Slant/Fin VHS-120, VHS-150, VHS-90 user service Annual Service Technician Inspection

Page 4

VICTORY II VHS MODELS

Figure 4. Vertical venting through chimney

Figure 5. Chimney venting

4

2.Condensation drain trap inspection

Check condensation drain trap to be full of water. Check for deterioration of the tubing. Check that trap is not plugged. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain should extend to a floor drain or to a contain- er which may require emptying periodically.

3.Piping inspection

Look at all water piping. There should be no leaks or signs of leaks at any pipe joints or around the boiler.

4.System water pressure inspection

The temperature and pressure gauge indicates the pressure in the boiler at each water temperature. For most installations, it should indicate about 12 to 15 psi pressure when temperature is about 70 to 100° F and from 15 psi to 25 psi when temperature is up to 240° F. FOR YOUR SYSTEM, there is one correct pressure for each temperature. ASK YOUR INSTALLER OR SERVI- CEPERSON TO EXPLAIN AND SHOW YOU. Learn what normal pressures to look for. If pressure decreas- es from normal, your system is losing water. If pressure rises from normal, the relief valve will open to relieve the pressure. Call your service organization if pressures are higher or lower than normal, and if the relief valve spills water. Repair or adjustment is needed.

5.Unusual noise

Stand near the boiler and look and listen. As the burn- ers start and shut off, there should be no unusual noise. No fire should be visible coming out from the front of the boiler when the burners start or run.

6.Boiler room air supply inspection

Ample air is required for your boiler to burn fuel cleanly and safely. Check to make sure all air vents are open and free of obstruction. Air needs are greatest in cold weather.

WARNING: The flow of combustion and ventilating air to the boiler should not be obstructed.

WARNING: If you find any problem during your inspection, call for service immediately.

ANNUAL SERVICE TECHNICIAN INSPECTION

A trained and qualified service technician should per- form these inspections before each heating season:

1.Safety check

Removing Control Box (cover). See Figure 6. To remove control box:

a.Turn back screw 1/4 turn clockwise to open

position .

b.Remove two sheet metal screws in the top of control box.

c.Remove control box.

To replace the box, reverse procedure. Be sure that black screw is in the lower bracket receptacle and

lock position .

Image 4
Contents For Your Safety User’s Information ManualLighting Instructions Victory II VHS ModelsUser Inspection InspectionVenting system inspection Annual Service Technician Inspection Annual Service Technician Inspection and Cleaning Flue passage cleaningSafety Information Flame ROLL-OUT Safety SHUT-OFF SwitchFor Your Safety Read Before Operating Operating Instructions To turn off gas to applianceSLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

VHS-90, VHS-120, VHS-150 specifications

Slant/Fin is a renowned manufacturer in the heating industry, known for producing high-quality hydronic heating solutions. Among their notable offerings are the VHS series of gas-fired hot water boilers, which include the VHS-120, VHS-90, and VHS-150 models. These boilers are characterized by their advanced design and technology that focuses on efficiency, reliability, and user convenience.

The VHS-120, VHS-90, and VHS-150 are designed for residential and light commercial applications, making them versatile choices for various settings. Each model features a stainless steel heat exchanger that enhances durability and efficiency. The stainless steel construction allows for superior heat transfer, contributing to more effective water heating and lower operational costs.

One of the standout technologies in the VHS series is its modulating operation. This feature allows the boiler to adjust its output based on the heating demand, resulting in significant energy savings. With the ability to modulate, these boilers operate quietly and efficiently, only using the energy necessary to meet your specific heating needs. This is particularly beneficial in climates with fluctuating temperatures, as the system can provide consistent comfort without overspending on fuel.

Safety is also paramount in the design of the VHS series. These boilers come equipped with multiple safety features, including a high limit control, flow switch, and a spill switch. These systems work together to ensure that the boiler operates within safe parameters, minimizing the risk of accidents.

Additionally, the VHS series boasts a compact design, making installation easier in tight spaces. The user-friendly control interface allows for straightforward operation and monitoring, empowering users to manage their heating systems effectively. This simplicity extends to maintenance as well; the models are designed for easy access to critical components, making routine checks and servicing hassle-free.

In terms of performance, the VHS-120, VHS-90, and VHS-150 offer a range of heating capacities, enabling them to cater to various building sizes and needs. Their efficiency ratings comply with modern standards, making them environmentally friendly options for homes and businesses looking to reduce their carbon footprint.

In conclusion, the Slant/Fin VHS series — VHS-120, VHS-90, and VHS-150 — represents a blend of innovation and reliability. With their advanced heating technology, safety features, and ease of use, they stand out as excellent options for anyone in need of an efficient and dependable heating solution.