Rinnai E110CP, E75CN, E110CN, E75CP user manual Hot water supply, Condensate drain pipe

Page 24

6.5Hot water supply

!

i

DANGER

NOTICE

Connection of the drinking water installation should be performed according to the national secondary drinking water regulations.

Do NOT use toxic chemicals, such as are used for boiler treatment in potable water heating systems used for space heating.

The sanitary water pipes can be connected to the installation by use of adapter fittings. The cold water inlet on the Combi boilers must be equiped with the following components (counted in the water flow direction):

Flow regulator valve (supplied), Safety group, Expansion vessel 87 PSI / 6bar (potable water, blue).

The 3/4" NPT adapter fitting with flow reducing valve must be fitted in the cold water connection.

A flow regulator valve is supplied with the boiler in a 3/4"NPT adapter fitting. The flow regulator valve ensures that a quantity of water is supplied which has a outlet temperature of 120°F (assuming a cold water temperature of 45°F). The quantity of water is virtually unaffected by the water pressure.

When there is a water pressure lower than 22PSI / 1.5 bar it is advisable to remove the inside mechanism of the flow reducing valve.

6.6 Condensate drain pipe

Installation & Servicing Instructions Rinnai E-Series

24

i i

i

i

NOTICE

NOTICE

NOTICE

NOTICE

This boiler produces condensate. Condensate must be drained otherwise the boiler will not function and can cause property damage.

The condensation drain pipe should be connected to a drain in the building by means of an open connection. By this means the possibility of drain gases effecting the boiler is prevented. The drain connection should have a minimum diameter of 1.3" / 32mm.

Install the condensation drain pipe according to the applicable rules and regulations.

If the condensate outlet of the boiler is lower than the public sewage system a condensate pump must be used.

The condensate produced by the boiler has a pH value between 3 and 4.

Install a neutralization unit if required by the local code. It is recommended, but not required to install a condensate neutralizer.

Do not drain the condensation water to the external rain gutter because of the danger of freezing and blockage of the drain.

Before putting the boiler into operation fill the condensate trap with 1.27 cups / 300 ml of water. If the boiler will be installed in a high temperature installation such as baseboard, then fill the condensate trap with mineral oil instead of water.

Use materials approved by the authority having jurisdiction. In absence of such authority, PVC and CPVC pipe must comply with ASTM D1785, F441 or D2665. Cement and primer must comply with ASTM D2564 or F493.

For Canada, use CSA or ULC certified PVC or CPVC pipe, fittings and cement.

Periodic cleaning of the condensate disposal system must be carried out. See the Rinnai Boiler Application Manual for further information and for a piping

diagram for the condensate.

