Bryant NAHA003WK.01 installation instructions Single Stage Thermostat Operation

Page 2

Installation Procedures

1.Remove line power from both appliances before starting installation of the twinning kit.

2.Locate the Z1 and Z2 or C to C and H to H connections along one edge of each control (see Figure 1 and Figure 2). The designations are printed on top of the circuit board, and a black bar shows the correct orientation of the metal body which will be pushed in to make connection.

3.Remove furnace casing hole plugs and route the twinning leads through bushings provided as required, and lengthen if necessary by splicing. Be sure to observe the polarity required so as to match Z1 to Z1 and Z2 to Z2 or C to C and H to H (see Figure 3).

4.Push the terminal into the slot on the circuit board edge. Be sure to align the body with the black bar to line up the solder finger below the circuit board (see Figure 1). The terminal will “bite into” the solder and make the necessary connection. Repeat for each end of both wires.

5.Locate and mount the isolation relay in the circulating blower compartment on the same panel as the electronic fan control in furnace #1 (see Figure 1 and Figure 2).

6.Refer to single stage or two stage thermostat wiring as noted below.

“G” and “Y” connections only. Interconnect the wiring from the “C” connections at the terminal blocks on each fan control. Note: The “Y” connection is not required if air conditioning is not available.

2.Connect wire from “W1” of the thermostat to the “W” connection of the electronic fan control of furnace #1.

3.Connect wire from “W2” of the thermostat to one side of the 24Vac coil of the isolation relay (terminal #3). (Wire terminals for connection to the isolation relay are provided in the kit)

4.Connect wire from “R” connection at the thermostat to the “R” connection of the electronic fan control of furnace #1.

5.Connect wire from the “C” connection of the electronic fan control of furnace #1 to the other side of the 24Vac coil of the isolation relay (terminal #1).

6.Connect one wire to each of the normally open terminals of the isolation relay (terminal #2 and #4) and connect to the “R” and “W” connections at the electronic fan control of furnace #2.

7.Set the heat delay off timings on each control to the same setting.

8.Set thermostat anticipator setting at 0.75 for the 1st stage and 0.15 for the 2nd stage.

Single Stage Thermostat Operation

9.

Recheck wiring connections, splices, and insulation.

Reference Figure 6 and Figure 7

 

Re--apply line power to both appliances.

1.

Interconnect the thermostat wiring in parallel from the

Twinning Kit Operation

 

 

thermostat to the terminal blocks on each fan control, for the

1.

Turn the heat/cool switching at the thermostat to “OFF”, or

 

 

“G” and “Y” connections only. Interconnect the wiring from

 

 

the “C” connections at the terminal blocks on each fan

 

set so neither a call for heating nor cooling is being made.

 

 

control. Note: The “Y” connection is not required if air

2.

Turn the fan switch to “ON” from “AUTO”, or jumper from “R”

 

 

conditioning is not available.

 

 

 

to “G” at “furnace 1”. Within several seconds, the circulation

 

 

 

 

2.

Connect wire from “W” connection at the thermostat to the

 

blowers of each furnace will start at the same speed

 

 

“W” connection of the electronic fan control of furnace #1.

 

connected to their respective “heat” speed taps.

3.

Connect wire from “R” connection at the thermostat to the

3.

Turn the fan switch to “OFF” from “AUTO” or remove the

 

 

“R” connection of the electronic fan control of furnace #1.

 

jumper from “R” to “G”. Both circulation blowers will stop

4.

Connect wire from the “W” connection of the electronic fan

 

after several seconds.

 

 

 

 

 

control of furnace #1 to one side of the 24Vac coil of the

4.

Disconnect one wire from the high limit connection on

 

 

isolation relay (terminal #3). (Wire terminals for connection

 

“furnace 1”. Within several seconds, the circulation blowers

 

 

to the isolation relay are provided in the kit)

 

of each furnace will start at the same speed connected to

5.

Connect wire from the “C” connection of the electronic fan

 

their respective “heat” speed taps.

 

 

 

 

 

control of furnace #1 to the other side of the 24Vac coil of the

5.

Re--connect the wire removed from the high limit

 

 

isolation relay (terminal #1).

