NOTES:

1.Refer to information label on blower compartment door for procedure for use of LED status codes and problem solving suggestions.

2.LED indicator is viewed through window in blower compartment door.

3.If 115-vac power is de-energized or interrupted during a call for heat, the indoor blower will run for 90 sec before a gas heating cycle begins – Code 12.

4.After replacing any component, verify correct operating sequence.

START

Turn thermostat OFF.

On furnace control, note current

settings for setup switches 1 (SW-1) and 2 (SW-2) then set SW-1 to OFF and SW-2 to ON.

Cycle 115-v power

 

off for 3 sec, then on.

 

Continuous LED?

No

 

Yes

 

Set thermostat to call for heat.

 

Set FAN to AUTO mode.

 

Draft inducer motor starts.

No

 

Yes

No

Is Code 22 displayed?

 

Yes

 

Flame present when not normal.

 

Replace gas valve.

 

15-sec inducer pre-purge.

 

Yes

 

Ignitor warms up and glows

No

 

orange/yellow; 17-sec warm-up.

 

Yes

 

Main burners ignite.

No

 

Yes

 

Main burners stay on.

No

 

Yes

 

Indoor blower motor starts on

No

 

heating speed after 45-sec

 

 

 

 

warm-up period.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

No

 

 

 

 

Furnace runs until call for

 

 

 

 

heat ends.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Turn thermostat to OFF; gas valve

No

 

shuts off burners; 5-sec inducer

 

 

 

post purge.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

No

 

Indoor blower motor stops after

 

90, 135, 180, or 225 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

Heating sequence of operation complete. Remove blower door, move setup switch 1 (SW-1) to ON

TROUBLESHOOTING

GUIDE

If LED is flashing rapidly, check line voltage polarity.

If Code 24 is displayed, check for blown fuse.

If LED is OFF, check line voltage and 24-v transformer.

If Code 45 is displayed, replace control.

Is indoor blower on ?

No

24v should be present across Com and W at furnace control. If not, check for:

1.Open thermostat.

2.Open 24-v fuse (FU1) – Code 24.

3.Failed transformer.

If Code 23 is displayed, the pressure switch(es) is stuck closed. Replace switch and/or check pressure tube for blockage.

System malfunction – Code 21.

115v should be present at the inducer motor. If so, replace inducer motor. If not, check 115-v wiring.

If Code 32 is displayed check for:

1.Open gas inlet pressure switch (when used).

2.Open pressure switch (LPS) and/or tube – Code 32.

3.Open draft safeguard switch (DSS) – Code 32.

4.Open auxiliary switch (ALS)(downflow only) – Code 32.

5.Check all low-voltage wiring connections.

115v should be present at the ignitor. If so, replace the ignitor; if not, check 115-vac wiring to ignitor.

LPS, DSS, or ALS open while HPS if closed (high-gas-heat only) –

Code 43.

Control will attempt to light burners 4 times (approximately 1 minute between attempts – Code 34). Voltage is present at the gas valve for 7 sec during each ignition trial. System will lockout after 4 attempts.

Is the gas valve control knob or switch in the OPEN or ON position? 24v should be present across the gas valve terminals C and M/P (and C and HI for high-stage gas test) during the 7 sec ignition trial. If not, check all low-voltage wiring connections to valve.

If 24v are present, and main gas does not flow:

1.Supply pressure between 4.5- and 13.6-in. wc. If not, adjust supply pressure.

2.If supply pressure is between 4.5- and 13.6-in. wc, replace gas valve.

Check ignitor position.

Check burner carryover gap.

Check gas supply pressure (4.5-in. wc minimum).

Check manifold pressure (1.3- to 1.7-in. wc for low-stage gas; 3.2- to 3.8-in. wc for high-stage gas).

Check for proper orifice size.

Is Code 31 (high-gas-heat only), 32, 33, or 34 displayed? Check code information label to diagnose.

Check polarity of 115-v power at J-box and control. Twinned furnace polarities must match – rapid flashing LED.

Check ground continutity from J-box to control.

Check flame sensor microamps (4.0 nominal; 0.5 minimum for control to recognize flame).

115v should be present at the blower motor. If so, check capacitor. If capacitor is OK, replace blower motor. If 115v are not present at the blower motor, check all 115-v wiring to motor.

If not, check for:

1.Satisfied thermostat.

2.Open inlet gas pressure switch (when used).

3.Open pressure switch (LPS) – Code 32.

4.Open draft safeguard switch (DSS) – Code 32.

5.Open auxilliary limit (ALS)(downflow only) – Code 32.

6.Open 24-v fuse (FU1) – Code 24.

7.Open limit switch (LS) – Code 13 or 33.

