Configuration Menu
Item | Parameters | Display | Options | Default | Description |
|
|
|
|
|
|
1 | Temperature scale |
| °C / °F | °C | Select the temperature display format. |
|
|
|
|
|
|
2 | Balance point low |
| Set the bP L value (see section 4.2). | ||
| (14°F) | ||||
|
|
|
| ||
|
|
|
|
|
|
3 | Balance point high |
| 5°C | Set the bP H value (see section 4.2). | |
| (23°F to 86°F) | (41°F) | |||
|
|
|
| ||
|
|
|
|
|
|
4 | Defrost point |
| 10°C | During defrost, auxiliary heating is activated when the outside | |
| (14°F to 59°F) | (50°F) | temperature is below the defrost point (see section 4.3). | ||
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Set according to the type of heat pump installation (see section |
|
|
|
|
| 4.4). |
|
|
|
|
| Ad |
5 | Installation type |
| Ad / nr | Ad | downstream of the auxiliary heat source. This is generally the |
| case for | ||||
|
|
|
|
| |
|
|
|
|
| nr (normal): Select this setting when the indoor coils are located |
|
|
|
|
| upstream of the auxiliary heat source. This is generally the case |
|
|
|
|
| for new installations. |
|
|
|
|
|
|
6 | Cycles per hour |
| 2 to 6 | 4 | Allows you to select the number of cycles per hour. It is recom- |
| mended to use the default setting except in exceptional cases. | ||||
|
|
|
|
| |
|
|
|
|
|
|
7 | “Smart fan” |
| On / OF | OF | On: “smart fan” is On (see section 4.5). |
| OF: “smart fan” is Off. | ||||
|
|
|
|
| |
|
|
|
|
|
|
8 | Interstage delay |
| 5 to 90 min. | 10 min. | Set the interstage delay (see section 4.6). |
|
|
|
|
|
|
|
|
|
|
| Select between displaying the outdoor temperature or display- |
|
|
|
|
| ing the indoor humidity level. |
9 | Outdoor |
| On / OF | On | On: Displays the outdoor temperature. |
temperature display |
| OF (Off): Displays the indoor humidity level. | |||
|
|
|
| ||
|
|
|
|
| NOTE: To display the outdoor temperature, the outdoor sensor |
|
|
|
|
| must be connected. |
|
|
|
|
|
|
|
|
|
|
| HE (Heat): The humidifier can operate only when heating is |
| Humidifier |
|
|
| activated. |
10 |
| HE / Fn | HE | Fn (Fan): The humidifier can operate as long as the fan is run- | |
operating mode |
| ||||
|
|
|
| ning. | |
|
|
|
|
| |
|
|
|
|
| NOTE: The humidifier is disabled when cooling is activated. |
|
|
|
|
|
|
|
|
|
|
| Allows you to place the humidity adjustment to automatic mode. |
|
|
|
|
| On (automatic): The humidity level is automatically regulated by |
11 | Automatic humidity |
| On / OF | OF | the controller according to the outdoor temperature to avoid |
adjustment |
| condensation or ice formation on windows (see item 12). | |||
|
|
|
| ||
|
|
|
|
| OF (manual): The user manually sets the humidity level (see |
|
|
|
|
| item 12). |
|
|
|
|
|
|
|
|
|
|
| Set the desired humidity level. This parameter is available only |
| Humidity setpoint |
| 5% to 60% | 5% | when the humidity control is placed in manual mode (see item |
|
|
|
|
| 11). |
|
|
|
|
|
|
12 |
|
|
|
| Allows the user to apply an offset to the automatic humidity con- |
|
|
|
| trol. For example, the user can enter a negative offset if there is | |
|
|
|
|
| |
| Humidity offset |
| 0% | still ice formation or condensation on the windows. This param- | |
|
|
|
|
| eter is available only when the humidity control is placed in |
|
|
|
|
| automatic mode (see item 11). |
|
|
|
|
|
|
NOTE: Only the humidity setpoint or humidity offset (item 12) is available when the controller is placed in user mode (SW2 switch).
9/22/06 | 4/8 |