DRAFT DIVERTER
The draft diverter must be installed in the same atmospheric pressure zone as the combustion air supply for the main burner.
DOOR KNOB
Remove from the inside of the casing door and assemble to the outside of the door. VC201 and VC202 have finger holes in the door in lieu of knob.
| Ceiling |
|
34 IN. | 18 IN. |
|
45.72 CM |
| |
86.36 CM |
| |
|
| |
| 22 IN. | Wall |
55.88 CM | ||
| 6 IN. |
|
| 15.2 CM |
|
20/35 | 13 IN. |
|
| 33 CM |
|
Floor
CLEARANCES - VC20, VC35, VCR35
| Ceiling |
| |
31 IN. | 18 IN. |
| |
45.72 CM |
| ||
78.7 CM |
| ||
|
| ||
| 19 IN. | Wall | |
48.3 CM | |||
| |||
| 6 IN. |
| |
| 15.2 CM |
| |
50/70 | 14 IN. |
| |
| 35.6 CM |
|
Floor
CLEARANCES - VC50 & VC70,
VCR50 & VCR70
WIRING DIAGRAM
CLEARANCES
If the area where the appliance is to be installed contains carpeting, tile, or combustible materials, other than wood flooring, the appliance shall be installed on a metal plate (stoveboard), a wood panel, or other
Clearances to combustibles are as follows:
•From jacket to adjacent side walls, 2” on the 20/35, and 6” on the 50/70. Maintain adequate clearance on right side for accessibility.
•From rear surface vertical vent pipe to rear walls – 6”.
•From rear of unit to rear wall, 13” on 20/35, and 14” on the 50/70.
•From top of heater to ceiling, 34” on the 20/35, and 31” on the 50/70.
•From top of heater to any overhanging projections such as a mantle or window sill is 22” on the 20/35, and 19 inches on the 50/70 models, with a maximum horizontal extension of 18 inches.
The clearances around the air opening into the combustion chamber must be maintained, and the burner must be kept clean.
Do not permit dust or dirt to accumulate here. The other clearances previously mentioned must be maintained.
There must be adequate room provided and maintained around the heater for accessibility and for the flow of combustion and ventilation air.
TEMPERATURE
CONTROL
BLOCKEDFLUE
SWITCHPILOT GENERATOR