Image 24
Contents Instructions Contents of instructions Subject to technical changesUpdating of documentation Content Safety and general instructions Symbol definitionsDesignated use Hazard definitionsFollowing instructions must be followed What to do if YOU Smell GASFollow these instructions for the space heating water Tools, materials and additional equipmentDisposal Regulations and guidelines Description of the boiler Room sealed boilerCondensing ModulatingPackaging and transportation Scope of deliveryTransportation Installation Requirements for the installation roomFitting the boiler Dimensions E75CPConnection for combustion air supply and vent system Plumbing Kits Plumbing KitClearances from boiler Low Loss HeaderTechnical specifications CSAConnecting the boiler Central heating systemPlumbing Kit installation Compression fittingsInstallation & Servicing Instructions Rinnai E Safety valve Low water cut offExpansion tank With the boilerUnderfloor heating system plastic pipes Gas supply connectionGas connection with natural gas Gas pipingGas connection with propane gas Propane Supply Pressure RequirementsHot water supply Condensate drain pipeVent system and air supply system Intake / Exhaust GuidelinesTo the boiler. See the list on Agency2a Examples vent and air supply systems concentric 2b Examples vent and air supply systems parallel Installation of the vent system Concentric system seeParallel system see Room Air System outdoor combustion airRecommended vent/air intake terminal position Terminal positionsOccur to building products in the vicinity see Item Description Flue Material United StatesDimensioning of the exhaust and air intake duct Combustion air and vent piping lengths Calculation of equivalent length vent systemParallel system Total equivalent length Concentric systemCalculation of compensation factor Boiler type E75 E110Room Air System indoor combustion air Unconfined SpaceConfined Space Louvers and GrillsLocation Using Indoor Air For Combustion Using Outdoor Air For CombustionConnecting incoming power Electrical connectionsAre used must have a Volt free contact Connection terminal E-SeriesElectrical diagram Electrical ladder diagram Boiler controls Good-state or standard read outTechnical read out Operation indicationExplanation of the function buttons Requirements of the water system Filling the heating system Freeze protectionWith water will have to be done Do not try to light the burner by hand Close main gas shut off valveAdjustments Altering adjustmentsPress the Mode-button for 5 seconds Press the STORE-button to confirm the code code blinks1Parameter Mode Outdoor reset Activating factory settings green button function Boiler and/or the installationIsolating the boiler Commissioning Testing for gas leaks Testing the Ignition Safety shut off deviceStart up of the boiler Checking for contamination Type of boilerBoiler needs maintanance Follow the next procedure Checking of the zero pressure controlChecking the O2 Installing the casing Measuring the ionization currentMaintenance Periodic examination of venting systems and boilerInspection TechnicianChecking and adjusting the gas/air ratio Visual inspection for general signs of corrosionMeasuring the inlet gas pressure Carrying out a pressure test of the heating systemMaintenance activities Replace the gasket with a new oneCondensate trap Condensate trayWarranty Visual inspection of the flameParts of the boiler G KBlocks and Errors Error indication short referenceExternal safety contact is active BlocksBlock Check flow through the installation Execute Parameter-Reset Check flow through the boiler and DHW fascilityCheck the sensors NTC 1 and NTC Check the main Power supply Check the boiler PumpErrors ErrorRectify the short-circuit If necessary replace this part Disconnect voltage from the boiler and check the fuse F2 Check the 24 Volt ConnectionCheck Disconnected Components for short-circuiting Check the data in Error mode Ionisation flow Ionisation cable or O2 settingGas Software error con Trol unit Reset the boilerRectify the prece Ding error Error persists After reset Software error Control unit Software error Control unit Error Remove Voltage from the boiler and check fuse F2 Check the 24 Volt ConnectionsCheck Disconnected parts for wear and tear Software error Control unit Temperature of 36 is displayed at position If necessary Replace the flow SensorCheck actual flow temperature Check flow sensor NTC1Check actual return temperature Check return Sensor NTCFuse is working and the error is repeated Wiring and voltage are OK and error is repeatedFan is not Spinning If necessary Replace the fanCheck the wiring Wiring is OK but the error is repeatedReplace Sensor Shut down of return sensor T2 Contact for supply sensor T1 open Check the data Error mode Software error Control unit Other errors Central heating but no hot waterKey of the central heating program is not switched on Hot water but no central heatingRS100 with outdoor Sensor Room sensor-On Three-port valve is not circulating to central heatingKey pump program Is on Insufficient quantity of hot water Hot and cold water Connection to the boiler Mixed upIncorrect flow reducing Valve Absence Positive resultsTemperature drop of the DHW DHW power for the boiler is set too lowFlow reducing valve Incorrect choice Installation Radiators do not get hot enough or warming up takes too longSpare parts Parts casing E-SeriesInstallation Manual E-SERIES DescriptionParts heat exchanger E-Series OSS1 OSS2 Clamp BAR TOP Part H.EX. Long Parts rear wall E-Series OSS1 OSS2 Parts pipes E-Series Description Parts electrical components E-Series 166 167101 Parts list vent system Vent ProductsHeatfab Rinnai/ UbbinkCommon venting guidelines 103104 105 106 107 800000012 9/2009

E75CP, E110CN, E75CN, E110CP specifications

Rinnai is a leading name in the heating industry, recognized for producing highly efficient and reliable tankless water heaters. Among their popular models are the Rinnai E75CN, E75CP, E110CP, and E110CN, each designed to cater to various household needs and preferences.

The Rinnai E75CN and E75CP are both remarkable for their compact size and impressive heating capabilities. The E75CN is a natural gas model, while the E75CP runs on propane. These units are designed to deliver a maximum flow rate of up to 7.5 gallons per minute, ensuring that multiple fixtures can be used simultaneously without a dip in performance.

Both models incorporate advanced temperature control technology, allowing users to set their desired water temperature with precision. The units feature a durable heat exchanger, constructed from high-grade stainless steel, which not only promotes longevity but also helps in preventing corrosion. Additionally, they come with built-in safety features, such as freeze protection and an overheat cut-off system, ensuring safe operation in varying conditions.

Moving on to the Rinnai E110CP and E110CN, these tankless water heaters are designed for larger households with higher hot water demands. The E110CP operates on propane, while the E110CN utilizes natural gas. These units deliver a maximum flow rate of up to 11 gallons per minute, making them ideal for simultaneous use in multiple bathrooms, kitchens, and laundry rooms.

The E110 models showcase Rinnai's Smart Technology, which optimizes energy consumption by adjusting the heating output based on the demand. This not only maximizes efficiency but also significantly reduces energy costs. They are equipped with digital controls and diagnostics, providing users with real-time information and the ability to troubleshoot easily if any issues arise.

In terms of installation, all four models are designed for versatility. They can be installed indoors or outdoors, giving homeowners flexibility based on their space and preference. With their compact design, these units require less space compared to traditional tank heaters, making them a suitable choice for modern homes.

Overall, Rinnai's E75CN, E75CP, E110PC, and E110CN models represent cutting-edge technology in tankless water heating. Their efficiency, safety features, and advanced technology make them an excellent choice for homeowners looking to upgrade their hot water systems. With Rinnai, users can enjoy the convenience of continuous hot water without sacrificing energy efficiency.