•Controller terminal L to heat pump terminal L
•Controller terminal W to heat pump terminal W (see section 2.5)
•Controller terminal G to heat pump terminal G (see section 2.5)
2.4 24 V Transformer
You might need a 24 V transformer if you have an
2.5 RC845 Relay
If you have an
•relay terminals W, G and C to controller terminals W, G and C.
•relay terminals T and T to the appropriate furnace terminals: T and T (oil); TH and TH (gas); R and W (electric).
NOTE: Refer to the relay’s installation instructions for more details.
2.6 Humidifier
Connect the humidifier to controller terminals C and H (no polarity).
2.7 Outdoor Sensor (AC144-03)
The outdoor sensor is required for the following:
•balance points
•automatic humidity control
•outdoor temperature display
•defrost point
When installing the sensor, observe the following guidelines:
•Avoid locations where the sensor can be covered with snow or exposed to direct sunlight.
•Avoid air outlets and concealed chimneys or stove pipes. Install the sensor using its mounting clip and connect it to controller terminals OS and CS (no polarity).
NOTE: The maximum wire length is 30 m (100 feet).
2.8 Plenum Sensor (AC146-410)
The plenum sensor measures the temperature inside the plenum. This data is required for high pressure protection during the defrost cycle (see section 4.3).
NOTE: The plenum sensor is generally needed for
Install the sensor on the side of the plenum and position it such that its aperture faces the air flow.
Connect the sensor to controller terminals PS and CS (no polarity). For more information, refer to the instructions provided with the sen- sor.
NOTE: The maximum wire length is 30 m (100 feet).
2.9 Dual-energy Input
The
When the contact is open, the heat pump and auxiliary heating operate as usual. The contact closes when the outdoor temperature drops below the set threshold. When the contact is closed, the heat pump is disabled and only the auxiliary heat can be used.
2.10 Unoccupied Mode Input
To use the unoccupied mode, the controller requires a remote con- trol device such as Aube’s telephone controller CT241 equipped with a
2.11Wiring Table
24 Vac In | R | Power; 24 Vac |
| C |
|
Thermostat | TH | Console connection |
| TH |
|
Plenum | PS | Plenum temperature sensor connection |
Sensor | CS |
|
Outdoor | OS | Outdoor temperature sensor connection |
Sensor | CS |
|
Dual Energy | DE | Dual energy connection |
| CC | (requires a normally open contact) |
|
| |
Unoccupied | UN | Unoccupied mode connection |
| CC | (requires a normally open contact) |
|
| |
Heat Pump | R | Power; 24 Vac / 3 A |
| C |
|
| Y | Output; 24 Vac / 1 A (compressor) |
| O/B | Output; 24 Vac / 1 A |
|
| (reversing valve; energized on cool) |
| WW | Input; 24 Vac / 2 mA (defrost) |
| L | Input; 24 Vac / 2 mA (fault) |
Aux. Heat | W | Output; 24 Vac / 1 A (auxiliary heat and fan) |
| G |
|
Humidifier | C | Output; 24 Vac / 1 A |
| H |
|
3. Configuration
3.1 Switch Configuration
To access the 3 configuration switches, loosen the captive screw under the console and separate the console from its base by pulling it from the bottom part.
9/22/06 | 2/8 |