CWC Series Woodburning Fireplace
COMMON MATERIALS AND FACTORS
MATERIAL | K* | R | MINIMUM | |
THICKNESS | ||||
EH2416 | 0.458 | 1.09 | 0.50 in.** | |
(MHSC) | ||||
|
|
|
|
|
Common Brick | 5.0 | 0.10 | 5.46 in.** | |
|
|
|
|
|
R Value is for 1/2 inch.
*Units of K = BTU/SQ FT/HR/˚F/IN ** Thickness of Listed Material
FP533ADD
Fig. 25 Hearth extension material factors.
Example of Determining Hearth Extension Equivalents
NEW | K of new material (per inch) | thickness |
required | = | X of listed |
thickness | K of listed material (per inch) | material |
To determine the thickness required for any new mate- rial:
Wall Covering
Noncombustible
Decorative
Facing
Seal all cracks between fireplace surround and wall materials with noncombustible material.
Noncombustible
Decorative
Covering
Hearth Extension
Insulation
Side View
2x4" Header - Do not notch at standoffs.
Seal crack between fireplace and hearth extension with noncombustible material.
Safety Strips -
Must be overlapped
Z\x" minimum.
Example for Common Brick
T (new) = 5.0 / 0.458 x 0.50 in. = 5.46 in. (new re- quired thickness).
FP550
Fig. 26 Sealing gaps.