Lennox International Inc G50UH-60D-135 Filter Size, Supply Air Plenum, Combustion Air Inducer

Page 12

Thisunitisnotequippedwithafilteror rack.A field-pro-

videdhigh-velocityfilterisrequiredfortheunittooperate

properlyTable1listsrecommendedfiltersizes.. Afiltermustbein placeanytimetheunitisoperating.

TABLE 1

Furnace

 

Filter Size

 

Cabinet Size

Side Return

Bottom Return

 

14-1/2"

16X25X

1 (1)

14X25X1

(1)

17-112"

16X25X

1 (1)

16X25X1

(1)

21"

16X25X

1 (1)

20X25X

1 (1)

24-1/2"

16 X 25 X

1 (2)

24X25X

1 (1)

Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.

NOTE - Do not operate the furnace with an external static pressure that exceeds 0,5 inches w,c, Higher external stat- ic pressures may cause erratic limit operation,

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct, The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed, The furnace access panel must always be in place when the furnace is operat- ing and it must not allow leaks into the supply air duct sys- tem,

Return Air Plenum

Return air must not be drawn from a room where this furnace, or any other gas appliance (ie., a water heat- er), is installed. When return air is drawn from a room, a negative pressure is created in the room, If a gas ap- pliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room, This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system,

In upflow applications, the return air can be brought in through the bottom or either side of the furnace. If a fur- nace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely, Use fiberglass sealing strips, caulking, or equiva- lent sealing method between the plenum and the furnace cabinet to ensure a tight seal, Ifa filter is installed, size the return air duct to fit the filter frame.

A 4-inch diameter flue transition is factory-installed on the combustion air inducer outlet of all models. Modifying or removing the flue transition will cause the unit to oper- ate unsafely and will void the unit certification. The vent connector does not require insulation.

The combustion air inducer may be rotated clockwise or counterclockwise by 90° to allow for top or side vent dis- charge in all applications. When the unit is installed, the flue transition must be in the 9 o'clock, 12 o'clock or 3 o'clock position. The unit will not vent properly with the flue transition pointed down in the 6 o'clock position. Re- move the four mounting screws, rotate the assembly (in- cluding the gasket), then reinstall the mounting screws. See figure 14. Use the provided wire tie to bundle the pres- sure switch wires with the inducer motor power leads. Route the wires away from moving parts and the heat of the inducer motor to prevent damage to the wires.

Combustion Air Inducer

Flue Transition

(Do not remove)

Mounting

Screws

Power Leads

(Remove)

 

 

FIGURE 14

 

Optional

Flue Outlet

(Horizontal

Installation)

 

 

Top View of Furnace

Top Cap ----__ _

 

Flue Outlet

_<_J

Supply Air

Hole /

 

 

Opening

(Reattach

II 111

Cutout Here)

Optional

Flue Outlet

FIGURE 15

Page 12

Image 12
Contents G50UHX Series Supply AIR Gasket FlueTransition FlueBoxGasket HeatExchanger FlueCollectorBoxPackage 1 of 1 contains Wheninstalled,thisfurnacemustbeelectricallygrounded Canada,referto the standardCSAB149installation codes AcautionWiTER/ Room Air from InsideMm at unit front. The unit must be level Equipment in Confined Space ALL AIR from Outside27-5/8 Side View Front ViewLeveling Bolt Installation Inches mm Removingthe Bottom PanelRemoving the Bottom Panel Leveling an Upflow UnitHorizontal Application Unit Installed on Platform Filter Size Supply Air PlenumCombustion Air Inducer HoleVenting Using a Masonry Chimney OutletopeningSeefigure15Thelatesteditionof NationalFuelGasCodeNFPA54 Vent ConnectionCommon Venting Using Tile-Lined Interior Masonry Chimne Combined Vent ConnectorSingle appliance Minimum Vent capacityMaximum Horizontal Inches mm MIN MAX Serving a Single Category I Appliance Type B Double-WallVents with Type B Double-Wall Connectors Serving Two or More Category I AppliancesVent Removal of the Furnace from Common VentPropaneInstallationCodesinCanada Gas Pipe Capacity ft3/hr m3/hrPrecautions and Procedures Interior MAKE-UP BOX InstallationLeak Check Electrostatic Discharge ESDPowER @1HsuN,T INTERIORMAKE-UP BOX InstallationTypical G50UHX Field Wiring Diagram Zk for Correct Number of SecondaryG5OUHX SotFor Your Safety Read Before Lighting ManifoldHoneywell VR8205 Gas Valve with ON/OFF Switch RevolutionPrimary and Secondary Limits FlueAnd Chimney CheckunitforproperdraftG50UHX Burner & Heat Exchanger Removal Ak Caution Diagnostic Normal Heating Mode Abnormal Heating Mode Surelight Control=-l YESlNormalcooling Mode Abnormalcooling Mode YESlYEs BlowerMotorAmps FurnaceBtuInput

G50UH-60D-155, G50UH-36B-090, G50UH-36A-070, G50UH-24A-045, G50UH-60D-135 specifications

Lennox International Inc is renowned for its high-quality heating, ventilation, and air conditioning (HVAC) solutions. Among its versatile product lineup are the G50UH series of gas furnaces, which exemplify efficiency and performance. These models, specifically the G50UH-24A-070, G50UH-24A-045, G50UH-36B-090, G50UH-36A-070, and G50UH-48C-135, offer a range of features tailored to meet varying residential heating demands.

One of the key features of the G50UH series is its energy efficiency. Many models in this lineup boast an impressive Annual Fuel Utilization Efficiency (AFUE) rating, which indicates their ability to convert fuel into usable heat efficiently. These high AFUE ratings can lead to significant savings on energy bills, making these furnaces a cost-effective choice for homeowners.

The G50UH series incorporates advanced technology, including multi-speed blowers that enhance comfort levels. This feature allows for better airflow control and can help maintain consistent temperatures throughout the home. The controlled airflow reduces temperature swings and ensures that every room benefits from the heating provided by the furnace.

Safety is paramount in Lennox designs, and the G50UH series is no exception. Each unit is equipped with safety features designed to protect both the furnace and the home. Dual certification ensures that the products meet stringent safety standards. Moreover, features like a self-diagnostic control board streamline maintenance, allowing homeowners to easily identify potential issues.

Another important characteristic of the G50UH series is its compact design, which is beneficial for homes with limited space. The units are designed to fit comfortably in various installation environments, from basements to utility rooms.

Durability is another hallmark of the G50UH furnaces. Constructed with quality materials, these units are designed for long-term reliability. This ensures that homeowners can enjoy the comfort of their heating systems without frequent repairs.

Lastly, Lennox provides extensive support and warranties, giving homeowners peace of mind associated with their purchase. With options tailored to meet diverse home heating needs, the Lennox G50UH series stands out in the HVAC market, combining efficiency, safety, and reliability in one impressive package.