Page 16

Temperature Controls

The boilers covered in this instruction manual are equipped with (adjustable) thermostat or step control to regulate water temperature and other controls to provide safety features. See the wiring diagrams on page 13 & 14 and/or literature included with this manual for additional information.

Hot water temperatures required for automatic dishwasher and laundry use can cause scald burns resulting in serious personal injury and/or death. The temperature at which injury occurs varies with the person’s age and duration of exposure. The slower response time of children, the elderly or disabled persons increases the hazards to them. Never allow small children to use a hot water tap or draw their own bath water. Never leave a child or disabled person unattended in a bathtub or shower. The boiler should be located in an area where the general public does not have access to set temperatures.

Figure 1. shows the approximate time-to-burn relationship for normal adult skin.

Water Temperature

 

Time to Produce 2nd & 3rd

 

Degree Burns on Adult Skin

 

 

 

 

 

180°F (82°C)

 

Nearly Instantaneous

160°F (82°C)

 

About 1/2 second

150°F (82°C)

 

About 1-1/2 seconds

140°F (82°C)

 

Less than 5 seconds

130°F (82°C)

 

About 30 seconds

120°F (82°C)

 

More than 5 minutes

80°F (82°C)

 

- - - - - - - - - - - - - - - - -

 

 

 

 

FIGURE 1.

Additional instructional literature is provided with the boiler for adjusting this control.

Always close and lock the cabinet door after making a temperature adjustment. Turn on electricity.

DRAINING

The boiler must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the boiler.

1.Turn off the electrical disconnect switch.

2.Open a nearby outlet until the water is no longer hot and close the make-up water valve and system valves as necessary.

3.Open a nearby outlet to vent the parts of the system being drained.

4.Open the boiler drain valve.

5.If the boiler is being drained for an extended shutdown, it is suggested the drain valve be left open during this period.

• Follow FILLING instructions to restore boiler to service.

16

Image 16
Contents Installation Operation Service Maintenance Limited Warranty Commercial Electric BoilersSafe INSTALLATION, USE and Service Precautions Hydrogen GAS Flammable General Safety InformationGrounding Instructions Table of Contents IntroductionDimension Data Sizes and Data NW37 Thru NW150Sizes and Data NW220 Thru Dimension Data cont’d Boiler Specifications StandardFeatures and Components Actual Configuration MAY VaryModel and Rating Locating the Boiler ApprovalsFacts to Consider About the Location Installation Required AbilityGeneral Pressure Relief ValveClosed Water Systems Thermal ExpansionElectrical Data Branch CircuitCalculating Amperage Overcurrent Protection Boiler CircuitsWiring Diagrams Diagram Three Phase Delta with Step Control Diagram Three Phase WYE with Step ControlHigh Temperature Limits Temperature RegulationOperation Filling the BoilerTemperature Controls DrainingMaintenance FlushingSediment Removal Water and Lime Scale RemovalTroubleshooting Checklist System Water TestSW-37 Thru SW-670 Electric HOT Water Boiler Limited Warranty Division of A. O. Smith Corporation RENTON, Washington