Louisville Tin and Stove 90N75A GAS Supply and Piping, GAS Pipe Sizes Capacity *NATURAL GAS

Page 8

CONNECTING THE VENT - Continued

Typical Installation Using

Class “B” Vent Pipe

1.Adequate clearances around floor furnace.

2.Draft Diverter 6” from combustibles.

3.Adequate clearances around vent pipe.

4.Horizontal vent pipe sloping upward 1/4” per foot.

5.Pipe supported with metal straps.

6.Adequate height of vent system.

7.Listed vent cap.

If more than one gas appliance is vented through a common vent system, the vent should be increased in size to accommodate the increased load. Consult your local code or the tables in the latest edition of NFPA54/ANSI.Z223.1 for the correct size. If no local codes apply, use the following alternate method for sizing a vent connected to more than one appliance. The effective area of the vent must be not less than the area of the largest vent connection plus 50 percent of the areas of additional draft hood outlets.

The homeowner appreciates neatness in workmanship and the neat installation usually functions better than the sloppy one. Double check your work to verify that all clearances around the floor furnace and vent system are adequate and that the vent system is installed to code or pipe manufacturers specifications. See Figure 10.

FIGURE 10

GAS SUPPLY AND PIPING

The gas piping system must meet the requirements of local codes or the specifications of the servicing gas supplier. It must have adequate capacity to supply the floor furnace and any other appliance within the home with enough gas to maintain the full rated capacities without excessive pressure drop when all appliances are operating at full rate.

GAS PIPE SIZES - CAPACITY - *NATURAL GAS

Length of

INSIDE PIPE DIAMETER

 

Pipe - Feet

1/2”

 

3/4”

1”

 

 

 

1 0

132,000

 

278,000

520,000

 

2 0

92,000

 

190,000

350,000

Capacity

3 0

73,000

 

152,000

285,000

B.T.U.

4 0

63,000

 

130,000

245,000

Per Hour

5 0

56,000

 

115,000

215,000

Input

6 0

50,000

 

105,000

195,000

 

*Based on heating value of 1,000 btu per cubic foot (specific gravity of 0.6) @ 0.5 PSIG and a pressure drop of 0.3 inch water column.

GAS TUBING AND PIPE SIZES - CAPACITY - *L.P. GAS

Length of

**Copper Tubing

**Steel Pipe

 

 

Pipe/Tubing

Outside Diameter

Inside Diameter

 

 

Feet

1/2”

3/4”

1/2”

3/4”

 

 

1 0

92,000

329,000

275,000

567,000

 

 

2 0

62,000

216,000

189,000

393,000

Capacity

3 0

50,000

181,000

152,000

315,000

B.T.U.

4 0

41,000

145,000

129,000

267,000

Per Hour

5 0

37,000

131,000

114,000

237,000

Input

6 0

35,000

121,000

103,000

217,000

 

 

*Undiluted Liquefied Petroleum Gas @ 11 inches water column inlet pressure. Based on a pressure drop of 0.5 inches water column. **Copper tubing must comply with limitations of NATIONAL FUEL

GAS CODE reference 2.6.3 metallic tubing.

***Steel pipe should be of at least standard weight (Schedule 40).

Support the piping or tubing at regular intervals with metal pipe strapping. See chart below.

Nominal Steel

Spacing of

Pipe Size

Supports

 

 

1/2”

6’

3/4” or 1”

8’

 

 

Nominal size of

Spacing of

tubing O.D.

Supports

 

 

1/2”

4’

5/8” or 3/4”

6’

 

 

Where local conditions include earthquake, tornado, unstable ground or flood hazards, give special consideration to increased strength and flexibility of piping supports and connections. Consult local authorities for recommendations.

All unused openings in the piping system must be securely closed gas-tight.

Page 8

Image 8
Contents Millivolt Control System Natural GAS What to do if YOU Smell GASContents Floor Furnace SpecificationsSafety Rules IntroductionHelpful Installation Information Installation RequirementsFloor Furnace Location Fresh AIR for Combustion and VentingSetting the Floor Furnace Cutting the Floor OpeningFloor FurnaceInstalling the Draft Hood Connecting the VentSafe Unsafe Recommended GAS Tubing and Pipe Sizes Capacity *L.P. GAS GAS Supply and PipingGAS Pipe Sizes Capacity *NATURAL GAS Connecting the GAS Piping GAS Valve TEEGround Joint Union Manual Valve Supply Sediment Trap Additional L.P. GAS RequirementsThermostat Installation Wire AS Indicated See FigureFor Your Safety Read Before Lighting What to do if YOU Smell GASAdjusting the Pilot Flame Adjusting the BurnerVent System Burner OrificeOption Limit SwitchOptional Operation Service Record Maintenance InstructionsTo Clean Burner Trouble Shooting Chart Main Burner Symptom Possible Causes Corrective ActionModels Included 40 34 Burner Assembly forBurner Assembly for 90N30A 90N50A 90N65A 90N75A This is not AN Advertisement If YOU Smell GAS, DON’T Light ITIf YOU CAN’T Light IT DON’T Fight IT Limited Warranty Table a

90N50A, 90N30A, 90N65A, 90N75A specifications

Louisville Tin and Stove has established a reputation for quality and innovation in the heating and cooling industry with its line of products, particularly the 90N65A, 90N50A, 90N75A, and 90N30A models. Each of these units boasts distinctive features, technologies, and characteristics that cater to a variety of residential and commercial needs.

The 90N65A model stands out for its impressive energy efficiency, designed to operate at an efficiency rating of up to 95%. This model employs advanced condensing technology, which allows it to extract more heat from the combustion process, significantly reducing energy costs for users. Moreover, its variable speed blower promotes quiet operation while optimizing airflow, ensuring that spaces are comfortably heated or cooled without excessive noise.

In contrast, the 90N50A model is engineered for versatility and compactness. This makes it an ideal choice for smaller homes or tight spaces where every inch counts. Despite its size, the 90N50A does not compromise on performance, delivering robust heating capabilities with an efficiency rating also reaching up to 94%. Its straightforward installation process, along with its user-friendly interface, allows for quick setup and ease of operation, appealing to both homeowners and technicians.

The 90N75A model is tailored for larger environments, with a higher BTU output designed to keep extensive areas warm even during the coldest months. It features dual heat exchangers that enhance durability and thermal efficiency, ensuring a longer lifespan. Furthermore, the integrated smart technology allows homeowners to monitor and adjust settings remotely, providing ultimate convenience and control over indoor climates.

Finally, the 90N30A serves as a budget-friendly option without sacrificing quality or efficiency. It incorporates a simplified design that ensures reliability while still achieving a commendable efficiency rating. Ideal for those seeking an economical heating solution, the 90N30A supports both natural gas and propane fuel options, making it adaptable to various energy sources.

All models highlight Louisville Tin and Stove's commitment to sustainability and reducing environmental impact. By incorporating innovative technologies such as modulating burners and advanced heat exchangers, these units not only comply with modern regulatory standards but also contribute to a greener planet. In summary, the Louisville Tin and Stove series—90N65A, 90N50A, 90N75A, and 90N30A—offers a robust selection of heating solutions that cater to diverse needs, emphasizing efficiency, performance, and adaptability.