In the United States, continued:
If a continuous liner is not installed, a "direct flue con- nection" must be made. The direct flue connection re- quires a
1401 INSERT MODEL
An optional low clearance flue connector is available to facilitate hook up into a tight fitting fireplace. Consult your local dealer for details.
INSTALLATION INTO A FACTORY BUILT FIREPLACE.
The following installation requirements must be ob- served when installing solid fuel burning inserts into factory built fireplaces.
1.The factory built fireplace must be listed per UL 127 or ULC S610.
2.Clearances to any combustible material surround- ing this insert as identified in Figure 10 must be fol- lowed. These clearance requirements supersede any
3.Installation must include a full height listed chimney liner meeting HT requirements (2100°F) per 1777 (U.S.) or ULC S635 (Canada). The liner must be securely at- tached to the insert flue collar and the chimney top.
4.Means must be provided to prevent room air pas- sage to the chimney cavity of the fireplace. This may be accomplished by sealing the damper area around the chimney liner, or sealing the fireplace front.
5.The air flow within and around the fireplace shall not be altered by the installation of the insert (i.e. no lou- vres or cooling air inlet or outlet ports are blocked), unless specifically tested as such for each factory built fireplace manufacturer and model line. (Note - using a louvred face plate (surround) complies with this require- ment)
6.Alteration of the fireplace in any manner is not per- mitted with the following exceptions;
a.external trim pieces which do not affect the opera- tion of the fireplace may be removed providing they can be stored on or within the fireplace for reassembly if the insert is removed.
b.the chimney damper may be removed to install the chimney liner.
7.Circulating air chambers (i.e. in a steel fireplace liner or metal heat circulator) shall not be blocked.
8.Means must be provided for removal of the insert to clean the chimney flue.
9.Inserts that project in front of the fireplace must be supplied with appropriate support means.
10.A permanent metal warning label must be attached to the back of the fireplace stating that the fireplace must be restored to its original condition for safe use without the insert.
OPTIONAL FAN INSTALLATION
Drywall dust will penetrate into the fan bearings, causing irreparable damage. Care must be taken to prevent drywall dust from coming into contact with the fan or its compartment. Any damage re- sulting from this condition is not covered by the warranty policy.
Use of the fan increases the output of heat.
STOVE MODELS: Provisions have been made on the stove to install an optional blower kit
LEG MODELS ONLY
Note: if the optional blower (
Attach the mounting bracket to the blower assembly. Then attach the mounting bracket to the back of your stove, push on the variable speed knob and plug into any grounded electrical outlet.
MOUNTING
BRACKET
BLOWER |
ASSEMBLY |
VARIABLE |
SPEED |
SWITCH |
BLOWER GUARD
FIGURE 12
INSERT MODELS:
The 1401 insert comes equipped with two fans, while the 1101 has one fan. These fans are thermally acti- vated. Depending on the intensity of the fire, the fans will start