AIR FOR

WARNING

COMBUSTION

 

If the area in which the heater may be operated is smaller than

 

AND

that defined as an unconfined space, provide adequate combus-

tion and ventilation air by one of the methods described in the

VENTILATION

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

Continued

VENTILATION AIR

 

 

Ventilation Air From Inside Building

 

This fresh air would come from an adjoining unconfined space. When ventilating to an

 

adjoining unconfined space, you must provide two permanent openings: one within 12"

 

of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see

 

options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3,

 

Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air

 

for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING

Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

 

 

12"

Figure 2 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

 

Attic

 

 

Air

 

 

 

 

Outlet

 

 

 

Air

 

To Attic

 

 

 

 

 

 

To

 

 

 

Crawl

 

Inlet

 

Space

 

 

 

 

Air

 

 

 

 

Inlet Air

Ventilated

 

 

Crawl Space

 

 

 

 

Figure 3 - Ventilation Air from Outdoors

7

102990

Image 7
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualContents Safety Information Burner patterns can cause sooting Piezo Ignition System Local Codes Unpacking Product Features Safety Device OperationVentilation AIR forProviding Adequate Ventilation Determining AIR Flow for Heater Location AIR for Combustion and VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallingLOG Sizing Requirements Minimum Fireplace ClearanceMinimum Wall and Ceiling Clearances see Figure Minimum Non Combustible Material Clearances Log Set Installing Minimum Non Combustible Material ClearancesFloor Clearances Attaching Damper Clamp Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Installing Heater Base AssemblyMounting Bracket Connecting to GAS Supply Gas Connection Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig Pressure Testing Heater Gas ConnectionsInstalling Logs InstallingOperating Heater For Your Safety Read Before LightingHeater OperatingManual Lighting Procedure Control Knob Ignitor Button Pilot Flame Pattern Inspecting BurnersThermostat-Controlled Models Only ODS/PILOT and Burner CleaningMaintenance Trouble ShootingTROUBLE- Shooting Maintenance,Refer to Air for Com Gas leak. See Warning Optional Optional Positioning of Thermostat Sensing Bulb Service Hints Technical ServiceModel Models Parts Not Under Warranty Parts Under WarrantyParts Central Hood GA6052 AccessoriesValve GA5010 Hood GA6050Illustrated Parts Breakdown CGD3018N CGD3924N CGD3930N Parts ListCGD3924NT CGD3924NT 102990 102990 Keep this Warranty Warranty Information