Quadra-Fire 1100-I Floor Protection, Chimney and Exhaust Connections, Mobile Home Installation

Page 8

FLOOR PROTECTION

This unit may be installed on combustible flooring, providing there is 1 1/2” (37mm) of air space from the base to combustible floor, or it is placed on nominal 4” (100mm) hollow concrete blocks or any insulating material with a minimum R value of 2.5.

CHIMNEY AND EXHAUST CONNECTIONS

1.CHIMNEY AND CONNECTOR: Use 3” (75mm) or 4” (100mm) diameter listed “L” or “PL” venting systems. The insert can be either vertically or horizontally vented.

2.FIREPLACE INSTALLATION: Stainless steel rigid or flexible pipe.

3.AS A BUILT-IN: Use double-wall pipe with a stainless steel inner liner.

NOTE: All pipes are recommended to be sealed with high temperature RTV silicone.

NOTE: DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENT OF THIS INSERT.

When installing the insert as a built-in, the insert is approved for horizontal exhaust. However, we recommend that the exhaust be installed vertically for at least eight feet, or above the eaves of the house. This will help draw smoke out of the insert in the event of a power failure.

MOBILE HOME INSTALLATION

1.An outside air inlet must be provided for combustion air, and be unrestricted while the insert is in use.

2.The combustion air duct system must be made of metal, permit zero clearance to combustible construction, prevent material from dropping into the inlet or into the area beneath the dwelling, and contain a rodent screen.

3.The insert is to be secured to the mobile home. You may drill a hole through the outer panel and secure it to the wall with a ¼” x 2” lag bolt or equivalent.

4.Do not install the insert in a sleeping room.

5.The structural integrity of the mobile home floor, walls, and ceiling/roof must be maintained.

6.This insert is to be grounded with #8 copper grounding wire or equivalent, terminated at each end with an N.E.C. approved grounding device.

7.Refer to clearance to combustibles section (page 6) for measurements to combustibles, and appropriate chimney and venting systems for your application.

VENT TERMINATION REQUIREMENTS

1.Do not terminate vent in an enclosed or semi-enclosed area such as a carport, garage, attic, crawl space, under a sundeck or porch, narrow walkway or closely fenced area, or any location that can build up a concentration of fumes such as a stairwell, covered breezeway, etc.

2.Vent surfaces can get hot enough to cause burns if touched. Noncombustible shielding or guards may be required.

3.Termination must exhaust above air inlet elevation. It is recommended that at least five feet of vertical pipe be installed when the appliance is vented directly through a wall to create some natural draft, to prevent the possibility of smoke or odor during appliance shutdown, and to keep exhaust from causing a nuisance or hazard by exposing people or shrubs to high temperatures. In any case, the safest and preferred venting method is to extend the vent through the roof.

4.Distance from doors and windows, or gravity or ventilation air inlet into building:

a)Not less than 4’ (1.2m) below;

b)Not less than 4’ (1.2m) horizontally from;

c)Not less than 1’ (305mm) above.

5.Distance from bottom of termination and grade - 12” (305mm) minimum. This is conditional upon the plants and nature of grade surface. The grade surface must not be a lawn. Distance from bottom of termination to public walkway

-7’ (2.1m) minimum.

6.Distance to combustible materials - 2’ (510mm) minimum. This includes adjacent buildings, fences, protruding parts of the structure, roof overhang, plants and shrubs, etc.

Page 8

Image 8
Contents NorthAmerica’sBest Page Table of Contents Safety Label Page Listings and Specifications InstallationPage Mobile Home Installation Floor ProtectionChimney and Exhaust Connections Vent Termination RequirementsPower Supply Thermostat Installation100mm Diameter Pipe only Or 4 76mm or 100mm Diameter Pipe Feed Adjustment Instructions Operating Instructions Fuel Size and MaterialBefore Your First Fire Start Your First FireCleaning and Maintenance Door Glass Cleaning and Replacement Reading the Fire and Adjustment ProceduresComponent Information Blower #1 Small Convection Blower Feed SystemIgniter Door GasketTroubleshooting Thermostat will not Start Unit Unit Fails to Shut OFFSmoke from the Convection AIR Outlet Convection Blowers Keep Running or Fail to StartPage Lifetime warranty

1100-I specifications

The Quadra-Fire 1100-I is a renowned wood-burning insert, designed to deliver robust performance and efficiency for homeowners looking to enhance their heating solutions. Known for its sleek finish and effective heating capabilities, this model is an excellent choice for those who want to experience the warmth and ambiance of a traditional wood fire.

One of the standout features of the Quadra-Fire 1100-I is its impressive heating capacity. With the ability to heat spaces up to 2,000 square feet, it makes an ideal option for medium to large homes. This wood insert boasts a nominal output of 65,000 BTUs, providing sufficient warmth even in the coldest winters. Its efficient design allows for long burn times of up to 10 hours, ensuring that you can enjoy continued warmth throughout the night without the need for constant refueling.

A critical technology incorporated in the Quadra-Fire 1100-I is its Advanced Combustion System. This system utilizes a secondary combustion process that minimizes emissions and maximizes efficiency. As the fire burns, it re-burns the gases and particulates that would typically escape into the atmosphere, resulting in a cleaner and more environmentally friendly burn. This feature not only reduces the impact on the environment but also enhances fuel efficiency, saving homeowners money on wood consumption.

The insert features a large ceramic glass door that allows for a captivating view of the fire, adding a cozy and inviting ambiance to any room. The glass is designed to withstand high temperatures without warping or discoloring, ensuring a clear view for years to come. Additionally, the Quadra-Fire 1100-I offers an easy-to-use airflow control system, allowing you to adjust the flame and heat output according to your preferences, making it easy to manage your heating needs throughout the day.

Installation of the Quadra-Fire 1100-I is straightforward, as it is designed to fit into existing fireplaces, eliminating the need for extensive renovations. The unit is also available with several finishing options, allowing homeowners to choose a look that complements their interior design.

In summary, the Quadra-Fire 1100-I is an ideal wood-burning insert for those seeking efficiency, environmental consciousness, and aesthetic appeal. With its powerful heating ability, advanced combustion technology, and striking design, it stands out as a reliable and attractive choice for anyone looking to add a wood-burning solution to their home.