Lennox Hearth LBC-3824-H, LBR-4324-H, LBC-4324-H Roof Pitch Model Flat to 6/12, 12 to 12/12

Page 10

10

Note: Assemble one component of chimney at a time (inner section first; then outer section last) before preceding with the next complete section.

Continue to assemble the chimney up through framed opening. Assemble just enough to pen- etrate the roof flashing openings (Figure 28 ). Always maintain 2" minimum air space to com- bustible materials and always check each chim- ney joint (inner and outer) to ensure proper engagement. Check vertical alignment of chim- ney so that it projects from the roof in true vertical position.

1" Min. Air Space

To Combustibles

Figure 28

Security's chimney sections do not need to be screwed together. Additional reinforcement is not necessary except in certain offset condi- tions (refer to page 12, Figure 39 ).

Step 5. The height of vertical chimney pipe supported only by the fireplace must not ex- ceed 30'. Chimney heights above 30' must be supported by a Model FTF10-S4 stabilizer in- stalled at 30' intervals.

Note: The Model FTF10-S4 adds 3" net effective height to the total chimney system.

Install the Model FTF10-S4 stabilizer by fitting inner section down into respective section of proceeding flue pipe and locking outer stabi- lizer section into place over the outer chimney pipe. Position for proper clearance through framed opening and nail straps securely (under tension in “shear”) into place on framing. Use 8d nails. Attach successive lengths of chimney pipe directly to stabilizer using same tech- niques as described in Step 4 (Figure 29 ).

FTF8-S4 Stabilizer

Figure 29

Note: Do not apply excessive pressure to any subsequent chimney sections following the stabilizer when installing. Ensure each subse- quent chimney section is securely attached by testing as noted in Step 4.

Step 6. Select the proper Security Chimneys roof flashing based on pitch of roof. Use chart below for selection:

Roof Pitch

Model

 

 

Flat to 6/12

F10F6

 

 

6/12 to 12/12

F10F12

 

 

Next, slide roof flashing over extended chimney section that previously has been installed above the roof opening in Step 4. FTF10 flashings require flashing spacers. Slide flashing all the way down until the flashing base rests flat on the roof (Figure 30 ). Again, check the vertical position of the chimney and the 2" minimum air space to combustibles.

FTF10 Chimney

Do Not Seal

Flashing Spacers

FTF10 Flashing

Figure 30

Note:Donotcaulkorsealtheventilatingopenings.

Step 7. Secure flashing by nailing along the perimeter into roof using 8d nails. If shingled roof, slide upper end and sides of roof flashing under shingles (trim if necessary), seal the top and both sides of the flashing to the roof with roof caulking. Cover nail heads with roof caulk- ing (Figure 31 ).

Figure 31

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Step 8. The standard Security FTF10 roof flash- ing assemblies include a storm collar. Slide the storm collar over outer chimney, rest on flash- ing spacers and align with top surface of flash- ing. Insert tab in slot, pull tight and bend tab back over slot. Seal storm collar to outer chim- ney with roof caulking or mastic around entire circumference of pipe. Also add extra roof caulking to the tab/slot area to seal completely against water penetration (Figure 32 ). Check all joints very carefully to ensure no water intrusion can take place.

Locking Band

Waterproof

Caulk

Figure 32

Step 9. Security Chimneys locking bands, Model FLB, may be required if the chimney extends too high above the roof flashing. As a general rule, if the chimney extends more than 6' above the roof flashing, the use of locking bands is advisable to strengthen the chimney assembly. Align the locking band at the chim- ney joint. Locking bands wrap around pipe joints equally covering the joints of both pipe sections. Use the nut provided and TIGHTEN snugly. Do not overtighten as this might dam- age the chimney section (refer to Figure 29 ).

Note: If chimney extends more than 8' above roof surface, guy wires are also recommended. Use three (3) guy wires, attach to locking band assembly, extend and secure to roof in a triangular pattern (Figure 33 ). Guy wires are not supplied by the manufacturer.

Roof Ridge

120°

Figure 33

Image 10
Contents Retain These Instructions For Future Reference WH Report No -915173ATable of Contents Introduction Typical InstallationPrecautions Clearances and Height RequirementsChase Enclosure Assembly OutlineChimney Height Location of FireplacePRE-INSTALLATION Notes Installing the FireplaceAssembly Steps ClearancesLeft Side Right Side Fireplace SpecificationsFront LBC Shown Top ViewFraming Specifications FTF10For Canadian Installations, Proceed with Steps 6 through Installing the Chimney SystemFor Canada Only 8d nails when completely installedOr Ceiling Chimney 30 Offset Through FloorRoof Pitch Model Flat to 6/12 12 to 12/12Multiple Terminations TEN Foot Rule SummaryFTF10 Chimney Component Calculations FTF10-CT1 Termination Special Offset InstructionsOffset Calculations FTF10-CT2 TerminationChimney Only FTF10 Vertical Elevation ChartNumber Of FTF10 InchesInstalling Offsets FTF10 Offset Elevation ChartFirst, review the Offset Elevation Chart and for reference Optional Equipment Considerations Cold Climate Insulation Fireplace FinishesTL = minimum thickness of listed material Hearth Extension DimensionsMethods of Determining Hearth Extension and Wall Shield Opening WidthThere are a wide variety of finished looks for Finish to Your TasteRM = rM x TS = 0.05 x 3/4 = Value = 1/k = r x thickness of material usedInstallation Components 850,003M REV. G 01/2010 Installation ComponentsOrange, CA