Franklin SS-PCB50, Self-Contained Package Air Conditioner Electrical Connections, Electric Heat

Page 4

PRODUCT SPECIFICATIONS

ELECTRICAL CONNECTIONS

MODEL

B

 

 

PCB090-5

7⅞” (200 mm)

 

 

PCB120-5

23⅞” (606 mm)

 

 

PCB180-5

23⅞” (606 mm)

 

 

1– Main power entrance location (with electric heat installed)

2– Control wiring entrance location

3– Main power entrance location (without electric heat installed)

Note: Single-point wiring is available at location #1 when heat kit is installed. See installation instructions for heat kits.

FIGURE 3. ELECTRICAL HEAT UNITS

ELECTRIC HEAT

ELECTRIC HEAT AIR TEMPERATURE RISE @ NOMINAL VOLTAGE

Heater Model

HKCB20

HKCB30

HKCB40

 

No. Stages

 

2

2

2

Output MBH (W)

67.5

(19.8)

101.3 (29.7)

135.0 (39.6)

 

 

2600 (1227)

24.2

(13.4)

36.2 (20.1)

-

 

 

 

 

 

 

 

 

 

2800 (1320)

22.5

(12.5)

33.6 (18.7)

-

 

 

 

 

 

 

 

 

 

3000 (1415)

21.0

(11.7)

31.4 (17.4)

-

 

 

 

 

 

 

 

 

 

3200 (1510)

19.7

(10.9)

29.4 (16.3)

39.3 (21.8)

 

 

 

 

 

 

 

 

 

3400 (1605)

18.5

(10.3)

27.7 (15.4)

37.0 (20.6)

 

 

 

 

 

 

 

 

3600 (1700)

17.5 (9.7)

26.2 (14.6)

34.9 (19.4)

 

 

 

 

 

 

 

 

3800 (1793)

16.5 (9.2)

24.8 (13.8)

33.1 (18.4)

 

 

 

 

 

 

 

 

4000 (1888)

15.7 (8.7)

23.5 (13.1)

31.4 (17.4)

CFM

 

 

 

 

 

 

 

4200 (1982)

15.0 (8.3)

22.4 (12.4)

29.9 (16.6)

&

 

 

 

 

 

 

 

 

4400 (2076)

14.3 (7.9)

21.4 (11.9)

28.6 (15.9)

(L/S)

 

 

 

 

 

 

 

4600 (2171)

13.7 (7.6)

20.5 (11.4)

27.3 (15.2)

 

 

 

 

 

 

 

 

4800 (2265)

13.1 (7.3)

19.6 (10.9)

26.2 (14.6)

 

 

 

 

 

 

 

 

5000 (2360)

12.6 (7.0)

18.8 (10.4)

25.2 (14.0)

 

 

 

 

 

 

 

 

5200 (2454)

12.1 (6.7)

18.1 (10.1)

24.2 (13.4)

 

 

 

 

 

 

 

 

5400 (2548)

11.6 (6.4)

17.4 (9.7)

23.3 (12.9)

 

 

 

 

 

 

 

 

5600 (2643)

11.2 (6.2)

16.8 (9.3)

22.5 (12.5)

 

 

 

 

 

 

 

 

5800 (2737)

10.8 (6.0)

16.2 (9.0)

21.7 (12.1)

 

 

 

 

 

 

 

 

6000 (2832)

10.5 (5.8)

15.7 (8.7)

21.0 (11.7)

 

 

 

 

 

 

 

NOMINAL VOLTAGE FOR HKCB

 

@ 480V

@ 415V

@ 380V

HKCB20-4

19.8 kW

14.9 kW

12.5 kW

HKCB30-4

29.7 kW

22.3 kW

18.7 kW

HKCB40-4

39.6 kW

29.7 kW

25.0 kW

4

Notes:

1.Maximum air temperature rise of 40°F (22.2°C) must not be exceeded.

2.See Electric Heater Availability table for various unit sizes.

3.Air temperature rise is for total heating capacity: Temperature rises at other conditions may be calculated by using the formula:

Temperature Rise =

Output Capacity - BTU/h

 

1.08 x ft³/min. Airflow

Note: Temperature rises must be calculated in other than nominal volt- age conditions.

4.For altitudes over 2,000’, air temperature rise must be calculated using the formula:

Temperature Rise = Output Capacity - BTU/h

14.4x ft³/Min. Airflow x Specific Weight of Air

5.Operation at less than nominal voltages must be de-rated by the following factors: 415 volt-0.75; 380 volt-0.63.

ELECTRIC HEATER AVAILABILITY

Unit Size

HKCB20

HKCB30

HKCB40

X

X

X

10

X

X

X

15

X

X

X

SS-PCB50

Image 4
Contents PCB Specifications NomenclatureDimensions Vertical DischargeElectrical Connections Electric HeatFAN Performance Data Supply FAN Drive Data PCB090Supply FAN Drive Data PCB120 Supply FAN Performance PCB180 Supply FAN Drive Data PCB180PCB090-5 English Units PCB090-5 SI UnitsCooling Capacity Data PCB120-5 English Units PCB120-5 SI UnitsPCB180-5 SI Units PCB180-5 English Units Evaporator Motor HeatApplication Details and Accessories Rooftop Lift KIT RLK90-120Quality Makes the Difference