Bryant 359AAV instruction manual Procedure 3 Cleaning Burners, Electrical Shock Hazard

Page 4

359AAV

Center Clip side-to-side

9”

(228.6 mm)

A07691

 

Fig. 2 - Bottom Filter Arrangement

Filter Rack

End Cap

A07690

Fig. 3 - Filter Installed for Side Inlet

f. Remove blower wheel from housing.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in furnace component failure.

The blower wheel should not be dropped or bent as balance will be affected.

g.Clean wheel per instructions on degreaser cleaner. Do not get degreaser cleaner in motor.

9.Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation. Be sure to reattach ground wire. Tighten setscrew to 140 to 160 in.-lb torque.

10.Reinstall blower assembly in furnace.

11.Reinstall control box, transformer, and door switch assembly on blower shelf.

12.Reinstall condensate trap and tubing if previously removed.

a.Reinstall condensate trap in hole in blower shelf.

b.Connect condensate trap drain tubes. See Fig. 6, 7, or 8.

NOTE: Ensure tubes are not kinked or pinched, as this will affect operation.

c.Connect field drain to condensate trap.

13.Reconnect wires.

Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected. (See Fig.20.)

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit component damage.

Heating speed selection MUST be adjusted to provide proper temperature rise as specified on the rating plate.

Table 1 – Speed Selector

COLOR

SPEED

FACTORY

ATTACHED TO

Black

High

Cool

Orange

Medium High

Heat

Blue

Medium Low

M1

Red

Low

M2

White

Common

Com

14.Turn on electrical supply. Manually close blower access door switch. Use a piece of tape to hold switch closed. Check for proper rotation by jumpering R to G.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes.

15.If furnace is operating properly, remove tape to release blower access door switch, remove jumper across R to G, and replace blower access door.

Procedure 3 — Cleaning Burners

The following items should be performed by a qualified service technician. If burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:

1.Turn off gas and electrical supplies to furnace.

2.Remove main furnace door.

3.Using backup wrench, disconnect gas supply pipe from furnace gas control valve.

!CAUTION

ELECTRICAL SHOCK, UNIT DAMAGE HAZARD

Failure to follow this caution may result in personal injury or furnace component damage.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

4

Image 4
Contents Service Guide Unit Damage Hazard Fire / Explosion HazardElectrical Shock and Unit Damage Hazard Procedure 1 Cleaning and/or Replacing Air Filter Procedure 2 Blower Motor and Wheel MaintenanceCUT Hazard FIRE, Carbon Monoxide and Poisoning HazardElectrical Shock Hazard Procedure 3 Cleaning BurnersElectrical SHOCK, Unit Damage Hazard FIRE, EXPLOSION, Unit Damage Hazard Fire or Explosion HazardUpflow Installations Top Vent OnlyUpflow Installations Vent Through Left Side Side ViewAll Models Vent Through Right Side Upflow PVCExhaust Downflow Right Side Vent and Trap Exhaust Horizontal Left Side Vent InletHorizontal Right Through Top Inlet Procedure 5 Flushing Collector Box Drainage System Procedure 4 Cleaning Heat ExchangersUnit MAY not Operate Procedure 6 Servicing Hot Surface Igniter Gasket on Collector BoxField Wiring Burn HazardProcedure 7 Electrical Controls and Wiring Procedure 8 Checking Heat Tape Operation If ApplicableProcedure 9 Winterizing Unit and Property Damage HazardWinterizing the Furnace Wiring Diagram Service Label Catalog No. SM359AAV---01
Related manuals
Manual 8 pages 30.83 Kb

359AAV specifications

The Bryant 359AAV is a cutting-edge heating and cooling solution designed to deliver exceptional comfort, energy efficiency, and reliability for residential applications. With its innovative advancements and superior engineering, the Bryant 359AAV stands out in the competitive HVAC market.

One of the main features of the Bryant 359AAV is its two-stage heating and cooling system. This allows the unit to operate at two different levels of capacity, ensuring more consistent temperatures throughout your home. By running at a lower capacity most of the time, it can achieve greater energy efficiency compared to single-stage systems, and only ramps up to full power when there's a significant demand for heating or cooling. This results in improved comfort and lower energy bills.

Equipped with a variable-speed compressor, the Bryant 359AAV can adjust its speed to match the specific heating or cooling needs of your home. This feature not only enhances the system's efficiency but also reduces noise levels, making it one of the quietest units in its class. The advanced sound-dampening technology minimizes operational sounds, allowing homeowners to enjoy a peaceful indoor environment.

The Bryant 359AAV also features a high SEER (Seasonal Energy Efficiency Ratio) rating. This rating is crucial for determining the unit's efficiency during the cooling season. A higher SEER rating means that the unit consumes less energy for the same amount of cooling output, which helps in lowering utilities. This is particularly beneficial for homeowners looking to reduce their overall energy consumption and carbon footprint.

Another significant characteristic of the Bryant 359AAV is its advanced indoor air quality options. The system can be equipped with filters and purifiers to ensure that the air circulating in your home is clean and healthy. Enhanced filtration helps in capturing allergens, pollutants, and other harmful particles, improving the overall air quality.

Overall, the Bryant 359AAV is characterized by its durability and modern design. Built with high-quality materials, it is designed to withstand harsh weather conditions and provide reliable service for years. The unit’s compact footprint allows for versatile installation options, making it suitable for various home layouts. With optimal performance, impressive energy savings, and a focus on indoor air quality, the Bryant 359AAV is an excellent choice for homeowners seeking an efficient and effective HVAC solution.