Majestic Appliances SR42A, SC36A, SR36A, SC42A manual Side Wall Protection Hearth Installation

Page 16

SR/SC Series "A" Woodburning Fireplace

Side Wall Protection

Hearth Installation

Adjacent combustible side walls that are within the minimum dimensions shown in Figure 23 of fireplace opening must be protected with CFM Corporation Wall Shield Model SP40 or a specifically built wall shield described below.

The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

Examples of wall shield insulation:

1.Manville - CERAFORM 126, K=.27, 1/2 inches thick

2.CFM Corporation - EH2416, K = .458, 1 inch thick required.

A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for minimum dimensions and mounting detail.

NOTE: Hearth Extension must not cover the air inlet opening of a fireplace.

The hearth extension described in Figure 23 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; refer to Figure 24 for ex- amples. The overall height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.

The top of insulation must be covered with a noncom- bustible decorative covering or a piece of .018” minimum sheet metal, to protect hearth extension material. (Fig. 23)

Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fire- place hearth and hearth extension with a noncombus- tible material. (Figs. 23 and 25)

Minimum Wall Clearances

WITH

WITHOUT

Noncombustible

Noncombustible

Surround Facing

Surround Facing

Shaded area starts

1/2" away from

4" BRICKedge of unit. (Example material)

 

 

 

4"

 

E

F**

FIREBOX

E

D

 

OPENING

 

 

 

 

 

C**

 

A - Min. clearance

 

 

 

 

to combustible

 

 

 

 

perpendicular wall

 

 

SIDE

 

B - Min. clearance

SIDE

WALL

 

to combustible

WALL

 

 

perpendicular wall when

 

 

 

 

using noncombustible wall shield*

 

 

Combustible material permitted within shaded area.

*Noncombustible wall shield requires 1" CFM Corporation EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall. Minimum height and width is 40" x 40".

**Dimension/degree of angle will vary depending on thickness of noncombustible surround facing.

Minimum Hearth Extension Dimensions

(for On-Site Construction)

 

G

G

 

H

 

 

 

J

 

Seal cracks

 

May install

between the

 

noncombustible

fireplace

 

decorative

and hearth

 

covering

extension with

 

OR .018" min.

noncombustible

 

sheet metal

material

FIREPLACE

 

 

HEARTH

4" MIN.

 

 

COMBUSTIBLE

MINIMUM

Safety strips

FLOOR

INSULATION

must overlap

 

VALUE "R"

¹⁄₂" minimum

 

A

B

C

D

E

F

G

H

J

SR/SC36A

16"

12"

48°

41°

18"

14"

7³⁄₄"

16"

48"

 

406mm

305mm

 

 

457mm

356mm

197mm

406mm 1219mm

SR/SC42A

20"

12"

42°

35°

18"

14"

11¹⁄₂"

20"

61¹⁄₂"

 

508mm

305mm

 

 

457mm

356mm

292mm

508mm 1562mm

 

 

 

 

 

 

 

 

 

 

FP594

Fig. 23 Combustible side wall protection and hearth extension dimensions.

16

7412948

Image 16
Contents SR/SC Series a Safety Information Table of ContentsSR36A Series Woodburning Fireplace SR42A Series Woodburning Fireplace Chase Installation Chimney Requirements Offset Installations Installed lengths of chimney sections Planning InformationMounting The Fireplace Planning the Chimney RunInstallation Chase InstallationChimney Supports Insulating Fireplace Enclosure for Cold ClimatesInstalling Electrical Wire For Circulator Models Install Fan Kit AssemblyChimney Setup FramingStraight-Up Chimney Installation Offset InstallationCeiling Chimney Hole Possible Obstructions Cutting the HolePositioning, Safety Strips Securing the Fireplace Installing Outside Air KitInstalling the Chimney System Angle of Chimney at CeilingInstalling the Firestop Spacer Ceiling Hole Proper Firestop Spacer InstallationCanadian Requirements For Insulation ShieldContinue Installing Pipe to Complete Run Install Remainder of Chimney SectionsAdditional Ceilings Penetrating the RoofInstalling Top Housing or Termination Installing Chimney In a ChaseFinishing Finish Wall Front View Side ViewTop View Mantel clearancesSide Wall Protection Hearth Installation Noncombustible Surround FacingCommon Materials and Factors Installing Line for Gas Logs Fireplace Top ViewItem/Model Number 948Accessories Accessory Description Model NumberChimney Components Component Description Model NumberChimney Components cont. Canada Limited Warranty & 30 Year Protection Plan CFM Specialty Home Products