Trane SS-PRC003-EN manual Jobsite Connections, TTA050/TWE050A, 2TTA075A/TWE155B

Page 51

Jobsite Connections

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer- supplied wiring must be copper only and must conform to local electrical codes.

NOTE:

1.When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.

TTA050/TWE050A

FieldWiring:

A— 3 power wires. Line voltage for

3phase, 2 wires for single phase.

B— 3 power wires. Line voltage for

3phase, 2 wires for single phase.

C— Cooling only thermostat: 3 wires,

24volts.

One-stage electric heat: add

1additional wire, 24 volts.

Two-stage electric heat: add

2additional wires, 24 volts.

D— 2 wires, 24 volts.

(2)TTA050/TWE100B FieldWiring:

A— 3 power wires. Line voltage for

3phase, 2 wires for single phase.

B— 3 power wires. Line voltage for

3phase, 2 wires for single phase.

C— Cooling only thermostat: 5 wires,

24volts.

One-stage electric heat add

1additional wire, 24 volts.

Two-stage electric heat: add

2additional wires, 24 volts.

D— 2 wires, 24 volts to outdoor section ‘’A’’

2 wires, 24 volts to outdoor section ‘’B’’

TTA075A/TWE075A;

TTA085/TWE075A;

TTA085/TWE100A;

TTA100A/TWE100A

Field Wiring:

A— 3 power wires, line voltage.

B— 3 power wires, line voltage for

3 phase; 2 wires for single phase.

C— Cooling only thermostat: 4 wires,

24volts.

One-stage electric heat: add

1additional wire, 24 volts.

Two-stage electric heat: add

2additional wires; 24 volts.

D— 4 wires, 24 volts.

TTA100B/TWE100B

Field Wiring:

A— 3 power wires, line voltage.

B— 3 power wires, line voltage for

3 phase; 2 wires for single phase.

C— Cooling only thermostat: 5 wires,

24volts.

One-stage electric heat: add

1additional wire, 24 volts.

Two-stage electric heat: add

2additional wires, 24 volts.

D — 5 wires, 24 volts.

TTA125B/TWE155B;

TTA155B/TWE155B;

TTA200B/TWE200B;

TTA155C/TWE155B;

TTA200F/TWE200E

FieldWiring

A— 3 power wires, line voltage

B— 3 power wires, line voltage

C— Cooling only thermostat: 5 wires,

24volts.

One-stage electric heat: add

1additional wire, 24 volts.

Two-stage electric heat: add

2additional wires, 24 volts.

D— 5 wires, 24 volts.

(2)TTA075A/TWE155B;

(2)TTA100A/TWE200B FieldWiring:

A— 3 power wires, line voltage.

B— 3 power wires, line voltage.

C— Cooling only thermostat: 5 wires,

24volts.

One-stage electric heat: add

1additional wire, 24 volts.

Two-stage electric heat: add

2additional wires, 24 volts.

D— 6 wires, 24 volts.

