System Sensor BS5839 manual Lantern Lights, Location and Spacing of Optical Beam Detectors

Page 15

2.4.7. Stairwells and Lift Shafts

Internal stairwells and lift shafts and other vertical service ducts through a building provide a clear path for smoke to pass between floors of a building as if they were chimneys. It is therefore important to protect these, preferably using smoke detectors.

All vertical shafts through a building must be protected by a smoke or heat detector at the top of the shaft, and by a detector within 1.5m of each opening onto the shaft.

In internal stairways, a detector should be mounted on each main landing (Figure 2.4.7). In addition, if the detectors on the landings are separated by more than 10.5m, intermediate detectors should be mounted on the underside of the stairs.

Detectors should also be fitted into any room opening directly onto a stairway other than a WC cubicle.

<10.5M

Figure 2.4.7. Detector in Stairwells

1.5M1.5M

Where they are installed into voids, a detector's sensing element should be mounted either in the top 10% or the top 125mm of the void space whichever is greater. Although it can be difficult to install detectors the correct way up in void spaces, care should be taken as incorrect orientation of a detector can lead to increased ingress of dirt and dust, leading to reduced maintenance intervals, and possible nuisance alarms.

Detectors above a false ceiling may be used to protect the area below it, if the false ceiling is perforated uniformly across the complete area of the ceiling, with the holes making up over 40% of the ceiling surface area, having a minimum size of 10mm and the false ceiling having a thickness of less than three times the dimensions of the perforations.

In all other cases, the areas above and below a false ceiling should be treated as separate, and thus should be protected separately with detectors below the ceiling, and if necessary in the void above the ceiling.

2.4.9.Lantern Lights

A detector should be mounted in any lantern light used for ventilation or having a height exceeding 800mm. The temperature in lantern lights can change rapidly owing to heating by sunlight, which means that rate-of-rise heat detectors should not be used and heat detectors should be protected from direct sunlight.

2.4.10.Location and Spacing of Optical Beam Detectors

Generally, for an optical beam detector mounted within 600mm of a ceiling, the fire detection coverage is up to 7.5m either side of the beam (Figure 2.4.9). The beam of the detector should not be closer than 500mm to any obstruction. Similar recommendations to above apply to the application of beam detectors with sloped ceilings, voids, false ceilings, walls and partitions and ceiling obstructions.

 

 

 

 

 

Maximum 100m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

7.5m

 

500mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmitter or

 

 

 

Receiver or

 

 

 

Transmitter/Receiver

 

 

 

 

 

 

Reflector

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

 

15m

Transmitter or

 

 

 

Receiver or

 

 

 

Transmitter/Receiver

 

 

 

 

 

 

Reflector

 

 

 

 

 

 

 

Application Guide

Figure 2.4.8. Protection of Vertical Shafts

2.4.8.Voids and False Ceilings

Detectors need not normally be installed in voids less than 800mm deep, unless on the basis of a fire risk assessment it is thought that fire or smoke could spread extensively through the voids before detection, or unless the fire risk in the void is such as to warrant protection. Use of heat and smoke detectors in voids greater than 800mm high is dependant on the protection category, and fire risk assessment.

Figure 2.4.9: Standard Beam Detector Layout

Where it is likely that people will be present in an area protected by beam detectors, the detectors must be mounted at a minimum height of 2.7m, and consideration must also be given to the possibility of other temporary obstructions to the beam such as forklift trucks.

For further information on the use and mounting of beam detectors, see System Sensor Europe's Guide to Projected Beam Detectors.

Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.

Reference must be made to relevant national and local standards.

