System Sensor BS5839 manual Audible Alarm Signals, Visual Alarm Signals

Page 16

Application Guide

2.5. ALARM SIGNALS

2.5.1.Audible Alarm Signals

Audible fire alarm signals must provide a clear warning of a fire to all those for whom the signal is intended. For category M and L systems this would normally imply all occupants

of a building, however in some sites this may not apply, for example in hospitals or rest homes, residents might need assistance to evacuate, in which case it may be sufficient to alert staff.

The general requirement for the volume of audible alarm signals is that they should provide a Sound Pressure Level (SPL) of at least 65dB(A), but not more than 120dB(A) throughout all accessible areas of a building. See figure 2.5.1.

Minimum 65dB(A)

 

 

 

Minimum

Minimum

 

 

 

65dB(A)

65dB(A)

 

 

 

Minimum

 

 

 

 

65dB(A)

 

 

 

 

 

down

Area<60m²

Min60dB(A)

Minimum

Minimum

 

65dB(A)

65dB(A)

 

 

 

Stairwell

 

 

 

 

 

 

 

 

Min 60dB(A)

Figure 2.5.1. General Fire Alarm Sound Pressure Levels

Exceptions to this general rule are as follows:

In stairways the SPL may be reduced to 60dB(A)

Enclosures less than 60m² may be reduced to 60dB(A)

There is no minimum for enclosed areas less than 1m²

At specific points of limited extent the SPL may be reduced to 60dB(A)

Where a continuous background noise level greater than 60dB(A) is present the fire alarm signal should be 5dB above the ambient, but not greater than 120dB(A).

Sounder

Minimum

85dB(A)

Machinery

Generating

80dB(A)

Where the alarm is intended to wake people, an SPL of 75dB(A) is required at the bed head. Generally this will require a sounder to be placed within the room.

Volume at

Bed Head

75dB(A)

Where it is not possible to place a sounder within a room, there will be a loss of approximately 20dB(A) through a standard door, and 30dB(A) through a fire door.

 

Fire Door

Standard Door

 

Reduces by

Reduces by

 

30dB(A)

20dB(A)

Sounder

115 - 30 =

85 - 20 =

Volume

115dB(A)

85dB(A)

65dB(A)

 

 

 

Warning: Volumes greater than 120dB(A) will cause damage to hearing.

SOUND REDUCTION AGAINST DISTANCE

Based on a sounder rated at 1m

 

0

 

 

 

 

(dB(A)

-5

 

 

dB(A) Reduction

 

-10

 

 

 

 

reduction

-15

 

 

 

 

 

 

 

 

 

Sound

-20

 

 

 

 

 

 

 

 

 

 

-25

 

 

 

 

 

-30

 

 

 

 

 

0

5

10

15

20

Distance (Metres)

In open space, as the distance from a sounder doubles, the sound level will be reduced by 6dB(A), as shown.

It is preferable to use multiple quieter sounders to achieve the required sound level, rather than a smaller number of loud devices. This is to prevent points of excessive volume, which may lead to disorientation or damage to hearing. Two sounders providing equal sound levels will combine to add 3dB(A) to the SPL.

2.5.2.Visual Alarm Signals

25m

 

-16dB

-23dB

69dB(A)

 

 

4m

 

12.6m

 

1

 

0dB

63 + 3

85dB(A)

 

 

= 66dB(A)

 

 

 

 

 

 

4m

 

 

 

1

 

 

62 + 3

69dB(A)

 

-16dB

= 65dB(A)

Note: dB(A) figures are for example only. Left side represents attenuation; right side indicates typical sound pressure level

Visual alarms are normally used only as a supplement to audible alarms where they are likely to be ineffective, for example in areas of high background noise levels where hearing protection is likely to be worn. They can however be used alone where audible warnings are undesirable for example operating theatres and recording studios.

Visual alarms should be clearly distinguishable from other warning lights, preferably red and should flash at a rate of 30 to 130 flashes per minute. The recommended mounting height is above 2.1m, however they should not be mounted closer than 150mm from the ceiling. They should be positioned so that any alarm is clearly visible from all locations within the area protected.

16

Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.

Reference must be made to relevant national and local standards.

