Fig. 8 — Gasket Location on Roof Curb (48P075-100 Units with Optional High-Capacity Power Exhaust)

Step 8 — Connect Condensate Drain — There are a total of five drain connections required on each unit: one primary drain (on right-hand side of the unit) and four second- ary drains (two on each side of unit).

PRIMARY DRAIN — The primary drain is a 2-in. FPT pipe connection located on the right-hand side of the unit looking at the unit from the return air end. See Fig. 12-21. Fig. 22 shows the additional length of units with an extended chassis.

With field-supplied fittings and pipe sections, plumb the pri- mary condensate drain to the 2-in. FPT connector on the base rail. Use a trap height of at least 4-in. for size 030-070 units and 7-in. for size 075-100 units. See Fig. 23 and 24. Install with a height dimension of at least 2-in. from the top of the exit pipe from the trap section to the bottom of the connector. Apply a bead of RTV or similar sealant around the pipe joint at the con- nector in the base rail.

SECONDARY DRAINS (Units Installed on Curb) — There are two secondary drain connections on each side of the unit. See Fig. 25. There are secondary drains on each side of the unit in the filter section and on each side of the unit in the supply fan section. There are labels marking each lo- cation on the unit base rail. See Fig. 12-21.

Locate the four 11/4-in. drain coupling assemblies and mounting screws (shipped in a bag taped to the basepan in the supply fan section, located behind the access panel marked FAN SECTION). The drain couplings are a 10-gage plate with a 11/4 in. half coupling welded to the plate.

At each secondary drain hole location, there is a 13/8-in. hole pre-drilled in the bottom of the base rail, surrounded by

four 0.20-in. engagement holes. Install a drain coupling assem- bly using screws provided at each secondary drain hole loca- tion. See Fig. 26. Do not attach any drain coupling assemblies in the condenser section base rail.

Using field-supplied fittings and pipe sections, assemble U- traps at each secondary drain fitting. See Fig. 27. Provide a minimum size of ½-in. pipe for secondary drains. Use a trap at least 4-in. deep for size 030-070 units and 7-in. deep for size 075-100 units. Apply a bead of RTV or similar sealant around the drain assemblies.

Consult local plumbing codes for direction on joining multi- ple drain lines. Total size of any combined line does not need to exceed nominal 2-in. size of primary drain connection.

Fill the U-traps at the secondary drain locations prior to unit start-up. Also check the U-traps before each cooling season to ensure the traps are filled and functioning properly.

SECONDARY DRAINS (Units Installed on Steel Beam or Slab) — There are two secondary drain connections required on each side of the unit. There are secondary drains on the bot- tom of the base rail on each side of the unit in the filter section and on each side of the unit in the supply fan section. There are labels marking each location on the unit base rail. See Fig. 12-

21.Drain holes will need to be drilled in these locations at the side of the base rail. The existing secondary drain holes in the bottom of the base rail must be sealed. Prior to final positioning of the unit, apply a bead of RTV or similar sealant around each secondary drain hole in the bottom of the unit base rail. See Fig. 27. Install the metal seal plates then position the unit into final location.