15

Image 15
Contents Guide to intelligent fire systems Contents Guide to Intelligent Fire Alarm SystemsGuide to Intelligent Fire Alarm Systems Alarm Systems Intelligent Fire Alarm SystemsIntelligent Fire Dedicated address programmer Decimal address switchesSystem Fault Tolerance Addressing MethodsIntelligent Fire Alarm Systems PRE-ALARM FacilityFire System Zones Advantages of Intelligent Systems Programming of Intelligent Fire Alarm PanelsRemote Leds Interface ModulesCategory M Systems GuideDetector Application Guide Fire System CategoriesApplication Guide 1. Manual Call Point Positioning Manual Call PointsSelection of Automatic Fire Detectors During normal use Fixed temperature detector 58CRate of rise heat detector Areas subject to rapid changesTo EN54-7 10.5m Heat detector conforming to Location and Spacing of Automatic Fire DetectorsCeiling Height Detector typeCorridors Corridor being 7.5m and 5.3m respectivelySloping Ceilings Lantern Lights Location and Spacing of Optical Beam DetectorsVoids and False Ceilings Visual Alarm Signals Audible Alarm SignalsCodes and standards in the UK BS5839 Part 12002, Section Maintenance of Fire DetectorsSeries 200 Plus Analogue Addressable Detector Range Series 200 Plus FeaturesGeneral Specifications Intelligent Product Range2251TEM PHOTO-THERMAL Sensor WeightSystem Sensor Intelligent Product Range 2251EM Photoelectric Smoke Sensor5251REM, 5251EM and 5251HTEM Heat Sensors Drift Compensation and Smoothing6500S Beam Detector Remote Test SwitchOperating Temperature -10C to 55C Weight 142gLaser Detector 2251EIS Intrinsically Safe Detector and IST200 Interface With LED blink enabledB500 Series Bases Depth Weight 100gInterior diameter Exterior diameterM200XE Short Circuit Isolator Module M200 Series Module RangeM210E-CZ Conventional Zone Module Specifications Max Standby Current, externally powered zoneM201E Output Module 5A at 250VACIndoor products are generally rated at IP24D AccessoriesCall Points IndoorMajority of back box formats Audio Visual ProductsDetector Base Sounders Sounder StrobesOther Information Jernholmen DK-2650 Hvidovre Denmark Tel +45 36 349 Other InformationApproval Bodies for Fire Detection Products Avenue Hoch Paris, France Tel +33 1 53 89 00Fax + 7 095 System Sensor Fire DetectorsVolochaevskaya Str 40, Bld Telephone + 7 095 Telephone + 91 124

BS5839 specifications

System Sensor BS5839 is a standard that pertains to fire detection and alarm systems, providing guidelines for the design, installation, and maintenance of these essential safety tools. It is crucial for safeguarding lives and property, ensuring that fire detection systems are effective and reliable. The BS5839 standard, established in the UK, covers a wide range of fire alarm system types, including conventional, addressable, and wireless systems.

One of the main features of BS5839 is its comprehensive classification of fire detection systems. The standard divides systems into categories based on the level of risk and the environment in which the system will operate. This classification helps ensure that the system installed meets the specific needs of the building and its occupants. For example, Category L systems are meant for life safety, while Category P systems are designed to protect property.

The technologies underpinning BS5839 include various types of detectors, alarm devices, and control panels. Smoke detectors, heat detectors, and multi-sensor detectors are prominent among the devices specified in the standard. Smoke detectors use photoelectric or ionization principles to detect smoke and signal an alarm, while heat detectors respond to temperature changes. Multi-sensor detectors combine both smoke and heat detection technologies to provide a more reliable response to fire conditions.

Another key characteristic of BS5839 is the emphasis on regular testing and maintenance. The standard outlines procedures to ensure that systems remain operational and effective over time. This includes routine system checks, functional testing, and more in-depth inspections at regular intervals. Ensuring that systems are maintained according to BS5839 is vital for compliance with insurance requirements and for safeguarding against potential legal liabilities.

Furthermore, BS5839 highlights the importance of staff training and awareness. It emphasizes that personnel responsible for fire safety must be adequately trained in the operation and response to fire alarm systems. This ensures that in the event of a fire, occupants are prompted to take appropriate action and evacuate safely.

In summary, System Sensor BS5839 provides a crucial framework for fire detection and alarm systems. Its classification of systems, incorporation of advanced technologies, and emphasis on maintenance all contribute to enhanced safety and compliance, protecting lives and property effectively.