IMMERSION TEMPERATURE HIGH LIMIT CUT-OFF
1.Disconnect power from unit.
2.Remove access cover.
3.Remove high limit cover screw and cover.
Cover
Cover Screw
Reset Switch ![]()
4. Disconnect the two (2) 14 gauge wires.
Wires ![]()
Capillary Tube
5. Remove capillary tube and bulb from thermowell
6. Remove two (2) mounting screws.
Mounting Screws ![]()
7.Remove control and install new high limit switch by performing above steps in reverse order. (Note: Be sure to place capillary tube into slot in base prior to installing cover.)