White Rodgers 1F95-391 Compressor OFF Delay, Balance Point Temperature, Compressor Lockout

Page 7

COMPRESSOR OFF DELAY

Installer table, step 11 is available if the

fossil fuel kit alternative option (PUMP OFF) is selected.

This item allows a selection of 0 to 99 seconds, which is the time that the compres- sor will continue to run after the point that the auxiliary heat is energized. Running the compressor after the Auxiliary has started prevents cool air from creating drafts prior to the heat exchanger reaching normal tempera- tures. The factory default value of 60 seconds is typical for most systems. Consult with your equipment’s manufacturer before increasing this time.

BALANCE POINT TEMPERATURE

Installer

table step 12, bPT, is available only

 

if the fossil fuel kit option is selected and the

 

outdoor temperature sensor is used (see the

 

user menu in the owner manual).

 

This item allows a selection of 5 to 50

° F,

which is the outdoor temperature below

 

which the thermostat will not energize heat

 

pump compressor stages. It will use

 

Auxiliary heat stages (only) until the outdoor

 

temperature raises 3

° above the selected

 

temperature and then allow compressor

 

stages to operate. The factory default value

 

of 35 °

F is typical for most systems.

 

BALANCE POINT

Installer table step 13, bP, is available only if the fossil fuel kit option is selected and the outdoor temperature sensor is not used. The Balance Point influences when second stage comes on. The factory default creates

approximately 1 ° F between stages. Increas- ing the setting decreases the separation

between stages. Decreasing the value increases stage separation. This adjustment allows a small change in the operation of your heat pump system versus your auxiliary system relative to the thermostat adjustment.

PROGRAMMABLE BLOWER BALANCE POINT

Installer table step 14, bbP, is available only when configured for Heat Pump systems, and wired as shown in Fig. 3.

If the system is running a high percentage of the time due to cold weather conditions, the output vent air temperature may be cooler than normal thus creating a drafty room condition. This feature will reduce the draft by lowering the blower speed with the DHM terminal. The lower speed will make the air temperature slightly warmer and more comfortable.

Example: If you want the blower to go to a lower speed when the system is running greater than 50% of the time,then reduce the Blower Balance Point to 50%.

To turn this feature OFF, press

to 99

then press once more to display OFF.

COMPRESSOR LOCKOUT.

(Installer table step 15). This thermostat is capable of helping to protect the system against premature compressor failure by “locking out” the compressor for at least five minutes after each cycle. When the thermo- stat is in compressor lockout, the word COOL will flash on the display. With heat pump systems, the word HEAT will flash if the lockout occurs during a heat cycle.

During this period, the compressor will not be energized.

Lockout Bypass Option

FOR QUALIFIED SERVICE TECH-

NICIANS’ USE ONLY.

HOMEOWNERS SHOULD NOT USE

THIS FEATURE DUE TO POSSIBIL-

ITY OF EQUIPMENT OR PROP-

ERTY DAMAGE, OR PERSONAL

INJURY.

COMPRESSOR SHORT TERM CYCLE

PROTECTION

If this thermostat has been configured to provide short-cycle protection, during the 5-minute lockout period the thermostat will lock out the compressor to allow head pressure to stabilize. To override this feature for one cycle while testing

thermostat operation,

press

SET

TIME

and

SET

DAY

buttons at the same time.

 

 

 

 

 

If the

system

has short-cycle protection, this

 

item should not need to be enabled. How-

 

 

ever, if your system does not have short-

 

cycle protection,

turn COMP LOCK ON

.

This will protect the compressor from short-

 

 

cycling and potential premature compressor

 

 

failure.

 

 

 

 

 

Note that COMP LOCK OFF

permanently

disables compressor lockout. If you need to

 

 

temporarily

disable compressor lockout,

 

please see

Lockout Bypass Option

 

.

DISABLING AUTOMATIC

CHANGEOVER MODE.

(Installer table step 16). This thermostat, as configured at the factory, provides automatic changeover, which allows the thermostat to switch between heating and cooling to maintain temperature. In this configuration, when you press the SYSTEM button, the thermostat will go through HEAT-OFF- COOL-AUTO modes (HEAT-EMER-OFF- COOL-AUTO for heat pumps). Select HEAT(-EMER)-OFF-COOL to disable the automatic changeover feature.

Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage

 

 

 

 

 

 

 

 

 

 

Decreasing

 

Stage separation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

Fossil

 

 

 

 

 

 

 

 

 

1˚F at setting 05

 

Higher number

 

temperature

 

Auxiliary

 

 

 

 

 

 

 

 

 

 

 

 

Lower number

 

 

 

 

 

 

 

 

Stage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Continued)

 

 

HEATING

 

COOLING

 

 

 

 

 

 

 

Anticipation Value

Cycle Length

 

Differential Temperature

Cycle Length

 

Differential Temperature

 

 

 

 

 

 

 

1–8

Shorter

 

0.4–0.6°F (0.2–0.3°C)

N/A

 

N/A

 

 

 

 

 

 

 

9–20

Longer

 

0.6–1.0°F (0.3–0.6°C)

Shorter

 

0.6–1.0°F (0.3–0.6°C)

 

 

 

 

 

 

 

21–40

Hydronic

 

1.0–1.6°F (0.6–0.9°C)

Longer

 

1.0–1.6°F (0.6–0.9°C)

 

 

 

 

 

 

 

These numbers are approximate and represent operation with a typical system. Actual temperature differentials and run times may vary widely based on your building and equipment, as well as outdoor temperature conditions.

7

Image 7
Contents Electrical Data SpecificationsPrecautions DescriptionAttach Base to Wall InstallationConfiguring and PROGRAM- Ming Remove OLD ThermostatHeat Pump Terminal Outputs CONFIGURATIONsection for proper thermostat configurationConfiguration MULTI-STAGE Terminal OutputsDHM SwitchesReset Switch E2/P Switch DHM Terminal FunctionInstaller Configuration SET Time Installer TableComments Firmly PressBalance Point Compressor OFF DelayBalance Point Temperature Disabling Automatic Changeover ModeComments Service ReminderService OFFCheck Thermostat Operation TroubleshootingNo Heat Common ProblemsNarrow or wide temperature swing No Heat/No Cool/No FanWhy is the temperature change Thermostat Setting and ThermostatWhy does the system run with Setpoint and room temperature

1F95-391 specifications

The White Rodgers 1F95-391 is an advanced thermostat that stands out in the market for its user-friendly design, superior functionality, and energy-saving capabilities. Specifically tailored for both residential and light commercial applications, this programmable device is engineered to provide optimal climate control while enhancing energy efficiency.

One of the key features of the 1F95-391 is its large, easy-to-read display. The backlit LCD screen allows for simple navigation even in low-light conditions, ensuring you can adjust the temperature settings with ease. The interface is intuitive, allowing users to quickly familiarize themselves with its functionalities.

This thermostat supports a wide range of heating and cooling systems, making it versatile for various setups, including gas, oil, and electric systems. Its compatibility with both single-stage and multi-stage heating and cooling systems further aids in its adaptability, catering to different home environments.

Energy conservation is a hallmark of the 1F95-391. The programmable scheduling allows users to create customized temperature settings that align with their daily routines. This feature can significantly reduce energy consumption by allowing the system to operate at lower settings when occupants are away or sleeping, leading to substantial cost savings on utility bills over time.

The 1F95-391 also integrates advanced technologies such as Adaptive Intelligent Recovery, which learns how long it takes to reach the desired temperature and adjusts the heating or cooling accordingly. This means that the home maintains comfort while optimizing energy use, eliminating the need for excessive manual adjustments.

Moreover, the thermostat's filter change reminder ensures that users are alerted when it's time to replace or clean the HVAC filter. This feature not only helps maintain the air quality in the home but also extends the lifespan of the HVAC system by ensuring it operates efficiently.

In addition to its operational features, the White Rodgers 1F95-391 boasts reliability and durability. Constructed with high-quality materials, it is designed to withstand the test of time and provide consistent performance, making it a sound investment for any property owner.

Overall, the White Rodgers 1F95-391 represents a significant advancement in smart temperature control, combining functionality, efficiency, and ease of use. Whether upgrading an existing thermostat or installing a new one, consumers can expect enhanced comfort and reduced energy costs.