 

connection on “furnace 1”. After the completion of the

6.

Connect one wire to each of the normally open terminals of

 

heating “blower off” delay, both blowers will stop.

 

 

 

 

 

the isolation relay (terminals #2 and #4) and connect to the

6.

Repeat steps (4) and (5) with the limit connection in

 

 

“R” and “W” connections at the electronic fan control of

 

²

 

 

 

furnace #2.

 

“furnace 2” versus :furnace 1 . The same operation should

 

 

 

result.

7.

Set the heat delay off timings on each control to the same

7.

Operate the system through a normal call for heat, burner

 

 

setting.

 

on operation, and burner off operation. Each furnace

8.

Set thermostat anticipator setting at 0.90.

 

should fire and cycle both blowers, including blower on and

 

off delays, as in a normal single system.

 

 

 

 

9.

Recheck wiring connections, splices, and insulation.

8.

Operate the system through a normal call for cooling. The

 

 

Re--apply line power to both appliances.

 

 

 

compressor operation should function normally, with each

Two Stage Thermostat Operation

 

 

furnace circulation blower operating at the speeds

Reference Figure 6 and Figure 7

 

connected to their respective “cool” speed taps after

1.

Interconnect the thermostat wiring in parallel from the

 

cooling “blower on” delay. When the call for cooling ends,

 

the circulation blowers will stop upon the completion of the

 

 

thermostat to the terminal blocks on each fan control, for the

 

“cooling off” delay.

 

 

 

 

 

 

 

 

 

 

441 06 1003 02 (10/2001)

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 2
Contents Twinning Kit NAHA003WK.01 Single Stage Thermostat Operation Twin Twining Leads 25--23--7825--23--79 Obtain necessary lengthSplice if Required,to Obtain necessary length Proper Connection of Twinning Leads for ST 25--23--80 Thermostat Wiring For Single Stage HeatingThermostat Wiring For Two Stage Heating Thermostat Wiring For Single Stage Heating Two Stage Cooling 25--23--81 Cooling Thermostat Wiring ForThermostat Wiring For Two Stage Heating Cooling Thermostat Wiring For Single Stage Heating Cooling

NAHA003WK.01 specifications

The Bryant NAHA003WK.01 is a cutting-edge air conditioning unit designed for both residential and light commercial applications. As a reliable brand in the HVAC industry, Bryant offers this model with a focus on energy efficiency, comfort, and advanced technology.

One of the standout features of the Bryant NAHA003WK.01 is its impressive SEER (Seasonal Energy Efficiency Ratio) rating, which ensures lower energy consumption and reduced utility bills. This model is engineered to operate efficiently, making it environmentally friendly while providing optimal cooling performance. The high efficiency is particularly beneficial for users looking to maintain a cool indoor environment without incurring high energy costs.

A key technology integrated into the Bryant NAHA003WK.01 is its variable-speed compressor. This advancement allows the unit to adjust its cooling output based on the current temperature demands, which means it can run at lower speeds for longer periods. This not only enhances energy savings, but also aids in maintaining consistent indoor temperatures, leading to improved overall comfort.

Moreover, the Bryant NAHA003WK.01 is equipped with a robust air filtration system designed to improve indoor air quality. With a filter that captures dust, allergens, and other particulates, this unit helps create a healthier living space. The ease of access to the filter also makes maintenance straightforward, allowing users to replace or clean the filter without hassle.

Durability is another characteristic of the Bryant NAHA003WK.01. Constructed with high-quality materials, the unit is built to withstand various weather conditions, ensuring longevity and reliable performance over time. Its compact design also allows for flexible installation options, making it suitable for different spaces without compromising on aesthetics.

In terms of controls, the Bryant NAHA003WK.01 features advanced smart technology compatibility. Users can easily integrate the unit with a smart thermostat or home automation systems, enabling convenient remote management. This allows individuals to adjust settings and optimize performance from their smartphones or tablets.

In summary, the Bryant NAHA003WK.01 air conditioning unit stands out for its energy efficiency, variable-speed compressor technology, superior air filtration system, durable construction, and smart controls. This makes it an ideal choice for those seeking a reliable and effective cooling solution that caters to modern comfort needs while being conscious of energy consumption.