Majestic Appliances SC36A, SR42A, SR36A, SC42A manual Common Materials and Factors

Page 17

SR/SC Series "A" Woodburning Fireplace

COMMON MATERIALS AND FACTORS

MATERIAL

K*

R

MINIMUM

THICKNESS

 

 

 

EH2416

0.50 in.**

(CFM Corporation) 0.458 1.09

 

 

Common Brick 5.0 0.10

5.46 in.**

R Value is for ¹⁄₂ inch.

*Units of K = BTU/SQ FT/HR/ßF/IN

**Thickness of Listed Material

FP533ADD

Fig. 24 Hearth extension material factors.

WARNING: HEARTH EXTENSION MUST BE INSTALLED IN ACCORDANCE WITH FIGURE 23 AND MUST NOT COVER THE BOTTOM FRONT OPENING OF THE CIRCULATING MODEL.

Alternate noncombustible materials may be used providing the (total) thermal resistance (Rt value) of the alternate material employed is greater than or equal to R = 1.09. Thermal resistance (R) or thermal conductivity (K), may be obtained from manufacturer of the material. Factors are related by the formula K = 1/R.

T = given thickness

R = thermal resistance for a given thickness (T) K = thermal conductivity

Noncombustible material with a lower R value may be used, provided thickness of material is sufficiently greater to maintain an equivalent (total) thermal resistance (Rt).

Example of Determining Hearth Extension Equivalents

To determine the thickness required for any new material:

NEW

K of new material (per inch)

thickness

required =

 

x of listed

 

thickness

K of listed material (per inch)

material

Example for Common Brick

T (new) = 5.0/0.458 x 0/50 in. = 5.46 in. (new required thickness).

Side View

Wall Covering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noncombustible

 

 

 

 

 

 

 

 

2 x 4 Header

Decorative

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Do not notch

Facing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at standoffs)

Seal all cracks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

surround and wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

materials with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

noncombustible

 

 

 

 

 

 

 

 

 

 

 

 

 

material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noncombustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Decorative

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Covering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Seal crack between

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hearth Extension

 

 

 

 

 

 

 

 

 

fireplace and hearth

 

 

 

 

 

 

extension with

Insulation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

noncombustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Safety Strips

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be overlapped 1/2"

FP550

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

Fig. 25 Sealing gaps.

7412948

17

Image 17
Contents SR/SC Series a Table of Contents Safety InformationSR36A Series Woodburning Fireplace SR42A Series Woodburning Fireplace Chase Installation Chimney Requirements Offset Installations Planning Information Installed lengths of chimney sectionsMounting The Fireplace Planning the Chimney RunChase Installation InstallationChimney Supports Insulating Fireplace Enclosure for Cold ClimatesInstall Fan Kit Assembly Installing Electrical Wire For Circulator ModelsChimney Setup FramingOffset Installation Straight-Up Chimney InstallationCeiling Chimney Hole Possible Obstructions Cutting the HoleInstalling Outside Air Kit Positioning, Safety Strips Securing the FireplaceInstalling the Chimney System Angle of Chimney at CeilingProper Firestop Spacer Installation Installing the Firestop Spacer Ceiling HoleCanadian Requirements For Insulation ShieldInstall Remainder of Chimney Sections Continue Installing Pipe to Complete RunAdditional Ceilings Penetrating the RoofInstalling Chimney In a Chase Installing Top Housing or TerminationFinishing Finish Wall Front View Side ViewMantel clearances Top ViewNoncombustible Surround Facing Side Wall Protection Hearth InstallationCommon Materials and Factors Fireplace Top View Installing Line for Gas Logs948 Item/Model NumberAccessory Description Model Number AccessoriesComponent Description Model Number Chimney ComponentsChimney Components cont. Canada Limited Warranty & 30 Year Protection Plan CFM Specialty Home Products