Carrier 48P2, P5030-100, P3, P4 Optional UPC Open Installation, MS/TP Wiring Recommendations

Page 74

c.Secure the black (–) wire to CCN screw terminal – on the COMM board.

d.Secure shield wire to CCN screw terminal SHIELD on the COMM board.

IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent unit from starting. If abnormal conditions occur, unplug the connec- tor. If conditions return to normal, check CCN connector, and run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.

Optional UPC Open Installation

WIRING THE UPC OPEN TO THE MS/TP NET- WORK — The UPC Open controller communicates using BACnet on an MS/TP network segment communications at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.

Wire the controllers on an MS/TP network segment in a dai- sy-chain configuration. Wire specifications for the cable are 22 AWG (American Wire Gage) or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire. The maximum length is 2000 ft.

Install a BT485 terminator on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing. See Fig. 85-87.

To wire the UPC Open controller to the BAS network:

1.Pull the screw terminal connector from the controller's BAS Port.

2.Check the communications wiring for shorts and grounds.

3.Connect the communications wiring to the BAS port’s screw terminals labeled Net +, Net -, and Shield.

NOTE: Use the same polarity throughout the network segment.

4.Insert the power screw terminal connector into the UPC Open controller's power terminals if they are not current- ly connected.

5.Verify communication with the network by viewing a module status report. To perform a module status report

using the BACview keypad/display unit, press and hold the “FN” key then press the “.” Key.

To install a BT485 terminator, push the BT485 on to the BT485 connector located near the BACnet connector.

NOTE: The BT485 terminator has no polarity associated with it.

To order a BT485 terminator, consult Commercial Products i-Vu® Open Control System Master Prices.

MS/TP WIRING RECOMMENDATIONS — Recommen- dations are shown in Tables 29 and 30. The wire jacket and UL temperature rating specifications list two acceptable alterna- tives. The Halar specification has a higher temperature rating and a tougher outer jacket than the SmokeGard specification, and it is appropriate for use in applications where the user is concerned about abrasion. The Halar jacket is also less likely to crack in extremely low temperatures.

NOTE: Use the specified type of wire and cable for maximum signal integrity.

Smoke Control Modes — Rooftop units can be used for aid in building smoke control in the event of a building fire. The available functions include: Fire Shutdown, Pressuriza- tion, Evacuation, and Smoke Purge. These functions are enhanced when multiple rooftop units are used to zone a build- ing. See Table 31 and Fig. 82 and 83.

FIRE SHUTDOWN — Fire Shutdown mode terminates all unit operation (cooling, heating, supply fan, and power exhaust). This mode prevents recirculation of contaminated air back into the space. The mode will not allow admission into the space of unsuitable outside air. See Fig. 82 for wiring.

PRESSURIZATION — Pressurization mode is intended to keep smoke out of a zone. The factory-installed optional econ- omizer is required for this function. Pressurization is accom- plished by the following:

opening the economizer (option)

running the supply fan (optional inlet guide vanes open or optional VFD at normal duct static pressure set point)

closing the power exhaust dampers (if installed as option or accessory)

shutting off the power exhaust fans (if installed as option or accessory)

 

 

Table 29 — MS/TP Wiring Recommendations

 

 

 

 

 

SPECIFICATION

 

RECOMMMENDATION

 

Cable

 

Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable

 

Conductor

 

22 or 24 AWG stranded copper (tin plated)

 

Insulation

 

Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.

 

Color Code

 

Black/White

 

Twist Lay

 

2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal

 

Shielding

 

Aluminum/Mylar shield with 24 AWG TC drain wire

 

Jacket

 

SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.

 

 

Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.

 

 

 

 

DC Resistance

 

15.2 Ohms/1000 feet (50 Ohms/km) nominal

 

Capacitance

 

12.5 pF/ft (41 pF/meter) nominal conductor to conductor

 

Characteristic Impedance

 

100 Ohms nominal

 

Weight

 

12 lb/1000 feet (17.9 kg/km)

 

UL Temperature Rating

 

SmokeGard 167°F (75°C)

 

 

Halar -40 to 302°F (-40 to 150°C)

 

 

 

 

Voltage

 

300 Vac, power limited

 

Listing

 

UL: NEC CL2P, or better

 

LEGEND

 

 

AWG

American Wire Gage

 

 

CL2P

Class 2 Plenum Cable

 

 

DC

Direct Current

 

 

FEP

Fluorinated Ethylene Polymer

 

 

NEC

National Electrical Code

 

 

O.D.