16

Image 16
Contents Installation Instructions Installation Physical Data 48P2,P3,P4,P5030-050 Base Unit5810 6310 6025 6525 Optional Power Exhaust Physical Data 48P2,P3,P4,P5055-070Physical Data 48P2,P3,P4,P5075-100 Optional Return Fan Physical Data 48P075-100 Only Optional Humidi-MiZerCoil DataOperating Weights of Options and Accessories lb Option or Accessory 48/50P Unit SizeOptional High-Capacity Power Exhaust Fan Drive Data Power Exhaust Fan Drive DataOptional Return Fan Drive Data Roof Curb Sizes Roof Curb Sizes 055 Roof Curb Sizes Condenser Section Roof Curb Sizes 070 Condenser Section Roof Curb Sizes 090 Gasket Location on Roof Curb Size 070-100 Units Page ALL Panels Must be in Place When Rigging ALL Panels Must be in Place When Rigging Total Optional HIGH-CAPACITY Power Exhaust SizeTotal 48P2,P3,P4,P5 Units with SizeTotal With Optional Return FAN A48-8613 A48-8614 A48-8615 A48-8616 A48-8617 A48-8618 A48-8619 A48-8620 A48-8621 A48-8622 Drain Piping Details Location Curb MountDrain Pipe Details Secondary Drain Seal Plate Location Slab Mount 25% Outdoor-Air Hood Location Large Economizer Hood Assembly Route Field Wiring Disconnect Location Size 030 and 035 Units Wire FieldFAN Motor RLA LRA FLA Fuse or Electrical Data, 48P2,P3,P4,P5030 UnitsMCA Hacr MCA Electrical Data, 48P2,P3,P4,P5035 Units FAN Motor RLA LRAFLA MCA Fuse or Hacr BrkrElectrical Data, 48P2,P3,P4,P5040 Units FAN Motor RLA LRA FLAFAN Motor RLA LRA FLA Fuse or Electrical Data, 48P2,P3,P4,P5050 Units Electrical Data, 48P2,P3,P4,P5050 Units Electrical Data, 48P2,P3,P4,P5055 Units Electrical Data, 48P2,P3,P4,P5060 Units Electrical Data, 48P2,P3,P4,P5070 Units Voltage Compressor Condenser Evaporator Power Range FAN Motor Exhaust Power Supply VoltageElectrical Data 48P2,P3,P4,P5075 Standard Units FLA MCAVoltage Compressor Condenser Evaporator Power Range Fuse or Hacr Electrical Data 48P2,P3,P4,P5090 Standard Units FAN Motor RLA LRA FLA FAN Motor RLA LRA FLA Electrical Data 48P2,P3,P4,P5100 Standard Units FAN Motor RLA LRA FLA FAN Motor RLA LRA FLA Auxiliary Control Box Location Sizes Auxiliary Control Box Details Sizes Sizes 055-100 without Optional Return FanShipping Brackets Size 030-050 Units Shipping Brackets Sizes Gas Piping Details Flue/Inlet Hood Locations, Sizes Low Heat, Horizontal Supply UnitsFlue Hood, Inlet Hood, and Baffle Usage Horizontal Supply UnitsFlue Deflector Baffle Curve-Type Inlet Hood Assembly 30-in Wind Baffle Details Controls Installation T55 or T56 Wiring TB201 RED BRN TB201 CCN Connections CCN Connection Approved Shielded CablesOptional UPC Open Installation MS/TP Wiring RecommendationsOpen System Wiring Specifications and Recommended Vendors UPC Open ControllerOpen System Network Wiring Smoke Control Modes
Related manuals
Manual 8 pages 7.82 Kb

P4, 48P2, P3, P5030-100 specifications

Carrier, a leader in the HVAC industry, offers a range of advanced air conditioning systems designed to provide optimal indoor climate control. Among their innovative products are the Carrier P4, P5030-100, P3, and 48P2 models, each delivering unique features tailored to diverse applications.

The Carrier P4 series is engineered for versatility and efficiency. This compact unit integrates advanced inverter technology, allowing for precise temperature control and reduced energy consumption. The P4 employs a variable speed compressor, which adjusts according to cooling needs, ensuring both comfort and energy savings. Additionally, it features a user-friendly interface with smart connectivity options, enabling remote access and management via smartphones.

Next in line, the Carrier P5030-100 model is designed with commercial applications in mind. It is equipped with a robust scroll compressor and advanced heat exchange technology that enhances its performance and efficiency. The P5030-100 operates quietly, making it ideal for office environments where noise reduction is a priority. Furthermore, its eco-friendly refrigerant aligns with today’s environmental standards, further making it a sustainable choice for businesses.

The Carrier P3 model excels in energy efficiency, boasting top SEER ratings while maintaining powerful cooling and heating capabilities. This model incorporates advanced refrigerant management, which minimizes environmental impact while ensuring optimal performance. Its compact design makes it an excellent choice for residential installations, providing homeowners with an unobtrusive yet effective climate control solution.

Finally, the Carrier 48P2 unit stands out with its robust design tailored for large-scale applications. It features a high-capacity scroll compressor and enhanced airflow capabilities, ensuring consistent and reliable performance across various conditions. The 48P2 comes equipped with a comprehensive control system that allows for integration with building management systems, facilitating easy monitoring and control of multiple units. This model is ideal for commercial buildings that demand high performance and energy efficiency.

Overall, Carrier's P4, P5030-100, P3, and 48P2 models represent the forefront of HVAC technology, combining efficiency, reliability, and advanced features to meet the varying demands of both residential and commercial environments. With a commitment to innovation and sustainability, Carrier continues to provide solutions that enhance indoor comfort while reducing environmental impact.