Switch Adjustment Operating InformationIntegrated Furnace Control Error Flash Codes What to do if YOU Smell GAS