DO NOT USE ANY MAKESHIFT MATERIALS DURING INSTALLATION.
1.Move the stove into position with the flue centered, midpoint between two joists to prevent having to cut them. Use a plumb bob to line up the centre.
2.Cut and frame an opening in the roof to provide a 2" clearance between the outside of the chimney and any combustible material.
DO NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL.
Nail headers between the joist for extra support. Firestop spacers must be placed on the bottom of each framed opening in any floor or ceiling that the chimney passes through.
3.Hold a plumb bob from the underside of the roof to determine where the opening in the roof should be. Cut and frame the roof opening to maintain proper 2" clear- ances.
MOBILE HOME INSTALLATION
PEDESTAL MODEL 1100 IS APPROVED FOR IN- STALLATION IN MOBILE HOMES IN BOTH CANADA AND THE UNITED STATES.
PEDESTAL MODEL 1400 IS APPROVED FOR IN- STALLATION IN MOBILE HOMES IN THE UNITED STATES ONLY.
HEADERS |
FIRESTOP SPACER -
UNDERSIDE OF JOIST
FIGURE 5
ADDING CHIMNEY SECTIONS
FIGURE 8
The pedestal base must be firmly bolted to the floor with 1/4 inch lag bolts. Minimum clearances to combustibles are as shown in FIGURE 8.
VENTING | FIGURE 9 | |
| ||
Connect the stove to a | RAIN CAP | |
chimney system using |
| |
a listed double wall con- | MOBILE HOME | |
nector, Security DL6 | ||
in Canada or Dura | ROOF FLASHING | |
RADIATION SHIELD | ||
Vent DVL in the U.S.A. | ||
| ||
Use chimney system | CEILING SUPPORT | |
|
Add chimney sections, twist lock- ing (clockwise) securely, to the re- quired height. The chimney must extend, at least, 3 feet above its point of contact with the roof and at least 2 feet higher than any wall, roof or building within 10 feet. FIGURE 6. If your chimney sys- tem is enclosed within the attic area, a rafter radiation shield is required.
2 FT. |
|
MIN. | 3 FT. |
| 10 FT. |
| MIN. |
FIGURE 6
listed to ULC S629 in | TRIM COLLAR |
|
|
|
|
|
|
|
|
| ||||||||
Canada or either of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Simpson |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
chimney models SDP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
or Dura Tech in the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
U.S.A. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The chimney must be |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
installed in accordance | STOVE BOLTED |
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||||||||
with the manufacturer's | TO FLOOR |
|
|
|
|
|
|
|
|
|
| |||||||
instructions. Use only | HEARTH PAD |
|
|
|
|
|
|
|
|
| ||||||||
specified components |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PEDESTAL MODELS OUTSIDE AIR
If possible connect the air intake at the pedestal's back or bottom to the outside with a 4 inch (100mm) diameter fresh air kit available at your Napoleon/Wolf Steel Ltd. dealer. Follow detailed instructions under "Mobile Home Outside Air".
FIGURE 7
with no substitutions. | OUTSIDE AIR CONNECTION | |
The chimney and pipe | ||
THROUGH WALL OR FLOOR | ||
must extend at least 8 |
|
feet above the stove and 3 feet above the highest point of the roof. Install a rain cap at the top which will not impede the smoke exhaust. The chimney must be sup- ported at the ceiling or roof so that its weight does not rest on the stove.
It must be installed between ceiling joists, with radia- tion shield and roof flashing, so that the structural strength, insulation and waterproof qualities of the home are not lessened. Seal with silicone to maintain a va- pour barrier at the chimney and outside air pipe penetrations.