TSK WALL STAT KIT OPTIONAL

(VC/VCR-H SERIES HEATERS)

WALL THERMOSTAT INSTALLATION INSTRUCTIONS

Your heater can be re-wired to operate with a millivolt wall thermostat by your installer. See wiring diagram below for correct wiring.

NOTE: Do not disconnect the wire from the blocked flue switch to the “TH” terminal on the gas valve.

STEP 1. Disconnect wire leading from Part #70080 (Bulb Control Switch) from valve.

STEP 2. Cut the remaining wire leading from Part #70080 (Bulb Control Switch) to the blocked flue switch, leaving its end connected to the blocked flue switch and leaving enough length to reach the gas valve. Strip 1/2” of the insulation from the cut end of the wire.

STEP 3. Connect one leg of thermostat wire to the “TH/PP” terminal on the gas valve.

STEP 4. Connect second leg from the thermostat to the stripped wire coming from the blocked flue switch. Secure this connection inside the heater cabinet.

STEP 5. Secure both red wires from blocked flue switch inside heater cabinet. Make sure none of the wires have enough slack to lay against the heat exchanger or draft hood.

THERMOSTAT

OPTIONAL

BLOCKED

FLUE SWITCH

PILOT

GENERATOR

WIRE

NUT

(Not provided)

Page 14

Image 14
Contents Natural GAS This Unit is not to be Installed in Mobile HomesWhat to do if YOU Smell GAS VCR351A-H VCR501A-H VCR701A-H Propane GASRoom Heater Specifications Table of ContentsRead Carefully Before Installing Unit Specifications Type Control GAS Model NumbersPossible Causes Corrective Action IntroductionVenting Connecting the Vent Into AN Existing Chimney Unsafe RecommendedLocation and Speical Precautions GAS SupplyCombustion and Ventilation AIR UL Listed Vent Cap UL Listed Gas Vent OpeningClearances Draft DiverterDoor Knob Ment Pilot AdjustmentPilot Flame Adjust Radiants and Glass PanelsMaintenance Cleaning of Combustion ChamberFor Your Safety Read Before Lighting What to do if YOU Smell GASTrouble Shooting Chart for qualified serviceman Main Burner Symptom Possible Causes Corrective ActionTrouble Shooting Chart Automatic Pilot & Valve If any part of the original wire as suppied TSK Wall Stat KIT Optional Models Included REV /05March Revised 01/05 *2 Required Tampering is Dangerous Critical Safety Points to RememberYour GAS Control and Pilot Light System If YOU Smell GAS, DON’T Light ITLimited Warranty