8.Open flame rollout switch (FRS) – Code 13 or 33.

9.Check 115-v line voltage – LED off.

Check for sources of electrical noise interference (electronic air cleaners, nearby TV, or radio antennas).

If inducer and burners continue to operate, check for 24v at the gas valve. If 24v are present, verify that the thermostat is open across R and W. If no voltage is present, turn the gas valve control knob or switch to the OFF position. Replace gas valve.

!WARNING

ELECTRICAL SHOCK HAZARD

ONLY QUALIFIED AND TRAINED

SERVICE PERSONNEL SHOULD

PERFORM THIS PROCEDURE

 

 

24v should be present across R

 

Yes

and Com. If not, check for:

 

 

1. Open flame rollout switch

 

 

 

 

(FRS) – Code 33.

 

 

2.Open limit switch (LS) –

Code 33.

3.Check all low-voltage wiring connections.

 

 

No

No

 

 

Replace control only if all checks

 

are OK.

 

 

 

No

 

Replace control only if Code 45 is

 

 

displayed, or if all checks are OK.

 

 

 

 

 

 

No

Replace control only if Code 45 is

 

 

displayed, or if all checks are OK.

 

 

No

Replace control if Code 45 is dis-

played, or if all checks are OK.

 

Clean flame sensor if microamps

 

are below nominal.

No

 

 

Replace control only if Code 45 is

 

displayed, or if all checks are OK.

 

 

No

Replace control only if Code 45 is

 

displayed, or if all checks are OK.

 

 

No

Replace control only if Code 45 is

 

displayed, or if all checks are OK.

 

 

position and repeat process to check

high-stage gas heat operation. (When finished return SW-1 and SW-2 to original desired settings.)

24v should be present across R and Com. If not, check for:

No

Replace control only if Code 45 is

 

 

displayed, or if all checks are OK.

1.

Open limit switch (LS) – Code 13 or 33.

 

 

 

 

 

2.

Open flame rollout switch (FRS) – Code 13 or 33.

 

 

 

24v should not be present across R and G. If so, set thermostat

 

 

 

FAN to AUTO mode.

 

 

 

A97544

—10—

Image 10
Contents Table of Contents Safety ConsiderationsCleaning AND/OR Replacing AIR Filter Electrostatic Discharge ESD Precautions ProcedureCare and Maintenance IntroductionDownflow Filter Arrangement II. Blower Motor and WheelIII. Cleaning Heat Exchanger Speed SelectorPosition of Ignitor to Burner IV. Electrical Controls and Wiring Wiring Diagrams Troubleshooting324459-101 REV. D Service Start Service Training
Related manuals
Manual 4 pages 14.45 Kb

330JAV, 331JAV specifications

The Bryant 331JAV is a remarkable air conditioning unit that epitomizes efficiency, reliability, and advanced technology. Designed for residential use, the 331JAV series stands out with its Energy Star certification, ensuring that homeowners can enjoy optimal cooling while minimizing their energy consumption. This unit is particularly appealing to environmentally conscious individuals looking to reduce their carbon footprint without sacrificing comfort.

One of the key features of the Bryant 331JAV is its two-stage cooling system. This technology allows the unit to operate at varying speeds, adjusting its performance based on the home's cooling needs. By running at a lower speed for extended periods, the unit can maintain a consistent temperature with less energy consumption. This not only enhances comfort but also contributes to lower electricity bills.

In terms of design, the Bryant 331JAV boasts a compact and modern look, making it suitable for various home aesthetics. Its durable cabinet is designed to withstand harsh weather conditions, ensuring longevity and reliable performance. Additionally, the unit is equipped with a quiet operation system, which helps to maintain a peaceful indoor environment while cooling.

The Bryant 331JAV also incorporates advanced refrigerant technologies. It utilizes R-410A refrigerant, which is known for its efficiency and safety, as it does not harm the ozone layer. This focus on eco-friendly materials further underscores Bryant's commitment to sustainability.

Connectivity is another notable characteristic of the Bryant 331JAV. The unit is compatible with smart thermostats, allowing homeowners to control their cooling systems remotely through smartphones or other devices. This feature not only adds convenience but also enhances energy management, as users can adjust settings according to their schedules.

Furthermore, the unit has multiple capacity options, ensuring that it can be tailored to meet the specific needs of different homes. It is also designed for easy installation and maintenance, with accessible components that simplify service tasks.

Overall, the Bryant 331JAV is an exemplary choice for any homeowner looking to invest in a cutting-edge air conditioning system. With its combination of energy efficiency, advanced technology, and user-friendly features, it represents a significant leap forward in residential climate control solutions.