SS-PRC003-EN

51

Image 51
Contents Split System Cooling Units Filters Manufacturing ControlDesigning the Details Standardized CabinetsContents Air Handlers Offer More Flexibility Features and BenefitsCondensing Unit Options Low Ambient Cooling OperationOdyssey Lowers Installation Costs Micro Controls ReliaTel MicroElectromechanical Controls QualityAnd ReliabilityTesting We test designs at our factory not on our customersVariTrac Typical HorizontalAir Handler Application Clearance RequirementsBlower Rotation Low Ambient CoolingAir Delivery Selection Selection ProcedureCooling Capacity Heating CapacityModel Number Description Split System Condensing Unit Model NomenclatureAir Handler Model Nomenclature Table GD-1 General Data General DataTable GD-2- General Data Table GD-4 General Data Table GD-3 General DataDataSystem PerformanceTGC SHC SHC TGC SHC TGC SHC TTA075A Condensing Unit withTWE100AAir HandlerDataSystem TTA085A Condensing Unit withTWE100AAir Handler DataSystem TTA100B Condensing Unit withTWE100BAir Handler DataSystem DataSystem TTA125B Condensing Unit withTWE100B Air Handler TTA125B Condensing Unit withTWE155B Air Handler TTA155B Condensing Unit withTWE155B Air Handler DataSystem DataSystem DataSystem TTA200B Condensing Unit with TWE200B Air Handler Enter Bulb Entering Wet Bulb Temperature C M3/h AirflowPerformance Data TTA075A Condensing Unit Only I-PTable PD-17- Cooling Performance MBh Table PD-18 Cooling Performance kW TTA085A Condensing Unit Only SITable PD-19 Cooling Performance kW TTA100A Condensing Unit Only I-PTTA100A Condensing Unit Only SI Table PD-19 Cooling Performance MBhTable PD-20 Cooling Performance kW TTA100B Condensing Unit Only SI105 Cap. Btuh/1000 80.9 89.5 98.5 Cap. Btuh/1000 95.7Cap. Btuh/1000 90.8 Cap. Btuh/1000 85.9 94.9Cap. Btuh/1000 46.5 OD Unit Power kW Head pressure kPA 192673.7 80.1 OD Unit KW Head press Psig Cap. Btuh/1000 48.9 54.0 59.3 64.9 70.8Table PD-23 Cooling Performance kW TTA125B Condensing Unit Only I-PTTA125B Condensing Unit Only SI Table PD-23 Cooling Performance MBhTable PD-24 Cooling Performance MBh TTA155B Condensing Unit Only I-P56.1 60.5 OD Unit Power kW ODTemp Suction ReferenceTemperature F Head press. Psig56.0 60.8 65.9 OD Unit Power kW 45.2 49.5 54.0 58.6 63.4 OD Unit Power kWOD Unit KW Head press. Psig 23.7 26.0 28.4 30.8 OD Unit Power kW Head pressure kPA 172179.5 96.859.3 64.6 70.1 75.9 OD Unit Power kW 63.6 69.5 75.6 82.0 88.6 OD Unit Power kW66.2 72.0 78.1 84.4 OD Unit Power kW 80.1 OD Unit Power kWPerformance Data Table PD-29- Evaporator Fan Performance TWE050A I-P Table PD-29- Evaporator Fan Performance TWE050A SITable PD-30- Blower Speeds TWE050A Table PD-32 Blower Speeds TWE075A Table PD-31- Evaporator Fan Performance TWE075A I-PTable PD-29 Table PD-31 Evaporator Fan Performance TWE075A SITable PD-33 Evaporator Fan Performance TWE100A, TWE100B I-P Table PD-33Table PD-34 Blower Speeds TWE100A, TWE100B Motor SheaveTurns Open Drive Standard Table PD-35 Evaporator Fan Performance TWE155B I-PTable PD-35 Evaporator Fan Performance TWE155B SI Table PD-36- Blower Speeds TWE155BTable PD-38- Blower Speeds TWE200B,E Table PD-37 Evaporator Fan Performance TWE200B,E I-PTable PD-37- Evaporator Fan Performance TWE200B,E SI Table PD-37TWE050 1800 UnitModel No Straight 1400Table PD-41 Auxiliary Electric Heat Capacity Air Handler Electrical Data Table ED-1 Unit Wiring Condensing UnitsTable ED-3 Electrical Characteristics Motors Air Handler Table ED-4 Unit Wiring Air HandlerWith Unit Electric Heat DataHeater Minimum Maximum Model No2TTA075A/TWE155B Jobsite ConnectionsTTA050/TWE050A TTA075A/TWE075A TTA085/TWE075A TTA085/TWE100AAir Handler Typical WiringAir Handler Condensing Unit Single Compressor Typical Wiring Condensing Unit Dual Compressor Typical Wiring Figure DD-1 TTA075 Condensing Units Dimensional DataFigure DD-2 TTA085A and 100A Condensing Units Figure DD-3 TTA100C Condensing Units Figure DD-4 TTA100B and TTA125B Condensing Units Figure DD- 5- TTA155B Condensing Unit Figure DD-6 TTA155C Condensing Units Figure DD-7 TTA200B Condensing Unit Figure DD-8 TTA200F Condensing Unit 203.20 495.30 660.40 403.23 Table DD-1 Air Handler Dimensions in. mmTable DD-1 19-1/2 15-7/8Table DD-2 Table DD-2 Air Handler Dimensions in. mmTWE100A, 100B Table DD-3 Air Handler Dimensions in. mmFigure DD-12- TWE155B and 200B Air Handlers Table DD-4 Table DD-4- Air Handler Dimensions in. mm1826 2353 775 71 7/8 92 5/8 30 1/251 7/8 59 1/8 20 7/8 89 1/418 1/8 Figure DD-16 Electric Heater for TWE155 and 200 Air HandlersTable DD-6 Discharge Plenum Grille Dimensions in. mm Weights Table W-1 Unit and Corner Weights Net Lbs kgTableW-2 AccessoryWeights Net Lbs kg Table W-3 Air Handlers and Corner Weights lb1 kg Table W-4 Accessory Weights Net Lbs kgVertical TWE050, 075 TWE155 Refrigeration System Dual Manifolded Compressors MechanicalGeneral CasingLowAmbient Operation ControlsZone Sensor ThermostatEvaporator Fan Mechanical SpecificationsAccessories Evaporator CoilStocking Location Electronic Only Literature Order NumberFile No PL-UN-SS-PRC003-EN-0606 Supersedes PL-UN-SS-PRC003-EN-0104

SS-PRC003-EN specifications

The Trane SS-PRC003-EN is a high-efficiency commercial HVAC solution designed to cater to a wide variety of industrial applications. Known for its robust engineering and innovative design, this unit provides reliable climate control, ensuring optimal indoor environments in commercial spaces, manufacturing plants, and large facilities.

One of the standout features of the SS-PRC003-EN is its advanced inverter technology. This variable-speed compressor allows for precise cooling and heating adjustments based on real-time demand, which not only enhances system efficiency but also significantly reduces energy consumption. This capability not only minimizes operational costs but also contributes to a more sustainable energy profile, aligning with growing environmental concerns.

Another notable characteristic is its user-friendly control system. The unit is equipped with intuitive interfaces that allow facility managers to monitor and adjust settings remotely. This functionality ensures optimal performance, facilitates maintenance, and offers diagnostics that help identify potential issues before they lead to system failure.

Moreover, the SS-PRC003-EN features a built-in air filtration system that improves indoor air quality. It effectively removes dust, pollutants, and allergens from the air, contributing to healthier environments for occupants. This is particularly critical in commercial settings where many individuals congregate, ensuring compliance with health and safety regulations.

The design also emphasizes noise reduction technology. The unit operates at whisper-quiet levels, minimizing disruption in work environments and enhancing comfort for occupants. This is achieved through a combination of sound-absorbing materials and engineered airflow paths.

Additionally, the Trane SS-PRC003-EN is constructed with durability in mind. It resists corrosion, withstands harsh environmental conditions, and maintains performance longevity, making it a reliable choice for facilities that require constant operation.

With its combination of efficiency, advanced technology, user-friendly controls, and superior air quality management, the Trane SS-PRC003-EN stands out as a market leader in commercial HVAC systems. It offers businesses the performance they need while also promoting energy savings and environmental stewardship, making it an invaluable addition to any commercial infrastructure.