Outside Diameter

 

 

TC

Tinned Copper

 

 

UL

Underwriters Laboratories

 

 

74

Image 74
Contents Installation Instructions Installation Physical Data 48P2,P3,P4,P5030-050 Base Unit5810 6310 6025 6525 Optional Power Exhaust Physical Data 48P2,P3,P4,P5055-070Physical Data 48P2,P3,P4,P5075-100 Optional Return Fan Physical Data 48P075-100 Only Optional Humidi-MiZerCoil DataOperating Weights of Options and Accessories lb Option or Accessory 48/50P Unit SizeOptional Return Fan Drive Data Power Exhaust Fan Drive DataOptional High-Capacity Power Exhaust Fan Drive Data Roof Curb Sizes Roof Curb Sizes 055 Roof Curb Sizes Condenser Section Roof Curb Sizes 070 Condenser Section Roof Curb Sizes 090 Gasket Location on Roof Curb Size 070-100 Units Page ALL Panels Must be in Place When Rigging ALL Panels Must be in Place When Rigging Total Total Optional HIGH-CAPACITY Power ExhaustSize 48P2,P3,P4,P5 Units with SizeTotal With Optional Return FAN A48-8613 A48-8614 A48-8615 A48-8616 A48-8617 A48-8618 A48-8619 A48-8620 A48-8621 A48-8622 Drain Pipe Details Location Curb MountDrain Piping Details Secondary Drain Seal Plate Location Slab Mount 25% Outdoor-Air Hood Location Large Economizer Hood Assembly Route Field Wiring Disconnect Location Size 030 and 035 Units Wire FieldMCA Hacr Electrical Data, 48P2,P3,P4,P5030 UnitsFAN Motor RLA LRA FLA Fuse or MCA Electrical Data, 48P2,P3,P4,P5035 Units FLA MCA Fuse or FAN MotorRLA LRA Hacr BrkrElectrical Data, 48P2,P3,P4,P5040 Units FAN Motor RLA LRA FLAFAN Motor RLA LRA FLA Fuse or Electrical Data, 48P2,P3,P4,P5050 Units Electrical Data, 48P2,P3,P4,P5050 Units Electrical Data, 48P2,P3,P4,P5055 Units Electrical Data, 48P2,P3,P4,P5060 Units Electrical Data, 48P2,P3,P4,P5070 Units Electrical Data 48P2,P3,P4,P5075 Standard Units Voltage Compressor Condenser Evaporator Power RangeFAN Motor Exhaust Power Supply Voltage FLA MCAVoltage Compressor Condenser Evaporator Power Range Fuse or Hacr Electrical Data 48P2,P3,P4,P5090 Standard Units FAN Motor RLA LRA FLA FAN Motor RLA LRA FLA Electrical Data 48P2,P3,P4,P5100 Standard Units FAN Motor RLA LRA FLA FAN Motor RLA LRA FLA Auxiliary Control Box Location Sizes Auxiliary Control Box Details Sizes Sizes 055-100 without Optional Return FanShipping Brackets Size 030-050 Units Shipping Brackets Sizes Gas Piping Details Flue/Inlet Hood Locations, Sizes Low Heat, Horizontal Supply UnitsFlue Hood, Inlet Hood, and Baffle Usage Horizontal Supply UnitsFlue Deflector Baffle Curve-Type Inlet Hood Assembly 30-in Wind Baffle Details Controls Installation T55 or T56 Wiring TB201 RED BRN TB201 CCN Connections CCN Connection Approved Shielded CablesOptional UPC Open Installation MS/TP Wiring RecommendationsOpen System Wiring Specifications and Recommended Vendors UPC Open ControllerOpen System Network Wiring Smoke Control Modes
Related manuals
Manual 8 pages 7.82 Kb

P4, 48P2, P3, P5030-100 specifications

Carrier, a leader in the HVAC industry, offers a range of advanced air conditioning systems designed to provide optimal indoor climate control. Among their innovative products are the Carrier P4, P5030-100, P3, and 48P2 models, each delivering unique features tailored to diverse applications.

The Carrier P4 series is engineered for versatility and efficiency. This compact unit integrates advanced inverter technology, allowing for precise temperature control and reduced energy consumption. The P4 employs a variable speed compressor, which adjusts according to cooling needs, ensuring both comfort and energy savings. Additionally, it features a user-friendly interface with smart connectivity options, enabling remote access and management via smartphones.

Next in line, the Carrier P5030-100 model is designed with commercial applications in mind. It is equipped with a robust scroll compressor and advanced heat exchange technology that enhances its performance and efficiency. The P5030-100 operates quietly, making it ideal for office environments where noise reduction is a priority. Furthermore, its eco-friendly refrigerant aligns with today’s environmental standards, further making it a sustainable choice for businesses.

The Carrier P3 model excels in energy efficiency, boasting top SEER ratings while maintaining powerful cooling and heating capabilities. This model incorporates advanced refrigerant management, which minimizes environmental impact while ensuring optimal performance. Its compact design makes it an excellent choice for residential installations, providing homeowners with an unobtrusive yet effective climate control solution.

Finally, the Carrier 48P2 unit stands out with its robust design tailored for large-scale applications. It features a high-capacity scroll compressor and enhanced airflow capabilities, ensuring consistent and reliable performance across various conditions. The 48P2 comes equipped with a comprehensive control system that allows for integration with building management systems, facilitating easy monitoring and control of multiple units. This model is ideal for commercial buildings that demand high performance and energy efficiency.

Overall, Carrier's P4, P5030-100, P3, and 48P2 models represent the forefront of HVAC technology, combining efficiency, reliability, and advanced features to meet the varying demands of both residential and commercial environments. With a commitment to innovation and sustainability, Carrier continues to provide solutions that enhance indoor comfort while reducing environmental impact.