If, during the inspection of your furnace, you find any of the following conditions:
•Excessive amounts of dust and lint on components.
•Damaged or deteriorated components or surfaces.
•Leaks or blockage in the vent pipe passages.
•Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur- nace, and set thermostat to the desired temperature.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
TABLE 1: Filter Sizes
Input / Output | CFM | Cabinet | Top Return |
BTU/H (kW) | (m3/min) | Size | Filter in(cm) |
40/37 (11.72/10.84) | 1200 (34) | A | (2) 14 x 20 (36 x 51) |
60/55 (17.57/16.10) | 1200 (34) | B | (2) 14 x 20 (36 x 51) |
80/75 (23.42/21.96) | 1200 (34) | B | (2) 14 x 20 (36 x 51) |
80/75 (23.42/21.96) | 1600 (45) | C | (2) 14 x 20 (36 x 51) |
100/95 (29.28/27.82) | 1600 (45) | C | (2) 14 x 20 (36 x 51) |
100/95 (29.28/27.82) | 2000 (57) | C | (2) 14 x 20 (36 x 51) |
120/112 (35.14/32.80) | 2000 (57) | D | (2) 14 x 20 (36 x 51) |
SECTION II: SERVICE AND MAINTENANCE MANUAL
SAFETY SECTION
The following safety rules must be followed when servicing the furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, and death or property damage.
•Before servicing, disconnect all electrical power to the fur- nace.
•When servicing controls, label all wires prior to discon- necting. Reconnect wires correctly.
•Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1.The vent terminal screen (if applicable).
2.The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac- turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3.The furnace burners, ignitor and flame sensor.
4.The condensate collection and disposal system. If any disassem- bly of components containing flue or vent gases is required, a qualified service agency must perform the service.
127237-UUM-A-0605
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer to Figure 1 for component location.
Continuous Blower
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the ON position the thermostat circuit is completed between terminals R and G. The motor will operate on the speed tap selected on the Continuous Fan Speed Jumper on the control board (HI COOL, LO COOL, or HEAT pins).
Intermittent Blower - Cooling
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the AUTO position the thermostat circuit is completed between terminals R and G when there is a call for cooling. The motor will operate on the speed tap wire that is connected to the HI COOL ter- minal on the control board. When used with two-stage cooling units, the motor will operate on the speed tap connected to the LO COOL terminal when first stage cooling is operating. The motor will operate on the speed tap connected to the HI COOL terminal when second stage cool- ing is operating. The fan off setting is fixed at 60 seconds for SEER enhancement.
Heating Cycle
When the thermostat switch is set on HEAT and the fan is set on AUTO, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control pro- vides a 17-second warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for 15 seconds and the blower motor will operate for the amount of time set by the fan-off delay jumper located on the control board. See Figure 8. The heating cycle is complete, and ready for the start of the next heating cycle.
| | | | | | | | RED - LOW SPEED |
| | | | | | | | YELLOW - MED. LOW SPEED |
| | | | | | | | BLACK - HIGH SPEED |
| | | | | | | | BLUE -MED. HIGH SPEED |
PARK PARK | LO COOL | HICOOL | HEAT | EAC | L1 | XFMR | HUM | NEUTRALS |
CONTINUOUS
FAN SPEED
JUMPER
FAN OFF
ADJUSTMENT
JUMPER
FIGURE 8: Typical Heat/Cool Speed Tap Connections
If the flame is not detected within 2 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.