Vanguard Managed Solutions VP1000B installation manual Connecting to GAS Supply

Page 13

CONNECTING TO GAS SUPPLY

NOTICE

A qualified service person must connect heater to gas supply. Follow all local codes.

CAUTION

WARNING ICON

G 001

Never connect heater directly to the propane supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane supply.

The installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing rain or sleet.

Propane

Supply Tank

External

Regulator

Vent Pointing

Down

Figure 12 - External Regulator With Vent Pointing Down

CAUTION

WARNING ICON

G 001

Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe 3/8" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.

Installation must include a manual shutoff valve, ground joint union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13, page 14).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION

WARNING ICON

G 001

Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 13, page 14. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

Continued

13

 

099406

Image 13
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualContents Safety Information Safety Information Safety Device Local Codes Unpacking Product FeaturesProduct Identification Piezo Ignition SystemProducing Adequate Ventilation Fresh AIR for Combustion and VentilationUnusually Tight Construction Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Ventilation AIRNever install the heater A bathroom A recreational vehicle Installation ItemsCheck GAS Type Locating HeaterMarking Screw Locations Installing Heater to WallFolding Anchor Installing Two Mounting ScrewsPlacing Heater On Mounting Screws External Regulator With Vent Pointing Down Connecting to GAS SupplyPressure Testing GAS Supply Piping System Connecting to GAS Supply Checking GAS ConnectionsManual Shutoff Valve Pressure Testing Heater GAS ConnectionsOperating Heater For Your Safety Read Before LightingControl knob and turn counterclockwise C-clockwise Pilot Flame Pattern Operating Heater Inspecting BurnerShutting Off Heater Shutting Off Burner Only pilot stays litCorrect Burner Flame Pattern Burner Flame PatternODS/PILOT and Burner Orifice Cleaning and Maintenance Trouble ShootingCabinet TROUBLE- Shooting See CleaningCleaning and Mainte Trouble ShootingTop Ing statement atService Hints Technical ServiceParts Under Warranty Replacement Parts Service Publications AccessoryParts Not Under Warranty Valve GA5010Heater Exploded View KEY Part Number Description QTY Parts ListKeep this Warranty Warranty Information