Lennox International Inc EL180UHE installation instructions Equipment in Confined Space

Page 7

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)

CHIMNEY OR

GAS VENT

VENTILATION LOUVERS

(Each end of attic)

 

OUTLET

 

FURNACE

AIR

WATER

 

 

HEATER

VENTILATION

 

INLET

 

AIR

LOUVERS

 

 

 

(For unheated crawl space)

 

 

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 3

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

EQUIPMENT IN

CONFINED SPACE

ALL AIR FROM

CHIMNEY

(All Air Through Ventilated Attic)

OR GAS

 

VENT

 

CHIMNEY

OR GAS

OUTSIDE

VENTILATION LOUVERS

(Each end of attic)

OUTLET

AIR

FURNACE

INLET AIR

 

 

(Ends 12 in.

 

above bottom)

 

WATER

 

HEATER

NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip­ ment in the enclosure.

VENT WATER

HEATER

OUTLET AIR

FURNACE

INLET AIR

NOTE - Each air duct opening shall have a free area of at least one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­ cate directly with the outdoors, each opening shall have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.

FIGURE 4

FIGURE 5

Page 7

Image 7
Contents Table of Contents Installation Instructions EL180UHEOpening Unit Dimensions inches mmEL180UHE Gas Furnace Safety InformationShipping and Packing List Use of Furnace as Construction Heater Installed in Combination with a Cooling CoilGeneral Unconfined Space Combustion, Dilution & Ventilation AirAir from Inside Confined SpaceAir from Outside Equipment in Confined Space Upflow Applications Setting EquipmentWith transition and filter Return Air -- Upflow ApplicationsSingle Side Return Air Horizontal Applications Removing the Bottom PanelReturn Air -- Horizontal Applications Supply Air Plenum Horizontal Application Unit Installed on PlatformFilters Duct SystemUpflow Position VentingReturn Air Plenum Mounting Screws LocationSide Vent Discharge Horizontal Left PositionLeft Side Vent Discharge Right Side Vent DischargeHorizontal Right Position Venting Using a Masonry ChimneySide Vent Discharge no modifications necessary Vent Connection Upflow and Horizontal Position Common Venting Using Metal-Lined Masonry ChimneyConnector Length feet m Connector Diameter Maximum HorizontalGeneral Venting Requirements Page MIN FAN + FAN FAN + NAT Removal of the Furnace from Common Vent Gas PipingGas Supply 103.92 97.69 92.31 Gas Pipe Capacity ft3/hr m3/hrLeak Check Horizontal Applications Possible Gas Piping ConfigurationsPrecautions and Procedures ElectricalThermostat Interior MAKE-UP BOX InstallationAccessory Terminals Generator Use Voltage RequirementsEL180UHE Schematic Wiring Diagram Automatic Hot Surface Ignition System Diagnostic Codes / Status of FurnaceIntegrated Control Integrated ControlUnit Start-Up For Your Safety Read Before LightingHigh Altitude Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionOther Unit Adjustments Service Blower Parts Repair Parts ListML180UHE Burner Assembly & Removal Control Panel PartsStart-Up & Performance Check List Unit Operation Cooling ModeTemperature Drop Temperature Rise

EL180UHE specifications

Lennox International Inc. has long been a leader in providing innovative heating and cooling solutions, and the EL180UHE represents a notable advancement in their line of high-efficiency gas furnaces. Designed to meet the demands of residential heating, this unit combines advanced technology with user-friendly operation and significant energy savings.

One of the standout features of the EL180UHE is its efficiency rating, with an Annual Fuel Utilization Efficiency (AFUE) of up to 80%. This high efficiency not only helps homeowners save on energy bills but also reduces their carbon footprint. The furnace is equipped with a reliable, multi-speed blower motor, which enhances comfort levels by maintaining consistent air circulation throughout the home.

The EL180UHE employs advanced combustion technologies, such as Lennox's low-NOx burner, which minimizes nitrogen oxide emissions, contributing to a cleaner environment. The unit is also designed with a sealed combustion system that draws air directly from the outdoors rather than from inside the home, leading to improved indoor air quality and increased safety.

Another significant characteristic of the EL180UHE is its whisper-quiet operation. This is achieved through well-engineered insulation and a design that minimizes noise levels, allowing for a comfortable living environment without disruptive sounds. Many homeowners appreciate the quiet performance, especially during the night or in spaces where noise is a concern.

The installation process is straightforward, supported by Lennox's user-friendly design. The EL180UHE is compatible with various home configurations and can easily integrate with existing HVAC systems. Additionally, it has a compact footprint, making it suitable for homes with space constraints.

Further enhancing its appeal, this gas furnace features robust warranty options, reflecting Lennox's commitment to quality and customer satisfaction. Homeowners can rest assured that they are investing in a durable product that has been built to last.

In conclusion, Lennox International Inc.'s EL180UHE gas furnace exemplifies the company's dedication to innovation, efficiency, and reliability in home heating solutions. With its high AFUE rating, advanced combustion technology, quiet operation, and user-friendly design, the EL180UHE is an excellent choice for homeowners looking to enhance their comfort while minimizing energy costs.