Installation

Clearances

Provide enough space around the unit to allow unrestricted access to all ser- vice points. Refer to Figure 1 through Figure 4 for unit dimensions and mini- mum required service and free air clearances. Observe the following points to insure proper unit operation.

A. Do not install the unit under a low overhang. Condenser discharge must not be restricted. See Notes in Figure 1 through Figure 4.

NOTICE: Do not obstruct condenser discharge air. This can result in warm air recirculation through the coil.

B. Do not locate the unit in a position where runoff water can fall into the fan discharge openings.

C. Condenser intake air is supplied from three or four sides of the unit. Adhere to the minimum required clearances given in Figure 1 through Figure 4.

Unit Mounting

Rooftop Mounting: If the unit will be roof mounted, determine for certain that the structure is strong enough to support the unit and any required accessories. Unit weights are given in Table 2. The unit should be elevated on a level, field fabricated four-inch steel or wood 4" x 4" mounting frame. Complete the frame and secure it into position before lifting the unit to the roof. The mounting frame must sup- port a minimum of three of the unit’s four sides and should span roof sup- ports to distribute the load on the roof.

Figure 5 Roof Mounted Unit

WARNING

Structural Failure!

Ensure that the roof structure supports are strong enough to support the weight of the unit and any accessories. Failure to do this could result in death or seri- ous injury due to structural fail- ure and could seriously damage the unit and the building.

Ground Level Mounting

“For ground level installation, the unit base should be adequately supported and hold the unit near level. The installation must meet the guidelines set forth in local codes.” The support should extend two inches beyond the unit base channels at all points. The unit and support must be isolated from any adjacent structure to prevent possible noise or vibration problems. Any ground level location must com- ply with required clearances given in Figure 1 through Figure 4.

Holes must be made in the structure to run refrigerant lines. For the major- ity of ground-level installations, the holes can be made in the header that rests on top of the foundation. Alter- natively, these holes may also be made in the foundation itself. On roof- mounted units, refrigerant lines should enter the building as close to the unit as possible; preferably within three to four inches of the refrigerant connection on the unit, plus a six-inch (long radius) 90 degree "L" entering the building (See Figure 5).

Refrigerant Piping Guidelines A. Maximum recommended line lengths: (per circuit)

Maximum linear length

200 Ft.

(w/o accumulator)

 

Maximum discharge line lift

200 Ft.

Maximum liquid line lift

60 Ft.

B. Maximum allowable pressure

drops (R-410A):

 

Discharge line

10 psi

Liquid line (without subcooler)...

50 psi

Route refrigerant piping for minimum linear length, minimum number of bends and fittings (no reducers) and minimum amount of line exposed to outdoor ambients.

C. Recommended line sizes: CTA090, 120A (single circuit) CTA120B, 180B (dual circuit)

Discharge line - 7/8 inch sealed type L

refrigerant tubing.

Liquid line - 1/2 inch sealed type L refrigerant tubing.

10

PKG-SVX17A-EN

Image 10
Contents Installation Owner Diagnostics Later Design SequenceOverview of Manual Contents Split System Condensing Model Nomenclature Model Number DescriptionModel Number Description Digits 1,2,3 Product Type Digits 8 ElectricalCTA090A CTA120ACTA120B CTA180B Electrical Data CTA Unit Electrical DataInstallation Clearances Unit MountingRefrigerant Piping Procedures Outdoor Units Refrigerant Piping Procedure Indoor UnitSystem Evacuation Leak CheckInsulating and Isolating Refrigerant Lines Unit Power Supply ProcedureElectrical Wiring Gaseous ChargingWiring Low Voltage CTA180B/SC,IRH150Field Wiring Wiring Wiring Wiring Wiring Refrigeration Diagram Typical Split System Cooling DiagramSystem Pre-Start Procedure Refrigerant PipingGeneral Cooling ModeUnit Start-Up Evaporator Fan Indoor Supply AirMaintenance MonthlyMaintenance Log Warranty CTAPage Page Trane

PKG-SVX17A-EN specifications

The Trane PKG-SVX17A-EN is an advanced packaged air conditioning system designed for commercial applications. This unit stands out due to its robust construction, high efficiency, and user-friendly features, making it a suitable option for various building types, including offices, restaurants, and retail spaces.

One of the main features of the PKG-SVX17A-EN is its high energy efficiency, which is achieved through the incorporation of variable speed technology. This technology allows the compressor to adjust its output based on the cooling and heating demands of the space, leading to reduced energy consumption and lower utility bills. Additionally, the system’s SEER (Seasonal Energy Efficiency Ratio) ratings exceed industry standards, which is beneficial for both environmental sustainability and operational costs.

The PKG-SVX17A-EN utilizes advanced refrigerant management systems that incorporate environmentally friendly refrigerants. This aligns with Trane's commitment to sustainability and compliance with global environmental regulations. The unit is also equipped with an intelligent controller that enables precise monitoring and control of temperature, humidity, and airflow. This feature ensures optimal comfort levels while maximizing efficiency.

In terms of installation, the PKG-SVX17A-EN is designed for easy integration into existing infrastructure. Its compact design allows for flexible placement and minimizes the required space, making it ideal for commercial rooftops. The unit also incorporates advanced sound dampening technologies to reduce operational noise, making it suitable for noise-sensitive environments.

Another key characteristic of the Trane PKG-SVX17A-EN is its comprehensive warranty program, which provides peace of mind to building owners and operators. This warranty covers critical components and provides access to Trane’s extensive service network, ensuring that the system remains in peak operating condition throughout its lifespan.

The PKG-SVX17A-EN is designed with user convenience in mind, featuring accessible service points for maintenance and servicing. This design minimizes downtime and ensures that system performance remains at peak levels.

In summary, the Trane PKG-SVX17A-EN packaged air conditioning system is an innovative solution for commercial environments that value efficiency, reliability, and sustainability. With its advanced technologies and thoughtful design features, it is well-equipped to meet the demands of modern commercial spaces while promoting energy savings and enhanced comfort.