Vermont Casting 2468, 2467 manual Troubleshooting / Honeywell #8420 Gas Control System

Page 15

Dutchwest Natural Vent Gas Heater

Troubleshooting / Honeywell #8420 Gas Control System

NOTE: Before troubleshooting the gas control system, be sure the external gas shutoff is in the “ON” position.

WARNING: REMOVE THE GLASS PANEL BEFORE PERFORMING ANY GAS CONTROL SERVICE WORK.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1.

Spark ignitor will

A. Defective or misaligned

Using a match, light [ilot. If pilot lights, turn off pilot and

 

not light

electrode at the pilot

push the ignitor button again. If pilot will not light, check

 

 

 

gap at electrode and pilot - it should be 1/8” to have a

 

 

 

strong spark.

 

 

B. Defective ignitor (push

Push piezo ignitor button. Check for spark at electrode

 

 

 

 

button)

and pilot. If there is no spark at the pilot, and electrode

 

 

 

wire is properly connected, replace ignitor.

2.

Pilot will not stay lit

A. Defective pilot generator

Check pilot flame. It must impinge on the thermocouple

 

 

after carefully fol-

(thermocouple)

or thermopile. NOTE: This pilot burner assembly uses

 

lowing the lighting

 

both a thermocouple adn a thermopile. The thermo-

 

instructions

 

couple operates the pilot flame. Tighten the thermo-

 

 

 

couple. The thermopile operates the main valve. (ON

 

 

 

and OFF) Clean and/or adjust pilot for maximum flame

 

 

 

impingement on thermocouple and thermopile.

 

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot; millivolt

 

 

 

operator

mete should read greater than 10mV. If the reading is

 

 

 

okay and the pilot does not stay on, replace the gas

 

 

 

valve. NOTE: An interrupter block (not supplied) must

 

 

 

be used to conduct this test.

 

 

C.Defective safety switch

Check the continuity accross the safety limit switch with

 

 

 

 

the unit cold. If there is no continuity, the safety switch

 

 

 

needs to be replaced.

3.

Pilot lights, no gas

A. Remote switch or wires

Check rocker switch and wires for proper connection

 

 

to burner, valve

defective

Use jumper wires across terminals at rocker switch. If

 

knob ON, remote

 

burner lights, replace rocker switch. If okay, use jumper

 

switch (rocker

 

wires across rocker switch wires at the valve. If burner

 

switch) ON

 

lights, wires are faulty or connections are bad.

 

 

B. Thermopile may not gen-

1. Be sure wire connecitons from thermopile at gas

 

 

 

ate sufficient voltage

valve terminals are tight and thermopile is fully inserted

 

 

 

into pilot bracket.

 

 

 

2. One of the rocker switch wires may be grounded

 

 

 

Remove rocker switch wire form valve termianls. If

 

 

 

burner now stays lit, trace rocker switch wiring from

 

 

 

ground. It may be grounded to the appliance of the

 

 

 

gas supply line.

 

 

 

3. Check the thermopile with a millivolt meter. Take

 

 

 

reading at thermopile (“TP” and “TP/TH”) terminals of

 

 

 

gas valve. Should read 325 millivolts minimum while

 

 

 

holding valve knob depressed in PILOT position and

 

 

 

with rocker switch OFF. Replace faulty thermopile if

 

 

 

reading is below specified minimum.

 

 

C. Plugged burner orifice

Check burner orifices for debris, and remove.

 

 

 

D. Defective automatic valve

Turn knob to ON, place rocker switch to ON. Millivolt

 

 

 

operator

meter should read greater than 10mV. If the reading is

 

 

 

okay and the burner does not light, replace the valve.

4.

Frequent pilot out-

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

 

 

age

or high, (blowing or lifting).

impingement on thermocouple and thermopile.

 

 

causing the pilot to drop out

 

 

 

 

 

B. Possible blockage of the

Check the vent termianl for blockage.

 

 

vent terminal

 

 

 

30002008

15

Image 15
Contents Dutchwest Table of Contents Installation & Operating Instructions Dutchwest dimensions Dutchwest Natural Vent Gas Heater DimensionsCeiling Clearances Parallel Installation Minimum Clearance Flue CenterlineCorner Installation Minimum Clearance Flue Centerline Alcove Minimum DimensionsVenting Requirements and Options Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsVenting Requirements Passing Through a Combustible Wall or CeilingAttach the fan assembly to the fan bracket Install the Optional FanAttach rheostat to left side of valve Venting System AssemblyConnect the Gas Supply Line Thermostat Connection optional Install ON/OFF SwitchInstall the Log Set Burner InformationInstall the back, left and right logs Install the Stove FrontOperation Your First FirePilot and Burner Inspection To Turn Off Gas To Heater Lighting and Operating InstructionsSymptom Possible Causes Corrective Action Troubleshooting / Honeywell #8420 Gas Control SystemConversion Precautions Conversion ProcedureFuel Conversion Instructions Remove pilot hood Injector Orifice Size Matrix Conversion to Natural Gas Input BTU/h Air ShutterConversion to LP Input BTU/h Air Shutter Maintenance Check the Gas Flame Regularly Gasket ReplacementStove Disassembly Inspect the Vent System AnnuallyBLK Wiring DiagramsOFF Description Part NumberFuel Conversion Kits Dutchwest Natural Vent Gas HeaterDecorative Rings Optional Accessories AvailableRemote Controls Fan KitsDutchwest Natural Vent Gas Heater 30002008 Limited Lifetime Warranty Model EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings

2467, 2468 specifications

Vermont Castings is known for producing high-quality wood stoves and fireplaces, and among their popular offerings are models 2468 and 2467. These models are lauded for their efficient heating, aesthetic appeal, and innovative technology, making them a favorite for both traditionalists and modern homeowners alike.

One of the standout features of the Vermont Castings 2468 and 2467 models is their exceptional heating capacity. The 2468 can heat spaces up to 2,200 square feet, making it an ideal choice for larger homes, while the 2467 is tailored for medium-sized spaces, comfortably heating up to 1,800 square feet. This makes both models versatile options for various home sizes and layouts.

Both models utilize Vermont Castings’ patented technology, which includes a unique air wash system that keeps the glass clean, providing an unobstructed view of the flames. This enhances the cozy ambiance characteristic of a wood-burning stove, allowing homeowners to enjoy the natural beauty of the fire. Additionally, the stoves feature advanced combustion technology, allowing for a longer burn time and improved efficiency. This means fewer trips to the woodpile and less maintenance overall.

The design of the 2468 and 2467 is another highlight. Available in various finishes and styles, these stoves can complement any decor, from rustic to contemporary. The cast-iron construction not only provides durability but also helps with heat retention, ensuring warm air is released evenly throughout the space.

Furthermore, these models come equipped with user-friendly controls that allow for easy adjustment of combustion levels, ensuring optimal performance and fuel savings. The efficient burn helps in reducing emissions, making both stoves environmentally friendly options that comply with stringent EPA standards.

Homeowners can also benefit from the additional features such as a built-in blower in the 2468 that helps circulate hot air, increasing overall heating efficiency. Both models are designed for easy installation, and with an extensive warranty, Vermont Castings ensures peace of mind for users.

In conclusion, the Vermont Castings 2468 and 2467 wood stoves are emblematic of quality craftsmanship, efficient heating technology, and elegant design. They are excellent choices for those seeking a reliable and attractive heating solution in their home.