System Sensor DH500ACDC specifications Mount Duct Housing, Install The Inlet Tube

Page 3

Figure 2. Speed nut mounting location:

HOLE B

HOLE A

DUCT

WALL

SPEED

NUT

H0116-00

CAUTION: Do not overtighten the screws.

Exception: Where it is physically impossible to locate the detector accordingly, the detector can be positioned closer than six duct widths, but as far as possible from the open- ing, bend, or deflection plates.

Step 3. Mount Duct Housing

Remove the duct housing cover. Slide the foam gaskets over the tube bushings as shown in Figure 2A. Make sure the two small holes in the gaskets line up with the two duct housing mounting holes. Put one 5/16-inch O-ring over each of the two #10 sheet metal screws. Use the two sheet metal screws to secure the duct housing to the duct.

Table 1. Sampling (Inlet) Tubes

 

TUBE

OUTSIDE DUCT WIDTH

ST-1.5

1 to 2 ft.

(0.3 to 0.6 m)

ST-3

2 to 4 ft.

(0.6 to 1.2 m)

ST-5

4 to 8 ft.

(1.2 to 2.4 m)

ST-10

8 to 12 ft.

(2.4 to 3.7 m)

Figure 3. Air duct detector inlet sampling tube:

Figure 2A. Installation of foam gaskets over sam- pling tube bushings:

MOUNTING

SAMPLING

DUCT DETECTOR

TUBE BUSHING

HOUSING

SCREWS

 

 

O-RINGS

 

EXHAUST TUBE

 

 

(EXTENSION BUSHING)

 

 

FOAM

 

 

GASKETS

SCREW HOLES FOR ATTACHING

DETECTOR HOUSING TO DUCT

H0117-00

Step 4. Install The Inlet Tube

The inlet tube (shown in Figure 3) is identified by a series of air inlet holes on the tube. This tube must be purchased separately. Order the correct length, as specified in Table 1, for the width of the duct where it will be installed. The exhaust tube is molded into the base of the duct housing.

The inlet tube should be installed in the inlet sampling tube bushing located in the center of the duct detector housing. (See Figure 2A.) The air inlet holes must face into the air flow. To assure proper installation, the tube mount- ing flange is marked with arrows. Mount the inlet tube so that the arrows point into the air flow. Figure 4 shows the various combinations of duct detector and tube mounting configurations with respect to air flow.

FLANGE

AIR HOLES

INLET

 

 

 

TUBE

 

 

END

 

 

PLUG

ARROWS

AIR FLOW DIRECTION

H0108-00

MUST FACE

 

 

INTO AIR FLOW

D500-07-00

3

I56-432-11R

Image 3
Contents Power Supply Electrical Ratings For DH500ACDC Before InstallingGeneral Description Contents Of The Duct Detector Housing Kit Installation SequenceDrill The Mounting Holes Install The Inlet Tube Mount Duct HousingInstallation for Ducts More Than 8 Feet Wide Installation for Ducts Less Than 8 Feet WideModification Of Inlet Sampling Tubes Field Wiring Wiring Installation GuidelinesWiring Instructions Install the FiltersD500-07-00 I56-432-11R Trouble Test Alarm TestsPerform Detector Check Air Flow MOD400R Sensitivity TestInstall the Cover Periodic Maintenance RequirementsPerform the Final System Check Ion Units Photo UnitsRA400ZA AccessoriesThree-Year Limited Warranty Detector Test LOG

DH500ACDC specifications

The System Sensor DH500ACDC is a versatile and reliable heat detector that has gained a reputation for its advanced technology and robust features, making it an ideal choice for both commercial and residential fire safety applications. This heat detector is designed to enhance fire detection systems by providing accurate temperature monitoring and fast response times, thereby ensuring optimal safety for buildings and their occupants.

One of the standout features of the DH500ACDC is its dual power source capability, allowing it to operate seamlessly on both AC and DC power. This flexibility ensures that the detector continues to function efficiently even during power outages, making it an essential component of any comprehensive fire safety system. The ability to work with varied power sources maximizes its usability across different environments.

Equipped with a sophisticated thermal sensing element, the DH500ACDC is capable of detecting high temperatures or rapid rises in temperature. Its fixed temperature setting, combined with its rate of rise detection feature, enables it to quickly identify potential fire hazards. This dual mechanism significantly reduces the likelihood of false alarms while maintaining sensitivity to genuine threats.

The device is built for durability and reliability. Featuring a rugged construction, it is designed to withstand harsh environmental conditions, making it suitable for industrial settings, warehouses, and other challenging environments. Additionally, the detector's low-profile design allows for easy installation and minimal aesthetic disruption in any setting.

Another noteworthy characteristic of the DH500ACDC is its compatibility with various fire alarm control panels. This interoperability facilitates seamless integration into existing systems, enhancing overall functionality without the need for extensive modifications. This feature is particularly beneficial for organizations looking to upgrade their fire safety infrastructure.

Moreover, the DH500ACDC has undergone rigorous testing and complies with international standards, ensuring quality and performance that fire safety professionals can trust. Its comprehensive range of features, alongside its advanced technologies, make it a top choice for those seeking to enhance their fire detection capabilities.

In conclusion, the System Sensor DH500ACDC represents a significant advancement in heat detection technology. Its dual power source capability, sophisticated sensing mechanisms, rugged construction, and compatibility with fire alarm systems make it an indispensable tool in safeguarding lives and property against the dangers of fire. This detector embodies the commitment to safety that System Sensor is known for, providing peace of mind to users in various applications.