Step 3. Position the appropriate firestop spacer at the ceiling and nail temporarily with
Attic Space
Note: For Canadian installations, all chimney installedoutsidethebuildingmustbeconstructed
two (2) 8d nails. Use a flat firestop spacer, Model
2" Min.
Air Space
2" Min.
Air Space
FTF10-S4
Stabilizer
10'
Max. 30° Firestop
And Attic Above
with galvalume (outer sections only) effective January 1, 1992. The appropriate model desig- nations are located in the back of this manual.
The FTF10 chimney system is a two piece chim- ney that snap locks together from the fireplace up. Always start with the inner flue section. With the lanced end up, snap lock the joint into the matching collar on top of the fireplace. At all subsequent joints, the upper flue section fits into the lower or preceding flue section. Each section
spacer must be secured in place by at least four
(4) 8d nails when completely installed.
Note: If there is a room above the ceiling level, the firestop spacer must be installed on the bottom side of the ceiling. If an attic is above the ceiling level, the firestop spacer must be in- stalled on the top side of the ceiling joists (Figures 21 and 22 ).
Room Above
Firestop Spacer
Figure 21
Attic Above
Firestop Spacer
Figure 22
CHIMNEY 30° OFFSET THROUGH FLOOR
OR CEILING
It may be necessary to assemble the chimney at 30° when passing through the floor or ceiling area. Use the
Figure 23
Room Above |
|
2" Min. | |
Firestop Spacer | |
| Air Space |
2" Min. | |
Air Space | Stabilizer |
10' | 30° Firestop |
Max. | And Room Above |
Figure 24
For Canada Only
When installing the chimney system through an open attic space, the attic shield assembly- firestop spacer must be used (Figure 25 ). This installation is required only for use in Canada.
Open Attic Space
Figure 25
Step 4. Note: All chimney sections are con- structed with a unique locking tabs and hem design, which ensures and immediate, tight assembly between sections. Plan your chimney requirements carefully before assembly, as the chimney is difficult to disassemble after instal- lation. If disassembled, the tabs might become damaged. Be certain that the tabs are properly formed to ensure they engage properly.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
snaps together by means of locking tabs (9 tabs per joint). Check each section by pulling up slightly from the top to ensure proper engage- ment before installing succeeding sections. If the flue has been installed correctly, it will not separate when tested. Also, the inner flue joint where each section is joined should be tight and flat without gaps (Figure 26 ).
Figure 26
The outer chimney section installs the opposite way; the lanced end goes down and each new section installs OVER the outside of the previ- ous section (Figure 27 ).
Locking Tabs (Lances)
Figure 27
9