SERVICE

If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.

LED CODE

STATUS

CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.

CONTINUOUS ON - Control has 24VAC power.

RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.

11NO PREVIOUS CODE - Stored status codes are erased when power

(115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

12BLOWER ON AFTER POWER UP (115VAC or 24 VAC) - Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed).

13LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Control will auto reset after three hours. Reset switch or replace fuse link. Refer to #33.

14IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.

21GAS HEATING LOCKOUT - Control will NOT auto reset.

Check for: - Mis-wired gas valve

-Defective control (Valve relay)

22ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared.

 

Check for:

- Leaky gas valve

 

- Stuck-open gas valve

23

PRESSURE SWITCH DID NOT OPEN - Check for:

 

- Obstructed pressure tubing.

- Pressure switch stuck closed.

24

SECONDARY VOLTAGE FUSE IS OPEN

 

Check for:

- Short circuit in secondary voltage (24VAC) wiring.

31

PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED

 

VENT SWITCH (when used) DID NOT CLOSE OR REOPENED

 

(DOWNFLOW ONLY*) If open longer than five minutes, inducer shuts off for 15

 

minutes before retry. Check for:

 

- Proper vent sizing

 

- Low inducer voltage (115VAC)

 

- Defective inducer motor

 

*- Defective Blower motor or capacitor

- Restricted vent

 

- Defective pressure switch

 

- Excessive wind

-Inadequate combustion air supply

-Disconnected or obstructed pressure tubing

If it opens after trial for ignition period, blower will come on for 90 second recycle delay.

33LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three minutes, code changes to #13. Flame roll-out switch requires manual reset.

Check for:

- Defective blower motor or capacitor.

-Dirty filter or restricted duct system.

-Loose blower wheel.

-Defective switch or connections.

-Inadequate combustion air supply (Flame Roll-out Switch or fuse link open).

-Open Flame Roll-out Switch, or fuse link. Manual reset or replace.

34IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost after trial for ignition period, blower will come on for 90 second recycle delay. Check for:

-Oxide buildup on flame sensor (clean with fine steel wool).

-Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).

-Gas valve defective or gas valve turned off.

- Defective Hot Surface Ignitor

- Manual valve shut-off.

- Low inlet gas pressure.

- Control ground continuity

-Green wire MUST be connected to furnace sheet metal.

-Inadequate flame carryover or rough ignition.

-Flame sensor must be ungrounded.

COMPONENT TEST

To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on.

9

6

3

8

5

2

7

4

1

LED

TEST

HUM Com W Y R G

24V

320615-102 REV. K (LIT)

A99233

Fig. 8ÐService Label

8

Image 8
Contents Introduction Table of ContentsSafety Considerations Care and Maintenance Electrostatic Discharge ESD Precautions ProcedureÐCleaning and/or Replacing Air Filter Ðspeed Selector ÐBlower Motor and WheelÐCleaning Heat Exchanger ÐPosition of Ignitor to BurnerÐElectrical Controls and Wiring TWO Terminal Wire Block FurnacePCB ÐFurnace Control Service Wiring Diagrams TroubleshootingTroubleshooting Guide A99123b 58yav3sm

58YAV specifications

The Carrier 58YAV is a high-efficiency gas furnace that has gained recognition in the HVAC industry for its performance and advanced technology. Specifically designed to meet the needs of modern homes, the 58YAV integrates various features that enhance comfort, energy efficiency, and reliability.

One of the standout characteristics of the 58YAV is its exceptional AFUE (Annual Fuel Utilization Efficiency) rating, which often reaches up to 96%. This means that the furnace converts a significant portion of fuel into heat, translating into lower energy bills and a reduced carbon footprint. The unit operates using a two-stage heating system which allows for greater temperature consistency and improved energy savings. The ability to operate at a low stage during mild conditions prevents energy wastage while providing adequate heating comfort.

The 58YAV employs advanced modulating technology that provides precise temperature control. This technology enables the furnace to adjust its heating output based on the specific demands of the home, ensuring optimal comfort without unnecessary energy consumption. Additionally, the integrated variable-speed blower motor enhances air circulation and reduces noise during operation, creating a quieter home environment.

Moreover, equipped with a smart thermostat capability, the Carrier 58YAV can be paired with Carrier’s Comfort™ series controls for enhanced programmability and remote access. This feature allows homeowners to conveniently adjust their home’s heating settings from their smartphones or other smart devices, maximizing convenience and control over their indoor environment.

The furnace also features a durable and robust cabinet design that ensures long-lasting performance. With enhanced insulation, the 58YAV minimizes operational noise and provides greater energy efficiency. Safety features, including a pressure switch and flame sensor, are integrated into the system to ensure safe and reliable operation.

In terms of installation, the Carrier 58YAV is designed to offer versatility with multiple venting options, allowing it to fit seamlessly into various home configurations. Its compact design makes it suitable for various spaces, from attics to basements.

Overall, the Carrier 58YAV is a pinnacle of modern heating technology, providing homeowners with efficient, reliable, and smart heating solutions that align with today’s energy standards. Its blend of efficiency, comfort, and innovative features establishes it as a top choice in the gas furnace market.