Image 16
Contents Guide to intelligent fire systems Guide to Intelligent Fire Alarm Systems ContentsGuide to Intelligent Fire Alarm Systems Intelligent Fire Alarm Systems Alarm SystemsIntelligent Fire Decimal address switches System Fault ToleranceAddressing Methods Dedicated address programmerPRE-ALARM Facility Intelligent Fire Alarm SystemsFire System Zones Programming of Intelligent Fire Alarm Panels Remote LedsInterface Modules Advantages of Intelligent SystemsGuide Detector Application GuideFire System Categories Category M SystemsApplication Guide Manual Call Points 1. Manual Call Point PositioningSelection of Automatic Fire Detectors Fixed temperature detector 58C Rate of rise heat detectorAreas subject to rapid changes During normal useLocation and Spacing of Automatic Fire Detectors Ceiling HeightDetector type To EN54-7 10.5m Heat detector conforming toCorridor being 7.5m and 5.3m respectively CorridorsSloping Ceilings Location and Spacing of Optical Beam Detectors Lantern LightsVoids and False Ceilings Audible Alarm Signals Visual Alarm SignalsMaintenance of Fire Detectors Codes and standards in the UK BS5839 Part 12002, SectionSeries 200 Plus Features General SpecificationsIntelligent Product Range Series 200 Plus Analogue Addressable Detector RangeWeight System Sensor Intelligent Product Range2251EM Photoelectric Smoke Sensor 2251TEM PHOTO-THERMAL SensorDrift Compensation and Smoothing 5251REM, 5251EM and 5251HTEM Heat SensorsRemote Test Switch 6500S Beam DetectorWeight 142g Operating Temperature -10C to 55CLaser Detector With LED blink enabled 2251EIS Intrinsically Safe Detector and IST200 InterfaceB500 Series Bases Weight 100g Interior diameterExterior diameter DepthM200 Series Module Range M200XE Short Circuit Isolator ModuleSpecifications Max Standby Current, externally powered zone M201E Output Module5A at 250VAC M210E-CZ Conventional Zone ModuleAccessories Call PointsIndoor Indoor products are generally rated at IP24DAudio Visual Products Detector Base SoundersSounder Strobes Majority of back box formatsOther Information Other Information Approval Bodies for Fire Detection ProductsAvenue Hoch Paris, France Tel +33 1 53 89 00 Jernholmen DK-2650 Hvidovre Denmark Tel +45 36 349System Sensor Fire Detectors Volochaevskaya Str 40, BldTelephone + 7 095 Telephone + 91 124 Fax + 7 095

BS5839 specifications

System Sensor BS5839 is a standard that pertains to fire detection and alarm systems, providing guidelines for the design, installation, and maintenance of these essential safety tools. It is crucial for safeguarding lives and property, ensuring that fire detection systems are effective and reliable. The BS5839 standard, established in the UK, covers a wide range of fire alarm system types, including conventional, addressable, and wireless systems.

One of the main features of BS5839 is its comprehensive classification of fire detection systems. The standard divides systems into categories based on the level of risk and the environment in which the system will operate. This classification helps ensure that the system installed meets the specific needs of the building and its occupants. For example, Category L systems are meant for life safety, while Category P systems are designed to protect property.

The technologies underpinning BS5839 include various types of detectors, alarm devices, and control panels. Smoke detectors, heat detectors, and multi-sensor detectors are prominent among the devices specified in the standard. Smoke detectors use photoelectric or ionization principles to detect smoke and signal an alarm, while heat detectors respond to temperature changes. Multi-sensor detectors combine both smoke and heat detection technologies to provide a more reliable response to fire conditions.

Another key characteristic of BS5839 is the emphasis on regular testing and maintenance. The standard outlines procedures to ensure that systems remain operational and effective over time. This includes routine system checks, functional testing, and more in-depth inspections at regular intervals. Ensuring that systems are maintained according to BS5839 is vital for compliance with insurance requirements and for safeguarding against potential legal liabilities.

Furthermore, BS5839 highlights the importance of staff training and awareness. It emphasizes that personnel responsible for fire safety must be adequately trained in the operation and response to fire alarm systems. This ensures that in the event of a fire, occupants are prompted to take appropriate action and evacuate safely.

In summary, System Sensor BS5839 provides a crucial framework for fire detection and alarm systems. Its classification of systems, incorporation of advanced technologies, and emphasis on maintenance all contribute to enhanced safety and compliance, protecting lives and property effectively.