Franklin SS-PCB50 specifications PCB180-5 English Units, Evaporator Motor Heat

Page 10

PRODUCT SPECIFICATIONS

COOLING CAPACITY DATA (CONT.)

PCB180-5 (ENGLISH UNITS)

INDOOR

 

 

 

 

 

CONDENSER AIR TEMPERATURE

 

 

 

 

 

AIR

 

 

75°F

 

 

85°F

 

 

95°F

 

 

105°F

 

 

115°F

 

SCFM

WB

Total

Sens

Kw

Total

Sens

Kw

Total

Sens

Kw

Total

Sens

Kw

Total

Sens

Kw

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

 

 

 

 

 

 

 

 

 

 

72

219.0

100.8

16.42

205.3

95.6

18.63

191.7

90.4

20.83

178.0

85.1

23.04

164.4

79.9

25.25

4760

 

67

202.0

121.4

15.36

188.6

117.7

17.50

175.2

113.9

19.63

161.8

110.2

21.76

148.4

106.5

23.89

 

62

183.8

149.6

14.67

174.5

142.9

16.64

165.2

136.3

18.61

155.9

129.6

20.59

146.6

123.0

22.56

 

 

 

 

57

177.6

162.6

14.10

167.2

152.7

16.15

156.9

142.8

18.21

146.5

132.9

20.27

136.1

123.0

22.33

 

 

72

228.3

111.6

16.97

213.6

106.3

19.21

199.0

100.9

21.45

184.3

95.5

23.68

169.6

90.1

25.92

5600

 

67

209.5

142.7

15.87

196.0

136.9

18.05

182.5

131.0

20.22

169.0

125.2

22.40

155.5

119.3

24.46

 

62

191.1

174.8

14.77

180.5

164.7

17.00

169.8

154.6

19.23

159.1

144.5

21.46

148.4

134.4

23.68

 

 

 

 

57

191.1

174.8

14.77

180.5

164.7

17.00

169.8

154.6

19.23

159.1

144.5

21.46

148.4

134.4

23.68

 

 

72

233.9

119.7

17.33

219.1

114.8

19.59

204.4

109.9

21.85

189.6

105.0

24.11

174.9

100.1

26.37

6440

 

67

215.1

160.4

16.27

201.5

153.6

18.46

187.9

146.8

20.64

174.3

140.0

22.83

160.7

133.2

25.01

 

62

202.0

185.6

15.49

190.4

174.7

17.76

178.8

163.9

20.03

167.1

153.0

22.30

155.5

142.1

24.57

 

 

 

 

57

202.0

185.6

15.49

190.4

174.7

17.76

178.8

163.9

20.03

167.1

153.0

22.30

155.5

142.1

24.57

Sensible heat capacities shown are based on 80 °F DB entering air at the evaporator coil. For sensible heat capacities at other than 80 °F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80 °F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80 °F.

EVAPORATOR MOTOR HEAT

Horsepower/(kW)

BTU/h (KW)

 

 

2 (1.49)

4400 (1.29)

 

 

3 (2.24)

6200 (1.82)

 

 

5 (3.73)

10,500 (3.08)

 

 

10

SS-PCB50

Image 10
Contents PCB Specifications NomenclatureDimensions Vertical DischargeElectrical Connections Electric HeatFAN Performance Data Supply FAN Drive Data PCB090Supply FAN Drive Data PCB120 Supply FAN Performance PCB180 Supply FAN Drive Data PCB180PCB090-5 English Units PCB090-5 SI UnitsCooling Capacity Data PCB120-5 English Units PCB120-5 SI UnitsPCB180-5 SI Units PCB180-5 English Units Evaporator Motor HeatApplication Details and Accessories Rooftop Lift KIT RLK90-120Quality Makes the Difference