11 - Are flame rollout switches tripped? If flame rollout switches are tripped, call the service technician for in­ spection.

Heating Sequence Of Operation

(follow steps below or see Figure 29 for more detail)

1 - When thermostat calls for heat, combustion air blower starts.

2 - Combustion air pressure switch proves blower opera­ tion. Switch is factory-set and requires no adjustment.

3 - After a 15-second prepurge, the hot surface ignitor en­ ergizes.

4 - After a 20-second ignitor warm-up period, the gas valve solenoid opens. A 4-second trial for ignition peri­ od begins.

5 - Gas is ignited, flame sensor proves the flame, and the combustion process continues.

6 - If flame is not detected after first ignition trial, the igni­ tion control will repeat steps 3 and 4 four more times before locking out the gas valve (“WATCHGUARD” flame failure mode). The ignition control will then auto­ matically repeat steps 1 through 6 after 60 minutes.

7 - To interrupt the 60-minute “WATCHGUARD” period, move thermostat from “Heat” to “OFF” then back to “Heat.” Heating sequence then restarts at step 1.

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 8

GAS METER CLOCKING CHART

 

Seconds for One Revolution

 

 

 

 

 

 

EL180UHE Unit

Natural

 

LP

 

 

 

 

 

1 cu ft

2 cu ft

1 cu ft

 

2 cu ft

 

 

 

Dial

Dial

Dial

 

DIAL

 

 

 

 

 

 

-045

80

160

200

 

400

 

 

 

 

 

 

-070

55

110

136

 

272

 

 

 

 

 

 

-090

41

82

102

 

204

 

 

 

 

 

 

-110

33

66

82

 

164

 

 

 

 

 

 

-135

27

54

68

 

136

 

 

 

 

 

Natural-1000 btu/cu ft

LP-2500 btu/cu ft

Furnace should operate at least 5 minutes before check­ ing gas flow. Determine time in seconds for two revolu­ tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 8. If manifold pressure matches table 10 and rate is incorrect, check gas orifices for proper size and restric­ tion. Remove temporary gas meter if installed.

NOTE - To obtain accurate reading, shut off all other gas appliances connected to meter.

Supply Pressure Measurement

A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field-provided barbed fitting and connect a manometer to measure supply pressure. See table 10 for proper line pressure. Replace the threaded plug after mea­ surements have been taken.

Manifold Pressure Measurement

1 - Remove the threaded plug from the outlet side of the gas valve and install a field-provided barbed fitting. Connect to a manometer to measure manifold pres­ sure.

2 - Start unit and allow 5 minutes for unit to reach steady state.

3 - While waiting for the unit to stabilize, observe the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.

4 - After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table 10.

NOTE - Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

Proper Combustion

Furnace should operate a minimum 15 minutes with cor­ rect manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue out­ let and compare to the tables below. The maximum car­

bon monoxide reading should not exceed 50 ppm.

TABLE 9

EL180UHE Unit

CO2% For

CO2% For

Nat

L.P.

 

-045

 

 

 

 

 

-070

 

 

 

 

 

-090

7.2 - 7.8

7.5 - 9.0

-110

 

 

 

 

 

-135

 

 

 

 

 

 

 

 

High Altitude

 

 

 

 

 

The manifold pressure may require adjustment and com­ bustion air pressure switch may need replacing to ensure proper combustion at higher altitudes. Refer to table 10 for manifold pressure and table 11 for pressure switch change and gas conversion kits.

IMPORTANT

For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

Page 27

Image 27
Contents Table of Contents Installation Instructions EL180UHEOpening Unit Dimensions inches mmSafety Information EL180UHE Gas FurnaceShipping and Packing List Installed in Combination with a Cooling Coil Use of Furnace as Construction HeaterGeneral Unconfined Space Combustion, Dilution & Ventilation AirConfined Space Air from InsideAir from Outside Equipment in Confined Space Upflow Applications Setting EquipmentReturn Air -- Upflow Applications With transition and filterSingle Side Return Air Removing the Bottom Panel Horizontal ApplicationsReturn Air -- Horizontal Applications Supply Air Plenum Horizontal Application Unit Installed on PlatformFilters Duct SystemUpflow Position VentingReturn Air Plenum Mounting Screws LocationSide Vent Discharge Horizontal Left PositionLeft Side Vent Discharge Right Side Vent DischargeVenting Using a Masonry Chimney Horizontal Right PositionSide Vent Discharge no modifications necessary Vent Connection Upflow and Horizontal Position Common Venting Using Metal-Lined Masonry ChimneyConnector Diameter Maximum Horizontal Connector Length feet mGeneral Venting Requirements Page MIN FAN + FAN FAN + NAT Gas Piping Removal of the Furnace from Common VentGas Supply 103.92 97.69 92.31 Gas Pipe Capacity ft3/hr m3/hrLeak Check Horizontal Applications Possible Gas Piping ConfigurationsPrecautions and Procedures ElectricalThermostat Interior MAKE-UP BOX InstallationAccessory Terminals Generator Use Voltage RequirementsEL180UHE Schematic Wiring Diagram Automatic Hot Surface Ignition System Diagnostic Codes / Status of FurnaceIntegrated Control Integrated ControlUnit Start-Up For Your Safety Read Before LightingHigh Altitude Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionOther Unit Adjustments Service Blower Parts Repair Parts ListML180UHE Burner Assembly & Removal Control Panel PartsStart-Up & Performance Check List Unit Operation Cooling ModeTemperature Drop Temperature Rise

EL180UHE specifications

Lennox International Inc. has long been a leader in providing innovative heating and cooling solutions, and the EL180UHE represents a notable advancement in their line of high-efficiency gas furnaces. Designed to meet the demands of residential heating, this unit combines advanced technology with user-friendly operation and significant energy savings.

One of the standout features of the EL180UHE is its efficiency rating, with an Annual Fuel Utilization Efficiency (AFUE) of up to 80%. This high efficiency not only helps homeowners save on energy bills but also reduces their carbon footprint. The furnace is equipped with a reliable, multi-speed blower motor, which enhances comfort levels by maintaining consistent air circulation throughout the home.

The EL180UHE employs advanced combustion technologies, such as Lennox's low-NOx burner, which minimizes nitrogen oxide emissions, contributing to a cleaner environment. The unit is also designed with a sealed combustion system that draws air directly from the outdoors rather than from inside the home, leading to improved indoor air quality and increased safety.

Another significant characteristic of the EL180UHE is its whisper-quiet operation. This is achieved through well-engineered insulation and a design that minimizes noise levels, allowing for a comfortable living environment without disruptive sounds. Many homeowners appreciate the quiet performance, especially during the night or in spaces where noise is a concern.

The installation process is straightforward, supported by Lennox's user-friendly design. The EL180UHE is compatible with various home configurations and can easily integrate with existing HVAC systems. Additionally, it has a compact footprint, making it suitable for homes with space constraints.

Further enhancing its appeal, this gas furnace features robust warranty options, reflecting Lennox's commitment to quality and customer satisfaction. Homeowners can rest assured that they are investing in a durable product that has been built to last.

In conclusion, Lennox International Inc.'s EL180UHE gas furnace exemplifies the company's dedication to innovation, efficiency, and reliability in home heating solutions. With its high AFUE rating, advanced combustion technology, quiet operation, and user-friendly design, the EL180UHE is an excellent choice for homeowners looking to enhance their comfort while minimizing energy costs.