4.CONTROLS

4.1INTEGRATED CONTROL

All units are equipped with an integrated control, located under the unit, in front of the electrical compartment. Use the push button (1) to control the unit. The LED (2) will then shows on which mode the unit is in.

Refer to table below to see how to operate the unit using its integrated control.

WARNING

AVERTISSEMENT

Risk of electric shock. Before performing

Danger d’électrocution. Débranchez

any maintenance or servicing, always

toujours l’appareil avant d’entreprendre

disconnect the unit from its power source.

des travaux d’entretien ou de réparation.

 

 

 

CAUTION

ATTENTION

 

Unscrew both screws to open the electrical

Dévisser les deux vis pour ouvrir le compartiment

 

compartment. To completely remove, detach

électrique. Pour retirer complètement, le

 

from its retention wire inside.

détacher de son fil de rétention intérieur.

No light

OFF or remote controled

 

Amber light

LOW speed

 

Green ligh

HIGH speed

 

Blinking light

See User Manual

 

Sans lumière

Arrêté ou contrôlé

 

 

par contrôle mural

 

Lumière ambre

Basse vitesse

 

Lumière verte

Haute vitesse

 

Clignotant

Voir guide d’utilisation

 

VD0182

1

2

PRESS ON PUSH BUTTON

LED COLOR

RESULTS

ONCE

AMBER

UNIT IS ON LOW SPEED

TWICE

GREEN

UNIT IS ON HIGH SPEED

THREE TIMES

NO LIGHT

UNIT IS OFF

If a problem occurs during the unit operation, its integrated control LED (2) will blink. The color of the blinking light depends on the type of error detected. Refer to Section 11 Troubleshooting on last page for further details.

4.1.1BOOT SEQUENCE

The unit boot sequence is similar to a personnal computer boot sequence. Each times the unit is plugged after being unplugged, or after a power failure, the unit will perform a 30-second booting sequence before starting to operate. During the booting sequence, the integrated control LED will light GREEN or AMBER for 5 seconds, and then will shut off for 2 seconds. After that, the LED will light RED for the rest of the booting sequence. During this RED light phase, the unit is checking and resetting the motorized damper position. Once the motorized damper position completely set, the RED light turns off and the booting sequence is done.

NOTE: No command will be taken until the unit is fully booted.

4.2ELECTRICAL CONNECTION TO OPTIONAL WALL CONTROLS

For more convenience, this unit can also be controlled using an optional main wall control.

NOTES: 1. The integrated control must be turned OFF to use an optional main control.

2. If an optional auxiliary control is used, if activated, this auxiliary control will override the optional main control.

0 ! WARNING

Always disconnect the unit before making any connections. Failure in disconnecting power could result in electrical shock or damage of the wall control or electronic module inside the unit.

CAUTION

Never install more than one optional main wall control per unit. Make sure that the wires do not short-circuit between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce electrical interference (noise) potential, do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.

Use the terminal connector included in the installation kit to perform the electrical connection for main and optional wall controls. Check if all wires are correctly inserted in their corresponding holes in the terminal block. (A wire is correctly inserted when its orange receptacle is lower than another one without wire. On picture beside, wire A is correctly inserted, but not wire B.)

AB

VE0106

- 17 -

Image 17
Contents Installation Instructions HRV90H and ERV90HC About These Units Limitation About this ManualTable of Contents HRV ERV Technical DataVentilation Performance Technical Data CONT’DHRV Typical Installations Typical Installations CONT’D Installation Make sure the unit is level Installation CONT’DStale air exhaust ductwork Fresh air distribution ductworkMethod 2 Return side connection Method 1 Supply side connectionDuct, see figure beside Fresh air distribution Method 2B Return-return with Automatic fresh air bypassStale air intake Do not use screws to connect the rigid ducts to the ports Insulated flexible ductsRigid ducts 457 mm Xmas tree pin ’’ Ø Avertissement ControlsNo C NC I OC OL Y R G B Controls CONT’DOC OL Y R G Electrical Connection to the Furnace6WIRINGDIAGRAM Balancing the Unit To drain Connecting the Drain HRV Units onlyMaintenance Maintenance CONT’D HRV90HS HRV90HT ERV90HCS ERV90HCT Service PartsProblems Possible causes You should try this Troubleshooting

ERV90HC, HRV90HS, HRV90H, ERV90HCS specifications

The Broan HRV90H, ERV90HCS, HRV90HS, and ERV90HC are advanced energy recovery ventilators designed to optimize indoor air quality while efficiently managing energy consumption in residential and commercial spaces. These models exemplify the marriage of function, effectiveness, and technology to ensure that you have a constant supply of fresh air without sacrificing comfort.

One of the main features of these units is their energy recovery technology. The HRV models are designed to recover heat from the outgoing stale air and transfer it to incoming fresh air, while the ERV models go a step further by transferring both heat and moisture. This is especially beneficial in climates where maintaining humidity levels is crucial for comfort. By using these units, homeowners can enjoy fresh air without throwing away energy costs associated with heating or cooling.

The compact design of the Broan HRV and ERV systems allows for flexible installation in various settings. They can be easily integrated into existing HVAC systems or used in new constructions. Each model is equipped with user-friendly controls, featuring various operation modes to suit different needs, whether it's a high-demand situation or a standard ventilation requirement.

Another standout characteristic is their quiet operation. Engineered with sound-dampening materials, these units ensure that they run quietly, allowing you to enjoy a peaceful indoor environment. Additionally, their high-efficiency filters capture airborne particles, thus promoting a healthier living space by reducing allergens and other irritants.

In terms of energy efficiency, the Broan HRV and ERV units boast impressive performance ratings, which can help homeowners save significantly on energy bills over time. The technology used in these products meets industry standards and certifications, ensuring that they not only perform well but also adhere to environmental regulations.

With a commitment to quality and reliability, Broan offers these energy recovery ventilators as a smart choice for those looking to enhance indoor air quality while remaining energy-conscious. The HRV90H, ERV90HCS, HRV90HS, and ERV90HC are the perfect solutions for creating a more comfortable, healthy, and efficient living or working environment. Whether you are renovating an older home or planning a new build, these systems provide an innovative approach to modern ventilation needs.